background image

The duct system must be installed respecting 

the following:

1. Remove the plates closing up the 8” dia. holes 

on top of the fireplace.  Then, cut the insula-

tion in order to obtain two 8” dia. openings.  

Fix the adaptors on the fireplace openings 

by turning clockwise (

Figure 12

).

2. Maintain at least a 2” (50 mm) clearance 

between  the  ducts  and  any  combustible 

material; the required hole size is 13”  x  13” 

(330 mm x 330 mm).

  Exception #1:  For the grills, the fram-

ing can be 10-3/4” x 10-3/4” (275 mm 

x 275 mm) to provide the clearance as 

required by the integral spacers on the 

double outlet duct system.

3. The maximum number of elbows in a run 

of duct is two.

4. Maintain at least 6-1/2” (160 mm) clearance 

from the outlet grill framing to a combustible 

ceiling, side wall or mantel.

5. When traversing a combustible wall or floor, 

a firestop must be installed at the wall or 

floor  penetration.    The  hole  size  must  be 

13” X 13” (330 mm x 330 mm).

6. Do not connect the hot air ducts to a central 

heating system.  Malfunction of the heating 

system’s blower will cause the fireplace to 

overheat.  A furnace duct is only single wall 

and not double wall as is required for the 

Brentwood™ hot air exhaust.  

7. Use only Lennox Hearth Products grills and 

components as described in this manual. 

Other grills or registers, for example, may be 

too restrictive and may overheat the fireplace 

or ceiling.

8. Do not use insulated flexible ducts as they 

will overheat.

9. Do not use tees or any other components 

than the ones specifically listed here.

10. Never allow the ducting to pitch down as 

hot air will be trapped creating a fire hazard.  

Never route the ducting downwards

.

11. The hot air outlet grills must be installed with 

the louvers pointing downwards in order to 

prevent overheating adjacent ceilings.

12. Always install the two outlet grills when using 

the double hot air outlet kit and blocking the 

upper louver of the fireplace.

OUTSIDE AIR KIT

During operation, the fireplace requires fresh air for combustion and draws air out of the house.  

It may starve other fuel burning appliances such as gas or oil furnaces.  As well, exhaust fans may 

compete for air, causing negative pressure in the house, resulting in smoke entering the house from 

the fireplace. This situation is aggravated in modern airtight houses. To overcome this problem, we 

strongly recommend that you install an outside air assembly. Check with local authorities having 

jurisdiction in your area, it may be mandatory.

Note: Should you decide not to install the outside air assembly, proceed as follows:

-  Remove the bottom grill. The air box is located on front left and is on a slant. 

-  Unscrew the four screws holding the inside air box covering plate and remove it.

Outside Air Installation

The outside air assembly may be installed according to the following requirements:

A) Duct length should be kept to a minimum.  The maximum length of duct is twenty (20) feet (6.1 

m) for a 4 in. dia. pipe (See note below).

B) The air intake register must not be installed more than ten (10) feet (3050 mm) above the base 

of the fireplace.

C) The fresh air must come from outside the house.  The air intake must not draw air from the 

attic, from the basement or garage.

D) The air intake should be installed where it is not likely to be blocked by snow or exposed to 

extreme wind and away from automobile exhaust fumes, gas meters and other vents.

E) The duct and register may be installed above or below floor level.

The following components are required:

-  Outside air kit (UZI)  (includes 40 inch flex that goes up to ten (10) feet long)

-  4” Adaptor for fireplace connection (supplied with the unit)

Make a 4-1/4” (110 mm) hole in the outside wall of the house at the chosen location. From outside, 

place the outside air register in the hole (open side down) and fasten the register to the wall, with 

screws as shown (see 

Figure 15

).  Slip the pipe into the insulated sleeve.  Place the insulated pipe 

over the register tube and over the fireplace’s outside air connector (see

 Figure 16

). At each end, 

carefully pull back the insulation and plastic cover exposing the flexible pipe.  Using the aluminium 

tape provided, wrap the tape around the joint between the flexible pipe and the air inlets.  Carefully 

push the insulation and plastic cover back over the pipe.  Using aluminium tape, fasten the plastic 

cover in place.

Note: 

We recommend not to exceed 20 feet of 4” flexible pipe.  If you require a longer length we 

recommend that you use a 5” diameter flexible pipe for the complete run up to 30 feet and a 6” 

diameter pipe for a run of up to 40 feet.

Figure 15

OUTSIDE CONNECTION

Outside

Intake

Screw

Opening

Facing

Down

Wall

Aluminum Tape

Plastic Cover

Insulation

Flexible Pipe

Aluminum Tape

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

12

Summary of Contents for BRENTWOOD SP

Page 1: ...LATION AND OPERATION INSTRUCTIONS Listed to standards ULC S610 UL 127 Report No 3011202 EPA Cert No 537 RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE WARNINGS Hot Do not touch The glass and surfaces...

Page 2: ...ength to be blown in front of an open flame when the window is opened Keepanycombustiblefurniture materials or decorative pillows at least 48 1219 mm from the front fireplace opening WARNING Nevermodi...

Page 3: ...el Brentwood SP 6 diameterchimney model ASHT S 2100 HT6000 HT6103 orACmanufacturedbySe curity Chimneys International only including Chimney lengths Elbows where necessary Associated components as per...

Page 4: ...factors including chimney length and the moisture content of the wood For instance a long chimney will necessitate closing the damper more To obtain the proper combustion closethedampercompletely then...

Page 5: ...ntenance combined with proper operation will prevent chimneyfires Keepyourchimneyclean Donot allow more than 1 16 1 6 mm creosote build upinyourchimney Theamountofcreosotewill depend on variables such...

Page 6: ...tory If the fit is still not perfect you can adjust the door using the hinge screws Figure 3 Figure 4 DOOR ADJUSTMENT The door may need to be adjusted to be completely airtight The gaskets air tightne...

Page 7: ...dealer in the following dimensions Figure 5 FIREPLACE INSTALLATION Locating The Brentwood A The best location to install your fireplace is determined by consider ing the location of windows doors and...

Page 8: ...e fireplace and wherever cold air could enter the room with noncombustible material Also the outside air inlet duct should be wrapped with noncombustible in sulation to minimize the formation of conde...

Page 9: ...Mantel The mantel must be installed at least 45 1143 mm above the base of the fireplace Figure 9 Figure 9 Figure 10 Roof Support Attic Radiation Shield Firestop 7 Feet Min 1 2 Plywood 2 x 4 Drywall No...

Page 10: ...The fireplace facade can be covered with non combustible material Figure 14 For safe installation the gravity kit must meet the following requirements Minimum height 68 1 727 mm Maximum length See Fig...

Page 11: ...Facing 13 x 13 10 Max 10 Max Maintain at least 6 1 2 160mm clearancefrom the outlet grill framing to a combustible ceiling side wall or mantel Outlet Grill Outlet Grill WARNING The outlet grills shoul...

Page 12: ...ome this problem we strongly recommend that you install an outside air assembly Check with local authorities having jurisdiction in your area it may be mandatory Note Should you decide not to install...

Page 13: ...eplace Connection Plastic Cover Insulation Flexible Pipe Fireplace OUTSIDE AIR CONNECTION TO THE FIREPLACE Figure 16 THE CHIMNEY system Chimney Installation Notes 1 Alwaysinstallaninteriorchimneyasitw...

Page 14: ...nd seal the joint between the roof and the flashing with roofing pitch see Figures 21 22 For sloping roofs place the flashing under the upper shingles and on top of the lower shingles Nail the flashin...

Page 15: ...the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From below install a firestop See...

Page 16: ...A 4 13 16 122 mm 6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm...

Page 17: ...n the home s thermal barrier RSM and RSMI30 RSMI45 Canada Only Chimney Model Angle Hole Size ASHT HT6103 6 dia Canada only 30 283 mm x 781 mm 11 1 8 x 30 3 4 45 283 mm x 518 mm 11 1 8 x 20 3 8 S 2100...

Page 18: ...PPORTED CHIMNEY OffsetSupport RoofSupport ASHT HT6103 6 dia 28feet 8 54m 29feet 8 84 m S 2100 HT6000 6 dia 18feet 5 49m 20feet 6 1 m AC 6 dia 40feet 12 19m 50feet 15 20 m Table 6 CHIMNEY CHASE AND MUL...

Page 19: ...er the masonry chimney 2 In the middle of the oval drill a hole in the masonry chimney at 30 3 Increase the size of the hole until a or 30 TUBINOX liner elbow can be easily slipped through 4 Slide the...

Page 20: ...SS 6 diameter with adaptor for installation in a masonry chimney Secure Temp ASHT 1 High Temp Insulated Stainless Steel Chimney 6 I D 8 O D Double Wall Stainl Steel Listed to CAN UCL S604 UL 103HT De...

Page 21: ...f Flashing FB H0496 Storm collar ACFC H0500 Misc Telescopic attic radiation shield ACRST H0498 Firestop ACBF H0485 Radiation Shield ACRS H0486 Attic Radiation Shield ACRSA H0487 Insulated Wall Radiati...

Page 22: ...PR SR2202D Front Refractory Left Side Ash Lip PR SR2202G Door Handle PR SR1787 Ceramic Glass Panel PR SR2222 1 Secondary Air Tube PR SR2271 Cast iron Log Retainer Supports Grate 2 PR SR2324 Cast Iron...

Page 23: ...or repair components will be shipped F O B the nearest LHP factory QUALIFICATIONS TO THE WARRANTY The complete fireplace Warranty outlined above is further subject to the following qualifications 1 T...

Page 24: ...arth Products dealer please call 1 800 9 LENNOX Replacement parts See Page 22 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be ordered...

Reviews: