Non−Communicating System
The unit will operate based on jumper and link settings on
the control. All setting changes must be done at the control
board. The Lennox ComfortSense
®
7500 thermostat may be
used, as well as other non−communicating thermostats.
Communicating System
The jumper and link settings are default settings and ONLY
control system operation if configuration settings in the iComfort
thermostat are not available. The Lennox iComfort
®
thermostat
must be used in communicating applications.
STEP 2
STEP 1
NOTE − Error code troubleshooting is included in all kit and unit installation instructions.
MAIN CONTROL Set−up
Use the procedures provided in this instruction or that of the
unit installation instruction.
Set jumpers and clip links to match parameters of equipment
Unit Size Code
See Figure 7 for details on this procedure.
Set Unit Size Code by following configuration procedure
provided in this instruction or unit installation instructions.
Configure Electric Heat
Configuring / Detecting Electric Heat Section .
System Operation Configuration
Confirm or configure system operation using iComfort
®
Thermostat Installer System Setup Guide.
Configure Electric Heat
Indoor Unit NEW MAIN CONTROL Catalog Number
Verify OLD CONTROL jumper settings, links and wiring connections. Use
the same settings and wiring connections for the NEW CONTROL. See
Figure 10 for location of jumpers and loop location.
Remove OLD MAIN CONTROL
Install NEW MAIN CONTROL
Transfer OLD CONTROL wire connections to NEW CONTROL
(See figure 3 in this instruction for location of single
character display, push button, jumpers and links.)
AIR HANDLER CONTROL (AHC)
AIR HANDLER CONTROL (AHC)
REPLACEMENT PROCEDURE
®
See Figure 8 for details on this procedure.
CBA38MV − Kit # 16B27
TURN OFF ALL POWER TO UNIT BEFORE SERVICING
Configuring System
During configuration, this pop-up
will confirm that model and serial
number have been copied to the
new control board.
Air Handler Control has the ability to detect the number of field-
installed electric heat stages present. The manual process for
detecting electric heat is outlned in Figure 8.
Configuring / Detecting Electric Heat Section .
CBX40UHV /
CBX32MV /
Figure 2. Replacement Procedure