BALTIC-IOM-0412-E / Installation manual
THERMODYNAMIC HEAT RECOVERY - SERVICE MANUAL
3. SERVICE DIAGNOSTIC
Refrigeration
Fault
Possible causes and symptoms
Solution
Low LP and LP cut out
Alarm 317: main frigori
fi
c issue
Lack of charge, obstructed components
Alarm 327: too low LP
Freezing: wait that coil is defrosted by
exhaust air;
Air
fl
ow too low on evaporating side (too low
speed rate / fouled
fi
lter or coil).
HP problem and HP cut out
Incorrect air
fl
ow rates
Check fan (exhaust or supply) function of
the mode (Amps) and also
fi
lter.
Refrigerant charge too high
Check the refrigerant charge load according
to the refrigerant load table.
See also frigori
fi
c diagnostic of BALTIC™ III section 'Refrigeration'.
Indoor or exhaust fan blower:
For both indoor supply fan and exhaust fan, same faults, causes and solutions than for BALTIC™ III are expected. See diagnostic of
BALTIC™ III 'Indoor fan blower'.
4. SPARE PARTS LIST
Refrigeration components R410a
Designation
Family
Code
Compressor
Comp.
Comp.
Comp.
Indoor coil
ID C-box TRMO
Coil
ID D-box TRMO
Coil
ID E-box TRMO
Coil
Exhaust coil
Exhaust coil TRMO
Coil
Exhaust coil TRMO
Coil
Exhaust coil TRMO
Coil
Expansion valve
Refrig.
Refrig.
4 way valve
Refrig.
4 way valve coil
Refrig.
HP pressostat
Refrig.
HP sensor
Refrig.
LP sensor
Refrig.
Electrical & control components
Designation
Family
Code
CLIMATIC™ extension
Control
Connector for BE60
Control
Summary of Contents for BAC 024 SNM 3M
Page 2: ......
Page 4: ......
Page 76: ...72 BALTIC IOM 0412 E Service manual...
Page 98: ...94 BALTIC IOM 0412 E Certificates CE CONFORMITY DECLARATION...
Page 99: ...95 BALTIC IOM 0412 E Certificates CE CONFORMITY DECLARATION...