background image

# 48392M005

Page 3

Before lifting a unit, make sure that the weight
is distributed equally on the cables so that it
will lift evenly.

 CAUTION

Roof Curb Assembly

Figure 2

Units may also be moved or lifted with a forklift while still
in the factory-supplied packaging. 

The lengths of the

forks of the forklift must be a minimum of 42".

Ductwork

Ductwork should be designed and sized according to the
methods in Manual Q of the Air Conditioning Contractors of
America (ACCA).

A closed return duct system shall be used. This shall not
preclude use of economizers or outdoor fresh air intake. It
is recommended that supply and return duct connections
at the unit be made with flexible joints.

Unit

Drain Connection

Positive Liquid Seal Required

3.00" Min.

1.00" Min.

12.00"

Max.

Typical Condensate Drain Connection

Figure 3

Roof Curb Installation

If a roof curb is used, follow the manufacturer

s Installation

Instructions and be sure that all required clearances are
observed (see following 

Clearances

 section).

Clearances

All units require certain clearances for proper operation and
service. Refer to Table 1 for the minimum clearances to
combustibles as well as minimum clearances necessary
for servicing and proper unit operation.

In the U.S., units may be installed on combustible floors
made from wood or class A, B, or C roof covering material.
In Canada, units may be installed on combustible floors.

Service Access

Access to all serviceable components is provided by four
removable panels: filter compartment, blower compart-
ment, heater compartment, and top panel.

Condensate Drain

The SA package unit is equipped with a 3/4" FPT coupling
for condensate line connection. Plumbing must conform to
local codes. Use a sealing compound on male pipe threads.

The condensate drain line must be properly trapped
and routed to a suitable drain.

 See Figure 3 for proper

drain arrangement. The drain line must pitch to an open
drain or pump to prevent clogging of the line. Seal around
the drain connection with suitable material to prevent air
leakage into the return air system.

Table 1

o

T

e

l

b

i

t

s

u

b

m

o

C

l

a

i

r

e

t

a

M

r

o

F

e

c

i

v

r

e

S

r

o

F

r

e

p

o

r

P

n

o

i

t

a

r

e

p

O

t

n

o

r

F

"

0

"

8

4

"

3

r

a

e

R

"

0

"

4

2

"

3

r

e

s

n

e

d

n

o

C

d

n

E

"

0

"

4

2

"

3

r

e

w

o

l

B

d

n

E

"

0

"

0

3

"

0

p

o

T

"

0

"

6

3

"

6

3

Minimum Clearance Requirements

Summary of Contents for 2SA13 Series

Page 1: ...lation of this appliance must conform to the requirements of the National Fire Protection Association the National Electrical Code ANSI NFPA No 70 latest edition in the United States the Canadian Elec...

Page 2: ...THE UNIT as claim may be denied Check the unit rating plate to confirm specifications are as ordered Limitations The unit should be installed in accordance with all national and local safety codes Lim...

Page 3: ...roper operation and service Refer to Table 1 for the minimum clearances to combustibles as well as minimum clearances necessary for servicing and proper unit operation In the U S units may be installe...

Page 4: ...0 6 7 6 6 When connecting electrical power and control wiring to the unit waterproof type connectors must be used so that water or moisture cannot be drawn into the unit during normal operation CAUTIO...

Page 5: ...0 90 C MIN WIRE POWER WIRING 24V CONTROL WIRING NEC CLASS 2 TYPICAL WIRING CONNECTION 1 PHASE GROUND SCREW THERMOSTAT OUTDOOR UNIT THERMOSTAT OUTDOOR UNIT GROUND SCREW POWER WIRING 200 230 3 60 460 57...

Page 6: ...common venting system are not in operation 1 Seal any unused openings in the common venting system 2 Visually inspect the venting system for proper size and horizontal pitch and determine there is no...

Page 7: ...ng air blower is controlled by a timing circuit in the blower control Timings are not adjustable There is no blower on delay after a call for heating or cooling Blower off delay is 90 seconds after th...

Page 8: ...nd outdoor fan and vent motors are permanently lubricated and require no maintenance Outdoor Coil Dirt and debris should not be allowed to accumulate on the outdoor coil surface or other parts in the...

Page 9: ...R R R XFMR C FUSE Y A15 BLOWER GRN RED BLU BLU YEL BLU W1 W2 CAN BE USED TO STAGE ELECTRIC HEAT ACCESSORY ON 15 20KW MODELS 5 7 5 10KW HEATER ACCESSORIES FUNCTION OFF W1 ONLY BLK BLK WHT P 1 P 2 P 4 P...

Page 10: ...and excludes all other warranties express or implied The warrantor does not authorize any person to provide any other warranty or to assume for it any further obligation in connection with the warran...

Reviews: