TABLE 9– ELECTRIC HEAT DATA (1 PHASE) – CB30M–51 & CB30M–65
Blower Coil
Model
Electric Heat kW,
Model Number
Number of
St
Volts
I
t
kW
I
t
Btuh
I
t
Blower
Motor
{
Minimum Circuit Ampacity
Model
Number
Model Number
& Shipping Weight
Steps
Input
Input
Input
Motor
Amps
Circuit 1
Circuit 2
Circuit 3
b
208/230v–1 ph
b
ECB29-5
(28K31)
208
3.8
12,800
2.4
26
– – – –
– – – –
5 kW
(28K31)
ECB29-5CB
1 step
220
4.2
14,300
2.4
27
– – – –
– – – –
5 kW
ECB29-5CB
(28K32)
( k )
1 step
230
4.6
15,700
2.4
28
– – – –
– – – –
(
)
4 lbs. (2 kg)
240
5.0
17,100
2.4
29
– – – –
– – – –
ECB29-8
(28K33)
208
6.0
20,500
2.4
39
– – – –
– – – –
8 kW
(28K33)
ECB29-8CB
2 steps
220
6.7
22,900
2.4
41
– – – –
– – – –
8 kW
ECB29-8CB
(28K34)
( k )
2 steps
230
7.3
25,100
2.4
43
– – – –
– – – –
(
)
4 lbs. (2 kg)
240
8.0
27,300
2.4
45
– – – –
– – – –
ECB29-10
(28K35)
208
7.5
25,600
2.4
48
– – – –
– – – –
10 kW
(28K35)
ECB29-10CB
2 steps
220
8.4
28,700
2.4
51
– – – –
– – – –
10 kW
ECB29-10CB
(28K36)
( k )
2 steps
230
9.2
31,400
2.4
53
– – – –
– – – –
(
)
5 lbs. (2 kg)
240
10.0
34,100
2.4
55
– – – –
– – – –
208
9.4
32,000
2.4
22
38
– – – –
CB30M-51
CB30U 51
12 5 kW
ECB29-12.5CB
(28K37)
3 steps
220
10.5
35,800
2.4
23
40
– – – –
CB30U-51
12.5 kW
(28K37)
10 lbs. (5 kg)
3 steps
230
11.5
39,200
2.4
24
42
– – – –
10 lbs. (5 kg)
240
12.5
42,600
2.4
25
43
– – – –
208
11.3
38,400
2.4
26
45
– – – –
15 kW
ECB29-15CB
(28K38)
3 steps
220
12.6
43,000
2.4
27
48
– – – –
15 kW
(28K38)
10 lbs. (5 kg)
3 steps
230
13.5
47,000
2.4
28
49
– – – –
10 lbs. (5 kg)
240
15.0
51,200
2.4
29
52
– – – –
208
15.0
51,200
2.4
48
45
– – – –
20 kW
ECB29-20CB
(28K39)
4 steps
220
16.8
57,300
2.4
51
48
– – – –
20 kW
(28K39)
14 lbs. (6 kg)
4 steps
230
18.4
62,700
2.4
53
49
– – – –
14 lbs. (6 kg)
240
20.0
68,200
2.4
55
52
– – – –
208
18.8
64,100
2.4
41
38
38
25 kW
ECB29-25CB
(28K40)
5 steps
220
21.0
71,700
2.4
43
40
40
25 kW
(28K40)
18 lbs. (8 kg)
5 steps
230
23.0
78,300
2.4
45
42
42
18 lbs. (8 kg)
240
25.0
85,300
2.4
47
43
43
ECB29-5
(28K31)
208
3.8
12,800
3.9
28
– – – –
– – – –
5 kW
(28K31)
ECB29-5CB
1 step
220
4.2
14,300
3.9
29
– – – –
– – – –
5 kW
ECB29-5CB
(28K32)
( k )
1 step
230
4.6
15,700
3.9
30
– – – –
– – – –
(
)
4 lbs. (2 kg)
240
5.0
17,100
3.9
31
– – – –
– – – –
ECB29-8
(28K33)
208
6.0
20,500
3.9
41
– – – –
– – – –
8 kW
(28K33)
ECB29-8CB
2 steps
220
6.7
22,900
3.9
43
– – – –
– – – –
8 kW
ECB29-8CB
(28K34)
( k )
2 steps
230
7.3
25,100
3.9
45
– – – –
– – – –
(
)
4 lbs. (2 kg)
240
8.0
27,300
3.9
47
– – – –
– – – –
ECB29-10
(28K35)
208
7.5
25,600
3.9
50
– – – –
– – – –
10 kW
(28K35)
ECB29-10CB
2 steps
220
8.4
28,700
3.9
53
– – – –
– – – –
10 kW
ECB29-10CB
(28K36)
( k )
2 steps
230
9.2
31,400
3.9
55
– – – –
– – – –
(
)
5 lbs. (2 kg)
240
10.0
34,100
3.9
57
– – – –
– – – –
208
9.4
32,000
3.9
24
38
– – – –
12 5 kW
ECB29-12.5CB
(28K37)
3 steps
220
10.5
35,800
3.9
25
40
– – – –
12.5 kW
(28K37)
10 lbs. (5 kg)
3 steps
230
11.5
39,200
3.9
26
42
– – – –
CB30M-65
CB30U 65
10 lbs. (5 kg)
240
12.5
42,600
3.9
27
43
– – – –
CB30U-65
208
11.3
38,400
3.9
28
45
– – – –
15 kW
ECB29-15CB
(28K38)
3 steps
220
12.6
43,000
3.9
29
48
– – – –
15 kW
(28K38)
10 lbs. (5 kg)
3 steps
230
13.5
47,000
3.9
29
50
– – – –
10 lbs. (5 kg)
240
15.0
51,200
3.9
31
52
– – – –
208
15.0
51,200
3.9
50
45
– – – –
20 kW
ECB29-20CB
(28K39)
4 steps
220
16.8
57,300
3.9
53
48
– – – –
20 kW
(28K39)
14 lbs. (6 kg)
4 steps
230
18.4
62,700
3.9
55
50
– – – –
14 lbs. (6 kg)
240
20.0
68,200
3.9
57
52
– – – –
208
18.8
64,100
3.9
43
38
38
25 kW
ECB29-25CB
(28K40)
5 steps
220
21.0
71,700
3.9
45
40
40
25 kW
(28K40)
18 lbs. (8 kg)
5 steps
230
23.0
78,300
3.9
47
42
42
18 lbs. (8 kg)
240
25.0
85,300
3.9
48
43
43
208
22.5
76,900
3.9
50
45
45
30 kW
ECB29-30CB
(28K41)
5 steps
220
25.2
86,000
3.9
53
48
48
30 kW
(28K41)
19 lbs. (9 kg)
5 steps
230
27.5
94,000
3.9
55
50
50
19 lbs. (9 kg)
240
30.0
102,400
3.9
57
52
52
{
Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167
°
F (75
_
C).
Electric heater capacity only — does not include additional blower motor heat capacity.
Minimum circuit ampacity for blower motor only.
Summary of Contents for CB29M-21
Page 44: ...Page 44 NOTES...