background image

# 48392M005

Page 5

Figure 5

Electrical Access

Heater Power Entry

Thermostat

Entry

Line Voltage

Entry

Unit must be grounded in accordance with
national and local codes. Failure to ground unit
properly can result in personal injury or death.

  WARNING

Power supply to the unit must be N.E.C. Class 1, and must
comply with all applicable codes. A fused disconnect switch
should be field provided for the unit. The switch must be
separate from all other circuits.

If any of the wire supplied with the unit must be replaced,
replacement wire must be of the type shown on the wiring
diagram. Electrical wiring must be sized to carry minimum
circuit ampacity marked on the unit. 

Use copper conduc-

tors only.

 Each unit must be wired with a separate branch

circuit and be properly fused.

Figure 6

Typical Wiring Connections

R

R

C

C

C

C

R

R

L2

L1

Y

Y

Y1

Y

L1

L2

L3

POWER WIRING

208/230-1-60

(90°C MIN. WIRE)

POWER WIRING

24V CONTROL WIRING

(NEC CLASS 2)

TYPICAL WIRING CONNECTION

1 PHASE

GROUND
SCREW

THERMOSTAT

OUTDOOR UNIT

THERMOSTAT

OUTDOOR UNIT

GROUND
SCREW

POWER WIRING

200/230-3-60, 460/575-3-60

(90°C MIN. WIRE)

24V CONTROL WIRING

(NEC CLASS 2)

POWER WIRING

TYPICAL WIRING CONNECTION

3 PHASE

* W1, W2 CAN BE USED TO STAGE ELECTRIC

HEAT ACCESSORY ON

MODELS.

15 & 20 KW

* 5 & 10 KW HEATER ACCESSORY FUNCTION

W1 ONLY.

OFF

* W1, W2 CAN BE USED TO STAGE ELECTRIC

HEAT ACCESSORY ON 15 & 20 KW MODELS.

* 10 KW HEATER ACCESSORY FUNCTION OFF

W1 ONLY.

ECONOMIZER

NOT

INSTALLED

ECONOMIZER

W1

W

W

W1

G

G

G

G

W2

Y2

W2

BLUE

WHITE

YELLOW

GREEN

BLACK

Do not connect        connections except when

required by the indoor thermostat. Refer to the

thermostat installation instructions.

C

CAUTION

Do not connect        connections except when

required by the indoor thermostat. Refer to the

thermostat installation instructions.

C

CAUTION

Thermostat

The room thermostat should be located on an inside wall
where it will not be subject to drafts, sun exposure, or heat
from electrical fixtures or appliances. Follow the

Summary of Contents for 2SA13 Series

Page 1: ...lation of this appliance must conform to the requirements of the National Fire Protection Association the National Electrical Code ANSI NFPA No 70 latest edition in the United States the Canadian Elec...

Page 2: ...THE UNIT as claim may be denied Check the unit rating plate to confirm specifications are as ordered Limitations The unit should be installed in accordance with all national and local safety codes Lim...

Page 3: ...roper operation and service Refer to Table 1 for the minimum clearances to combustibles as well as minimum clearances necessary for servicing and proper unit operation In the U S units may be installe...

Page 4: ...0 6 7 6 6 When connecting electrical power and control wiring to the unit waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation CAUTIO...

Page 5: ...0 90 C MIN WIRE POWER WIRING 24V CONTROL WIRING NEC CLASS 2 TYPICAL WIRING CONNECTION 1 PHASE GROUND SCREW THERMOSTAT OUTDOOR UNIT THERMOSTAT OUTDOOR UNIT GROUND SCREW POWER WIRING 200 230 3 60 460 57...

Page 6: ...common venting system are not in operation 1 Seal any unused openings in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no...

Page 7: ...ng air blower is controlled by a timing circuit in the blower control Timings are not adjustable There is no blower on delay after a call for heating or cooling Blower off delay is 90 seconds after th...

Page 8: ...nd outdoor fan and vent motors are permanently lubricated and require no maintenance Outdoor Coil Dirt and debris should not be allowed to accumulate on the outdoor coil surface or other parts in the...

Page 9: ...R R R XFMR C FUSE Y A15 BLOWER GRN RED BLU BLU YEL BLU W1 W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 15 20KW MODELS 5 7 5 10KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK BLK WHT P 1 P 2 P 4 P...

Page 10: ...and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to assume for it any further obligation in connection with the warran...

Reviews: