background image

Page 21

Indoor Unit 

1. Clean or change filters. 
2.  Lennox  blower  motors  are  prelubricated  and  perma

-

nently sealed. No more lubrication is needed. 
3. Adjust blower speed for cooling. Measure the pressure 

drop over the coil to determine the correct blower CFM. 

Refer to the unit information service manual for pressure 

drop tables and procedure. 
4. Belt Drive Blowers - Check belt for wear and proper 

tension. 
5. Check all wiring for loose connections. 
6. Check for correct voltage at unit. (blower operating) 
7. Check amp draw on blower motor. 

Motor Nameplate:_________ Actual:__________. 

Indoor Coil 

1 -  Clean coil if necessary. 
2 -   Check connecting lines, joints and coil for evidence 

of oil leaks. 

3 -  Check condensate line and clean if necessary. 

HOMEOWNER

 

Cleaning of the outdoor unit's coil should be performed by 

a trained service technician. Contact your dealer and set 

up a schedule (preferably twice a year, but at least once a 

year) to inspect and service your outdoor unit. The follow-

ing maintenance may be performed by the homeowner.

 IMPORTANT

Sprinklers and soaker hoses should not be installed 

where they could cause prolonged exposure to the 

outdoor unit by treated water. Prolonged exposure 

of the unit to treated water (i.e., sprinkler systems, 

soakers, waste water, etc.) will corrode the surface of 

the steel and aluminum parts, diminish performance  

and affect longevity of the unit. 

Outdoor Coil 

The outdoor unit must be properly maintained to ensure 

its proper operation. 
•   Please contact your dealer to schedule proper inspec-

tion and maintenance for your equipment. 

• 

 Make sure no obstructions restrict airflow to the outdoor unit. 

•   Grass clippings, leaves, or shrubs crowding the unit can 

cause the unit to work harder and use more energy. 

•   Keep shrubbery trimmed away from the unit and peri-

odically check for debris which collects around the unit. 

Routine Maintenance 

In order to ensure peak performance, your system must 

be properly maintained. Clogged filters and blocked airflow 

prevent your unit from operating at its most efficient level. 

1 -   

Air Filter

  – Ask  your  Lennox  dealer  to  show  you 

where  your  indoor  unit's  filter  is  located.  It  will  be 

either at the indoor unit (installed internal or external 

to the cabinet) or behind a return air grille in the wall 

or  ceiling.  Check  the  filter  monthly  and  clean  or 

replace it as needed. 

2 -   

Disposable Filter

  –  Disposable  filters  should  be 

replaced with a filter of the same type and size. 

NOTE

 – 

If you are unsure about the filter required for your 

system, call your Lennox dealer for assistance.

 

3 -   

Reusable Filter

 – Many indoor units are equipped 

with  reusable  foam  filters.  Clean  foam  filters  with 

a mild soap and water solution; rinse thoroughly; 

allow  filter to dry completely  before  returning  it to 

the unit or grille. 

NOTE

 – 

The filter and all access panels must be in place 

any time the unit is in operation.

 

4 -   

Electronic Air Cleaner

  –  Some  systems  are 

equipped with an electronic air cleaner, designed 

to remove airborne particles from the air passing 

through the cleaner. If your system is so equipped, 

ask your dealer for maintenance instructions. 

5 -   

Indoor Unit

 – The indoor unit's evaporator coil is 

equipped with a drain pan to collect condensate 

formed as your system removes humidity from the 

inside air. Have your dealer show you the location 

of the drain line and how to check for obstructions. 

(This  would  also  apply  to  an  auxiliary  drain,  if 

installed.) 

Thermostat Operation 

See the thermostat homeowner manual for instructions on 

how to operate your thermostat.

Preservice Check 

If your system fails to operate, check the following before 

calling for service: 
•  Verify room thermostat settings are correct. 
•  Verify that all electrical disconnect switches are ON. 
•  Check for any blown fuses or tripped circuit breakers. 
•  Verify unit access panels are in place. 
• 

Verify air filter is clean. 

•   If service is needed, locate and write down the unit 

model number and have it handy before calling. 

Accessories

 

For update-to-date information, see any of the following 

publications: 
• 

Lennox 16ACX Product Specification bulletin 

• 

Lennox Product Catalog 

• 

Lennox Price Book

Servicing Units Void of Charge  

If the outdoor unit is void of refrigerant, clean the system 

using the procedure described below.

1 - 

 Leak  check  system  using  procedure  outlined  on 

page 15.

2 -   Evacuate the system using procedure outlined on 

page 16.

3 -   Use nitrogen to break the vacuum and install a new 

filter drier in the system.

Summary of Contents for 16ACX Series

Page 1: ...isconnect all remote electric power supplies before opening access panel Unit may have multiple power supplies 16ACX Table of Contents Installation Clearances 2 Model Number Identification 2 Dimension...

Page 2: ...mm Clearance to one of the remaining two sides may be A clearance of 24 in must be maintained between two units 48 in 1219 mm clearance required on top of unit Model Number Identification 16 AC X 036...

Page 3: ...NECTION 6 3 8 162 TOP VIEW BASE SECTION COMPRESSOR COIL DRAIN OUTLETS Around perimeter of base OPTIONAL UNIT STAND OFF KIT 4 Field Installed 111 4 3 8 4 3 8 4 3 8 4 3 8 6 3 8 162 111 111 111 111 4 3 8...

Page 4: ...0 97 0 95 Outdoor Fan Motor Full load amps 1 0 1 7 1 7 1 4 Locked Rotor amps 1 9 3 2 3 2 3 2 CONTROLS ORDER SEPARATELY iComfort M30 Smart Wi Fi Thermostat 15Z69 Remote Outdoor Temperature Sensor X265...

Page 5: ...riately sized wrench should be used and fitted snugly over the cap before tightening TABLE 1 Torque Requirements Parts Recommended Torque Service valve cap 8 ft lb 11 NM Sheet metal screws 16 ft lb 2...

Page 6: ...7 8 9 10 11 12 1 12 TURN To Access Service Port A service port cap protects the service port core from contamination and serves as the primary leak seal 1 Remove service port cap with an appropriately...

Page 7: ...ent of unit in relation to a window see the provided illustration in figure 3 detail A PLACING UNIT ON SLAB When installing unit at grade level the top of the slab should be high enough above grade so...

Page 8: ...ons that may cause panels to be blown around and battered WARNING REMOVAL STEP 1 INSERT PANEL UNDER UNIT TOP CAP LIP AND LIFT SLIGHTLY TO CLEAR SIDE LIP OF PANEL FROM BASE STEP 2 PANEL INSTALLATION TO...

Page 9: ...of refrigerant charge in the system No need to add oil in system with 20 pounds of refrigerant or less For systems over 20 pounds add one ounce for every five pounds of refrigerant Recommended topping...

Page 10: ...be used if line set is to be installed on exterior of outside wall PVC PIPE FIBERGLASS INSULATION CAULK OUTSIDE WALL VAPOR LINE WRAPPED WITH ARMAFLEX LIQUID LINE OUTSIDE WALL LIQUID LINE VAPOR LINE WO...

Page 11: ...dous to your health Avoid breathing vapors or fumes from brazing operations Perform operations only in well ventilated areas Wear gloves and protective goggles or face shield to protect against burns...

Page 12: ...SERVICE VALVE Flow regulated nitrogen at 1 to 2 psig through the low side refrigeration gauge set into the liquid line service port valve and out of the suction vapor line service port valve CUT AND D...

Page 13: ...tions for the next step in preparing the unit WHEN BRAZING LINE SET TO SERVICE VALVES POINT FLAME AWAY FROM SERVICE VALVE PREPARATION FOR NEXT STEP 7 WARNING 1 FIRE PERSONAL INJURY OR PROPERTY DAMAGE...

Page 14: ...ISTING INDOOR UNIT GAUGE MANIFOLD INVERTED CYLINDER CONTAINS CLEAN HCFC22 TO BE USED FOR FLUSHING LIQUID LINE SERVICE VALVE INLET DISCHARGE TANK RETURN CLOSED OPENED RECOVERY CYLINDER RECOVERY MACHINE...

Page 15: ...hreads and expose surface of the Teflon ring with refrigerantoil E Attach the liquid line assembly to the expansion valve Finger tighten and use an appropriately sized wrench to turn an additional 1 2...

Page 16: ...losed connect the cylinder of HFC 410A refrigerant to the center port of the manifold gauge set Open the valve on the HFC 410A cylinder vapor only B Open the high pressure side of the manifold to allo...

Page 17: ...r unit until the absolute pressure does not rise above 500 microns 29 9 inches of mercury within a 20 minute period after shutting off the vacuum pump and closing the manifold gauge valves F When the...

Page 18: ...to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 24VAC TRANSFORMER Use the transformer provided with the furnace or air han dler for low voltage control power 24...

Page 19: ...Page 19 FIGURE 12 Typical Wiring Diagram...

Page 20: ...shut off compressor operation The auto reset switch closes when the compressor cas ing temperature falls to 151 187 F 66 C 86 C and the compressor is re energized This single pole single throw SPST bi...

Page 21: ...s filter is located It will be either at the indoor unit installed internal or external to the cabinet or behind a return air grille in the wall or ceiling Check the filter monthly and clean or repla...

Page 22: ...he thermostat for a cooling demand Turn on power to the indoor indoor unit and close the outdoor unit disconnect switch to start the unit 7 Recheck voltage while the unit is running Power must be with...

Reviews: