background image

Page 6

Refrigerant Piping

Field refrigerant piping consists of liquid and vapor lines
from the outdoor unit (sweat connections) to the indoor coil
(flare or sweat connections). Use Lennox L15 (sweat, non-
flare) series line sets as shown in table 1 or use field-fabri-
cated refrigerant lines. Refer to Refrigerant Piping Guide
(Corp. 9351−L9) for proper size, type, and application of
field−fabricated lines. Valve sizes are also listed in table 1.

Table 1

Refrigerant Line Sets

Model

Valve Field Size

Connections

Recommended Line Set

Model

Liquid

Line

Vapor

Line

Liquid

Line

Vapor

Line

L15

Line Sets

−18

3/8 in.

(10 mm)

5/8"

(15.9 mm)

5/16"*

(7.9 mm)

5/8"

(15.9

mm)

L15−21

15 ft. − 50 ft.

(4.6 m − 15

m)

−24
−30

3/8 in.

(10 mm)

3/4"

(19 mm)

5/16"*

(7.9 mm)

3/4"

(19 mm)

L15−31

15 ft. − 50 ft.

(4.6 m − 15 m)

−36

3/8 in.

(10 mm)

3/4"

(19 mm)

3/8"

(9.5 mm)

3/4"

(19 mm)

L15−41

15 ft. − 50 ft.

(4.6 m − 15 m)

−42
−48

3/8 in.

(10 mm)

7/8"

(22.2 mm)

3/8"

(9.5 mm)

7/8"

(22.2

mm)

L15−65

15 ft. − 50 ft.

(4.6 m − 15 m)

−60

3/8 in.

(10 mm)

1−1/8"

(28.5 mm)

3/8"

(9.5 mm)

1−1/8"

(28.5

mm)

Field

Fabricated

*Use reducer supplied in bag assembly

NOTE − Units are designed for line sets of up to fifty feet (15
m). For applications longer than fifty feet, consult the Len-

nox Refrigerant Piping Guide (Corp. 9351−L9)

.

 Select line

set diameters from table 1 to ensure that oil returns to the
compressor.

Installing Refrigerant Line

During the installation of any heat pump or a/c system, it is
important to properly isolate the refrigerant lines to prevent
unnecessary vibration. Line set contact with the structure
(wall, ceiling or floor) causes some objectionable noise
when vibration is translated into sound. As a result, more
energy or vibration can be expected. Closer attention to
line set isolation must be observed.

Following are some points to consider when placing and
installing a high−efficiency outdoor unit:

1- 

Placement −

 Be aware some localities are adopting

sound ordinances based on how noisy the unit is from
the adjacent property not at the original installation.
Install the unit as far as possible from the property line.
When possible, do not install the unit directly outside a
window. Glass has a very high level of sound transmis-
sion.

2- 

Line Set Isolation −

 The following illustrations demon-

strate procedures which ensure proper refrigerant line
set isolation. Figure 7 shows how to install line sets on
vertical runs. Figure 8 shows how to install line sets on
horizontal runs. Figure 9 shows how to make a transition
from horizontal to vertical. Finally, figure 10 shows how
to place the outdoor unit and line set.

Summary of Contents for 10HPB18

Page 1: ...h 5 tons 504 828M 06 04 Supersedes 02 04 Table of Contents 10HPB Outdoor Units 1 Shipping Packing List 1 General Information 1 Unit Dimensions 2 Setting the Unit 3 Electrical 4 Refrigerant Piping 6 Re...

Page 2: ...8 111 6 3 8 162 6 3 8 162 Top View Base Section 3 4 19 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 4 3 8 111 coil drain outlets around perimeter of base optional unit stand off kit 4 field installed liqu...

Page 3: ...to allow adequate drainage of defrost water and prevent ice buildup 3 In heavy snow areas do not locate the unit where drift ing will occur The unit base should be elevated above the depth of average...

Page 4: ...2 Ground unit at unit disconnect switch or to an earth ground NOTE To facilitate conduit a hole is in the bottom of the control box Connect conduit to the control box us ing a proper conduit fitting N...

Page 5: ...Y1 O Outdoor Unit Figure 5 power power common common 1st stage aux heat 1st stage aux heat indoor blower compressor R C W1 Y1 O G R C W1 W2 W3 G 10HPB and Blower Unit Thermostat Designations with auxi...

Page 6: ...Refrigerant Piping Guide Corp 9351 L9 Select line set diameters from table 1 to ensure that oil returns to the compressor Installing Refrigerant Line During the installation of any heat pump or a c s...

Page 7: ...Line IMPORTANT Refrigerant lines must not contact structure Outside Wall Inside Wall Liquid Line Vapor Line IMPORTANT Refrigerant lines must not contact wall Wood Block Between Studs Strap Sleeve Woo...

Page 8: ...ire Tie Wire Tie around vapor line only Floor Joist or Roof Rafter Tape or Wire Tie Strap the vapor line to the joist or rafter at 8 ft intervals then strap the liquid line to the vapor line To hang l...

Page 9: ...Line Metal Sleeve Anchored Heavy Nylon Wire Tie Automotive Muffler Type Hanger Wall Stud Wall Stud Liquid Line Vapor Line Wrapped in Armaflex Strap Liquid Line To Vapor Line Metal Sleeve Figure 9 Out...

Page 10: ...he indoor coil Refrigerant Metering Device 10HPB units are used in check expansion valve systems only See the Lennox Engineering Handbook for approved TXV match ups and application information Check e...

Page 11: ...erant lines have been leak tested and evacuated All precautions should be exercised to keep the system free from dirt moisture and air To Access Schrader Port 1 Remove service port cap with an adjusta...

Page 12: ...mixture check the high and low pressures before unbrazing WARNING Refrigerant can be harmful if it is inhaled Refrigerant must be used and recovered responsibly Failure to follow this warning may res...

Page 13: ...sure 6 When the absolute pressure reaches 23 000 microns 29 01 inches of mercury close the manifold gauge valves turn off the vacuum pump and disconnect the manifold gauge center port hose from vacuum...

Page 14: ...ng mode with a set point of 68 F 20 C When pressures have stabilized use a digital thermometer to record the liquid line temperature 5 The outdoor temperature will determine which charg ing method to...

Page 15: ...ns Significant differences could mean that the system is not properly charged or that a problem exists with some component in the system Pressures higher than those listed indicate that the system is...

Page 16: ...n the outdoor unit control circuit is isolated from power and field provided relays bypass the outdoor thermostats An amber indicating light simultaneously comes on to remind the homeowner that he is...

Page 17: ...ill lock out the unit if the optional high pressure switch opens The diagnostic LEDs will display a pattern for an open high pressure switch See table 8 The unit will re main locked out until the swit...

Page 18: ...Clean or change filters 2 Adjust blower speed for cooling Measure the pressure drop over the coil to determine the correct blower CFM Refer to the unit information service manual for pressure drop ta...

Reviews: