Page 19
Configuring Unit
This section identifies the requirements for configuring the air handler in non-communicating mode for unit size, heat mode
selection and EvenHeat. For communicating configuration see the iComfort
®
installation instruction.
c
heckout
Air Handler
Control Checkout
Power-up- Unit Size Code (Number or letter) displayed
represents unit size code (air handler model size and capacity).
If three horizontal bars displays, air handler control (AHC) does
not recognize unit size code (air handler model size and
capacity).
AHC
recognizes
Unit Size
Code?
Electric
heat
Installed?
Finished
Which
Heat
Mode
?
Refer to EVENHEAT operation flow diagram, air handler or
ECB40 Electric Heat installation instructions.
W1 Call?
Yes
No
Yes
Standard
EVENHEAT
Refer to
Heat Pump
or
Cooling
Sequence of Operation
flow
diagrams, Air Handler or ECB40
Electric
Heat
installation
instructions.
A call for electric heating first, second or third stage is
initiated when 24 VAC (R) is detected on W1, W2 and
W3 inputs on AHC. (Factory mounted metal jumpers
connect W1 to W2 and W2 to W3.)
At the completion of each heat section demand (W1,
W2, and W3), the control board will immediately
de-energize the corresponding pilot relay(s).
At the completion of all heating demands, the indoor
blower will run for an additional 10 seconds before
de-energizing.
No
Yes
NOTE - If the call for lower heat section is removed,
AHC will automatically de-energize higher heat
sections.
Indoor blower will immediately start to delivery CFM as
set by heating mode jumper on board with activation of
first electric heat pilot relay.
22 VDC pilot relays on board are energized one at a
time. There is a minimum of 10 seconds delay between
pilot relay activations.
After all electric heat installations, AHC must be
manually configured to detect number of heat sections.
Refer to Configuring/Detecting electric heat sections
flow diagram, Air Handler or ECB40 Electric Heat
installation
IMPORTANT
: Field replacement controls
MUST be manually configured to validate
air handler unit size code.
Refer to
Configuring Unit Size Codes
flow
diagram, Air Handler or ECB40 Electric Heat
installation instructions.
ONE (H1)
H1
TWO (H1-H2)
H1
H2
H2
THREE
(H1-H3)
H1
H2
H3
FOUR (H1-H4)
H1 AND H2
H3
H4
FIVE (H1-H5)
H1 AND H2
H3 AND H4
H5
T-STAT CALL
W1
W2
W3
NUMBER OF HEAT SECTIONS DETECTED
NOTE - AHC will not recognize higher heat section
demand if lower heat demand is not present.
AIR HANDLER CONTROL (AHC)
PUSH
BUTTON
No (Display
Alarm Code 302)
SINGLE
CHARACTER
DISPLAY
Figure 6. Checkout