Page 17
TABLE 6– ELECTRIC HEAT DATA (3 PHASE) – CB29M–41, CB29M–51 CB29M–65
Blower Coil
Model
Electric Heat kW,
Model Number
Number of
Volts
kW
**Btuh
D
Blower
Motor
*Minimum Circuit
Model
Number
Model Number
& Shipping Weight
Steps
Input
Input
Input
Motor
Amps
Ampacity
b
460v–3 ph
b
ECB29 10
440
8.4
28,700
1.3
15
10 kW
ECB29-10
(28K47)
12 lbs (5 kg)
3 steps
460
9.2
31,400
1.3
16
CB29M 41
12 lbs. (5 kg)
480
10.0
34,100
1.3
17
CB29M-41
ECB29 15
440
12.6
43,000
1.3
22
15 kW
ECB29-15
(28K48)
12 lbs (5 kg)
3 steps
460
13.8
47,000
1.3
23
12 lbs. (5 kg)
480
15.0
51,200
1.3
24
ECB29 10
440
8.4
28,700
1.9
16
10 kW
ECB29-10
(28K47)
12 lbs (5 kg)
3 steps
460
9.2
31,400
1.9
17
12 lbs. (5 kg)
480
10.0
34,100
1.9
17
ECB29 15
440
12.6
43,000
1.9
23
15 kW
ECB29-15
(28K48)
12 lbs (5 kg)
3 steps
460
13.8
47,000
1.9
24
CB29M 51
12 lbs. (5 kg)
480
15.0
51,200
1.9
25
CB29M-51
ECB29 20
440
16.8
57,300
1.9
30
20 kW
ECB29-20
(28K49)
18 lbs (8 kg)
3 steps
460
18.4
62,700
1.9
31
18 lbs. (8 kg)
480
20.0
68,200
1.9
32
ECB29 25
440
21.0
71,700
1.9
37
25 kW
ECB29-25
(28K50)
18 lbs (8 kg)
3 steps
460
23.0
78,300
1.9
39
18 lbs. (8 kg)
480
25.0
85,300
1.9
40
ECB29 10
440
8.4
28,700
2.3
17
10 kW
ECB29-10
(28K47)
12 lbs (5 kg)
3 steps
460
9.2
31,400
2.3
17
12 lbs. (5 kg)
480
10.0
34,100
2.3
18
ECB29 15
440
12.6
43,000
2.3
24
15 kW
ECB29-15
(28K48)
12 lbs (5 kg)
3 steps
460
13.8
47,000
2.3
25
CB29M 65
12 lbs. (5 kg)
480
15.0
51,200
2.3
25
CB29M-65
ECB29 20
440
16.8
57,300
2.3
30
20 kW
ECB29-20
(28K49)
18 lbs (8 kg)
3 steps
460
18.4
62,700
2.3
32
18 lbs. (8 kg)
480
20.0
68,200
2.3
33
ECB29 25
440
21.0
71,700
2.3
37
25 kW
ECB29-25
(28K50)
18 lbs (8 kg)
3 steps
460
23.0
78,300
2.3
39
18 lbs. (8 kg)
480
25.0
85,300
2.3
40
b
{
575v–3 ph
b
ECB29 20
550
16.8
57,300
{{
1.9
24
20 kW
ECB29-20
(28K51)
18 lbs (8 kg)
3 steps
575
18.4
62,700
{{
1.9
26
{
CB29M 51
18 lbs. (8 kg)
600
20.0
68,200
{{
1.9
26
{
CB29M-51
ECB29 25
550
21.0
71,700
{{
1.9
30
25 kW
ECB29-25
(28K52)
18 lbs (8 kg)
3 steps
575
23.0
78,300
{{
1.9
31
18 lbs. (8 kg)
600
25.0
85,300
{{
1.9
32
ECB29 20
550
16.8
57,300
{{
2.3
25
20 kW
ECB29-20
(28K51)
18 lbs (8 kg)
3 steps
575
18.4
62,700
{{
2.3
26
{
CB29M 65
18 lbs. (8 kg)
600
20.0
68,200
{{
2.3
27
{
CB29M-65
ECB29 25
550
21.0
71,700
{{
2.3
30
25 kW
ECB29-25
(28K52)
18 lbs (8 kg)
3 steps
575
23.0
78,300
{{
2.3
32
18 lbs. (8 kg)
600
25.0
85,300
{{
2.3
33
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167
°
F (75
_
C).
**Electric heater capacity only — does not include additional blower motor heat capacity.
D
Minimum circuit ampacity for blower motor only.
{
NOTE – ALL 575v ELECTRIC HEATERS ARE USED WITH CB29M-51 & CB29M-65 460v MODEL BLOWER COIL UNITS – A STEP-DOWN TRANSFORMER
FOR THE BLOWER COIL UNIT IS FURNISHED WITH ALL 575v ELECTRIC HEATERS.
{{
Blower motor is rated at 460v.
Summary of Contents for CB29M-21