background image

506318-03

Page 16 of 18

Issue 1946

Maintenance

Regular Maintenance Requirements

Your system should be regularly inspected by a qualified 

service technician. These regular visits may include 

(among other things) checks for:
•  Motor operation
•  Ductwork air leaks
•  Coil & drain pan cleanliness (indoor & outdoor)
•  Electrical component operation & wiring check
•  Proper refrigerant level & refrigerant leaks
• 

Proper airflow

•  Drainage of condensate
• 

Air filter(s) performance

•  Blower wheel alignment, balance & cleaning
•  Primary & secondary drain line cleanliness
•  Proper defrost operation (heat pumps)

Air Filter

Inspect air filters at least monthly and replace or clean as 

required. Disposable filters should be replaced. Washable 

filters  may  be  cleaned  by  soaking  in  mild  detergent  and 

rinsing with cold water. Allow filter to dry before reinstalling.  

Replace filters with the arrows pointing in the direction of 

airflow.  Dirty  filters  are  the  most  common  cause  of  poor 

heating / cooling performance and compressor failures.

Indoor Coil

If the system has been operated with a clean filter in place, 

it should require minimal cleaning. If cleaning is needed, 

call your dealer for service.

Condensate Drain

During cooling season check at least monthly for free flow 

of drainage and clean if necessary.

Condenser Coils

Grass cuttings, leaves, dirt, dust, lint from clothes dryers, 

and foliage from trees can be drawn into coils by movement 

of the air. Clogged condenser coils will lower the efficiency 

of your unit and could cause damage to the condenser. 
Periodically, debris should be brushed from the condenser 

coils. Use a soft bristle brush with light pressure only. DO 

NOT  damage  or  bend  condenser  coil  fins.  Damaged  or 

bent fins may affect unit operation.

SHARP OBJECT HAZARD!

Condenser coils have sharp edges. Wear adequate 

body protection on body extremities (e.g. gloves).

FAILURE TO FOLLOW THIS WARNING COULD 

RESULT IN BODILY INJURY.

 WARNING

Painted Surfaces

For maximum protection of the unit’s finish, a good grade 

of automobile wax should be applied every year. In 

geographical areas where water has a high concentration 

of minerals (calcium, iron, sulfur, etc.), it is recommended 

that lawn sprinklers not be allowed to spray the unit. In 

such applications, the sprinklers should be directed away 

from the unit. Failure to follow this precaution may result 

in  premature  deterioration  of  the  unit  finish  and  metal 

components.
In sea coast areas, special maintenance is required due 

to the corrosive atmosphere provided by the high salt 

concentration in ocean mists and the air. Periodic washing 

of all exposed surfaces and coil will add additional life to 

your unit. Please consult your installing dealer for proper 

procedures in your geographic area.

Homeowner Information

ELECTRICAL SHOCK HAZARD!

Turn OFF electric power to unit before performing any 

maintenance or removing panels or doors.

FAILURE TO DO SO COULD RESULT IN BODILY 

INJURY OR DEATH.

 WARNING

Heat Pump Operation

Your new heat pump has several characteristics that you 

should be aware of:
•  Heat pumps satisfy heating demand by delivering large 

amounts of warm air into the living space. This is quite 

different  from  gas-or  oil-fired  furnaces  or  an  electric 

furnace which deliver lower volumes of considerably 

hotter air to heat the space.

•  Do not be alarmed if you notice frost on the outdoor coil 

in the winter months. Frost develops on the outdoor 

coil during the heating cycle when temperatures are 

below 45°F. An electronic control activates a defrost 

cycle lasting 5 to 15 minutes at preset intervals to clear 

the outdoor coil of the frost.

Summary of Contents for 4HP14

Page 1: ...alified personnel and do not supersede any national or local codes in any way The installation must comply with all provincial state and local codes as well as the National Electrical Code U S or Cana...

Page 2: ...nstalled on a solid foundation This foundation should extend a minimum of 2 inches beyond the sides of the outdoor section To reduce the possibility of noise transmission the foundation slab should NO...

Page 3: ...l or other barrier Table 2 Clearances 30 around Control Box 24 6 NOTE See Table 2 for specific minimum clearance guidelines Figure 2 DO LOCATE THE UNIT With proper clearances on sides and top of unit...

Page 4: ...8 042 3 8 3 8 7 8 7 8 048 3 8 3 8 7 8 7 8 060 3 8 3 8 7 8 1 1 8 Field supplied 7 8 x 1 1 8 connector required on both ends of vapor tubing Table 3 Recommended Liquid Vapor Tube Diameters in Be extra c...

Page 5: ...UNIT VAPOR LINE SERVICE VALVE VAPOR LIQUID 1 A B C D A Cylinder with clean R 410A positioned to deliver liquid refrigerant to the vapor service valve B Refrigerant gauge set low side to the liquid lin...

Page 6: ...il Shown Sensing bulb insulation is required if mounted external to the coil casing sensing bulb installation for bulb positioning STUB END TEFLON RING LIQUID LINE ASSEMBLY WITH BRASS NUT DISTRIBUTOR...

Page 7: ...ound Do not crimp end of the line Remove service cap and core from both the vapor and liquid line service ports 1 2 LIQUID LINE SERVICE VALVE SERVICE PORT CORE SERVICE PORT CAP SERVICE PORT CORE SERVI...

Page 8: ...ES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WRAP SERVICE VALVES To help protect service valve seals during brazing wrap water saturated cloths around service valve bodies and co...

Page 9: ...of the manifold gauge set in order to pressurize the line set and the indoor unit E After a few minutes open one of the service valve ports and verify that the refrigerant added to the system earlier...

Page 10: ...id refrigerant Open the manifold gauge valve 1 to 2 psig in order to release the vacuum in the line set and indoor unit G Perform the following Close manifold gauge valves Shut off HFC 410A cylinder R...

Page 11: ...nch with a hex head extension to back the stem out counterclockwise as far as it will go Use a 3 16 hex head extension for liquid line service valves and a 5 16 extension for suction line service valv...

Page 12: ...the low voltage field wiring 2 Ground unit at unit disconnect switch or to an earth ground To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box using a...

Page 13: ...or varying lengths of line set refer to Table 4 for refrigerant charge adjustment A blank space is provided on the unit rating plate to list the actual field charge Table 4 Refrigerant Charge Adjustme...

Page 14: ...for 90 seconds following the start up of the compressor during test mode High Pressure Switch HI PS When the high pressure switch trips the defrost board will cycle off the compressor and the strike c...

Page 15: ...ition at power up the control will ignore the test pins When the jumper is placed across the TEST pins for 2 seconds the control will enter the defrost mode If the jumper is removed before an addition...

Page 16: ...ent fins may affect unit operation SHARP OBJECT HAZARD Condenser coils have sharp edges Wear adequate body protection on body extremities e g gloves FAILURE TO FOLLOW THIS WARNING COULD RESULT IN BODI...

Page 17: ...he defrost cycle In case of extended power outage If the outdoor temperature is below 50 F and power to your outdoor unit has been interrupted for one hour or longer observe the following when restori...

Page 18: ...506318 03 Page 18 of 18 Issue 1946 Figure 8 14 15 SEER Wiring Diagram...

Reviews: