Page 9
Table 7.
Seven-Segment Status Display
Operation
Description
Idle Mode:
Decimal point blinks at 1 Hz
Decimal point blinks at 1 Hz (0.5 second on, 0.5 second off). Display OFF.
Soft Disabled
Top & Bottom horizontal line and decimal point blink at 1
Hz
Top & Bottom horizontal line and decimal point blink at 1 Hz (0.5 second on, 0.5 sec-
ond off). See additional information below this table.
OEM Test Mode
All segments flashing at 2 Hz (unless error is detected)
Electrical Heating stage
Shows number of currently active electric heat pilot relays.
Following string is repeated if one stage Heat is active with 850 CFM:
H 1 pause A 8 5 0 pause
Cooling Stage
Shows what stage of cooling is currently operating.
Following string is repeated if second stage cooling is active with 1235 CFM:
C 2 pause A 1 2 3 5 pause
Heat Pump Stage
Shows what stage of heat pump is currently operat ing.
Following string is repeated if first stage heat pump is active with 925 CFM and no
Electri cal Heat:
h 1 pause H 0 pause A 9 2 5 pause
Heat pump & electrical heating stage
Shows current heat pump operating stage and number of
active electric heat pilot relays.
Following string is repeated if one stage electrical heat and second stage heat pump is
active with 600 CFM:
h 1 pause H 1 pause A 1 6 5 0 pause
Defrost Mode
Shown only while in an active defrost. (Simultaneous Y, W,
and O)
Following string is repeated if defrost is active with two electrical heat stages active
and 975 CFM:
d f pause H 2 pause A 9 7 5 pause
Dehumidification mode
Shows that the unit is providing dehumidification in
stead of straight cooling.
Following string is repeated if dehumidification is active with 685 CFM:
d pause A 6 8 5 pause
Indoor Blower only (G demand)
Shows the current CFM delivery of the main blower in
actual CFM.
If indoor blower is providing 1600 CFM: following string is repeated:
A 1 6 0 0 pause
Diagnostic recall
Shows the last 10 stored diagnostic error codes. Ini tiated
by a 2-second button press. Button press inter rupts the
current display pattern. After all codes are displayed,
current display status will resume opera tion.
If first error is 250, second 231:
E pause 2 5 0 pause E pause 2 3 1
Next codes (up to 10) are show using same method.
If there is no error codes stored:
E pause 0 0 0
Fault Memory clear
After the fault memory is cleared following string is displayed with 0.5 seconds charac-
ter on/off time:
0 0 0 0 pause
Active Error in AHC Idle mode
Shown all active error(s) codes
Following string is repeated if Error E125 and E201 are present:
E1 2 5 pause E 2 0 1
Active Error in Run Mode
Shown current status and all active error(s) codes
Following string is repeated if Error E311 is present while blower aped at 880CFM:
A 8 8 0 pause E 3 1 1
Discharge Air Temperature Sensor (DATS)
Any time DAT is sensed in operating range value is dis-
played if indoor blower is running.
Following string is repeated if three stage el. heat is active with 850 CFM & DAT is
104° F:
H 3 pause A 8 5 0 pause U 1 0 4 pause
Soft Disable
Steps to follow if the damper control module is displaying the soft disable code:
1.
Confirm proper wiring between all devices
(Thermostat, damper control module,
indoor and outdoor)
2. Cycle power to the control that is displaying the soft disable code.
3. Put the room thermostat through Set Up.
4. Go to
setup / system devices / thermostat / edit / push reset
.
5. Go to
setup / system devices / thermostat / edit / push resetAll.