Page 8

Unit must be grounded with separate ground conductor.
The unit wiring diagram is located inside the unit access
panel. Low voltage control wiring are pigtail leads located
below the main control box and are color coded to match
the connection called out on the wiring schematic.

If any of the original unit wiring is replaced, the same size
and type wire must be used. Electrical wiring must be
sized to carry minimum circuit ampacity marked on the
unit. Each unit must be wired with a separate branch cir
cuit and be properly fused.

System Performance

For maximum performance of this heat pump system, the
operating temperatures and pressures should be
checked and superheat determined at Standard ARI test
conditions of 82

_

F outdoor − 80

_

F indoor dry bulb/67

_

F

wet bulb. If superheat measured deviates from values in
table below, refrigerant charge should be adjusted ac
cordingly for maximum performance.

Verify system performance using table 3 or table 4 as a

general guide. These tables should not be used for charg
ing the unit. Minor variations in these pressures may be
expected due to differences in installations. Significant
differences could mean that the system is not properly
charged or that a problem exists with some component in
the system. Used carefully, this table could serve as a use
ful service guide. Table 3 should be used when unit is
charged during the heating mode. If outdoor ambient is
below 45

°

F, run unit through defrost cycle first, wait 15

minutes for system pressures to stabilize, then take pres
sures. Data in table 3 is based on 70

°

F dry bulb return air.

Data in table 4 is based on 80

°

F dry bulb / 67

°

F wet bulb

return air. Allow unit operation to stabilize before taking
pressure readings.

TABLE 2

SUCTION SUPERHEAT TABLE

UNIT MODEL NO.

SUCTION SUPERHEAT

82

_

F OD minus 80

_

F IDDB

/ 67

_

F IDWB

12CHP−030, −036

12CHP−024

12CHP−030

18 − 20

_

12CHP−036

18   20

12CHP−042, −048, −060

TABLE 3

NORMAL OPERATING PRESSURES −− HEATING MODE

70

°

F db RETURN AIR

AIR TEMPERATURE ENTERING OUTDOOR COIL (

°

F)

MODEL

PRESSURE

10°

15°

20°

25°

30°

35°

40°

45°

50°

55°

60°

12CHP−024

17

20

24

28

33

38

43

49

55

62

69

74

81

12CHP−030

14

17

21

25

29

34

39

45

51

56

63

70

78

12CHP−036

SUCTION

14

17

21

25

29

34

39

45

51

56

63

70

78

12CHP−042

SUCTION

16

19

23

27

31

36

41

45

51

55

62

68

76

12CHP−048

15

18

22

26

30

35

40

45

51

55

62

68

76

12CHP−060

14

 17

21

25

29

34

39

44

50

54

61

67

75

12CHP−024

181

191

200

209

219

228

237

247

256

265

275

284

293

12CHP−030

168

173

179

184

189

195

200

205

211

216

221

227

232

12CHP−036

LIQUID

165

172

178

184

191

197

203

210

216

222

229

235

241

12CHP−042

LIQUID

167

174

181

187

194

201

207

214

221

227

234

241

247

12CHP−048

203

211

220

229

237

246

255

263

272

281

289

298

307

12CHP−060

163

170

177

183

190

197

203

210

217

223

230

237

243

Summary of Contents for 12CHP024

Page 1: ...GED HEAT PUMP UNIT 2 5 TONS 504 176M 06 03 Supersedes 01 00 Table of Contents Shipping Packing List 1 General 1 Unit Dimensions 2 Parts Arrangement 3 Requirements 3 Clearances 4 Rigging Setting Unit 4...

Page 2: ...UTDOOR COIL EXHAUST AIR A C B B RIGHT SIDE BLOWER C HORIZONTAL RETURN AIR OPENING 048 060 A L E F G G 2 51 FF EE FILTER RACK BASE RAIL 2 7 16 62 4 5 8 117 CENTER OF GRAVITY K K K K J J J J E H N FORKL...

Page 3: ...gent to remove any residue from manufacturing processes Limitations for unit and appropriate accessories must also be observed The unit must not be installed with any duct system in the outdoor air st...

Page 4: ...to prevent ice accumulation Unit should not be located near walkways to prevent possible icing of surface from defrost condensate Avoid placing unit near quiet areas i e sleeping quarters or study ro...

Page 5: ...e control assembly 8 Field wiring of auxiliary heater is separate from unit power supply Wire power supply wiring for the heater to appropriate connections on heater kit OPTIONAL ELECTRIC HEAT INSTALL...

Page 6: ...Page 6 12CHP Series Heat Pump Packaged Units Typical Wiring Diagram Does not Include 12CHP060 FIGURE 7...

Page 7: ...Page 7 12CHP060 Series Heat Pump Packaged Units Typical Wiring Diagram FIGURE 8...

Page 8: ...table could serve as a use ful service guide Table 3 should be used when unit is charged during the heating mode If outdoor ambient is below 45 F run unit through defrost cycle first wait 15 minutes...

Page 9: ...outdoor fan The reversing valve is not energized in the heating mode The thermostat again automatically brings on the in door blower at the same time Upon satisfying heating de mand the thermostat op...