Page 18
Maintenance
WARNING
Electric shock hazard. Can cause inju-
ry or death. Before attempting to per-
form any service or maintenance, turn
the electrical power to unit OFF at dis-
connect switch(es). Unit may have
multiple power supplies.
Maintenance and service must be performed by a qualified
installer or service agency. At the beginning of each cooling
season, the system should be checked as follows:
Outdoor Unit
1 − Clean and inspect outdoor coil (may be flushed with a
water hose). Make sure power is off before cleaning.
2 − Outdoor unit fan motor is pre-lubricated and sealed. No
further lubrication is needed.
3 − Visually inspect all connecting lines, joints and coils for
evidence of oil leaks.
4 − Check all wiring for loose connections.
5 − Check for correct voltage at unit (unit operating).
6 − Check amp draw on outdoor fan motor.
Unit nameplate__________Actual__________.
7 - Inspect drain holes in coil compartment base and clean
if necessary.
NOTE − If owner complains of insufficient cooling, the unit
should be gauged and refrigerant charge checked. Refer
to section on refrigerant charging in this instruction.
Indoor Coil
1 − Clean coil if necessary.
2 − Check connecting lines, joints and coil for evidence of
oil leaks.
3 − Check condensate line and clean if necessary.
Indoor Unit
1 − Clean or change filters.
2 − Adjust blower speed for cooling. Measure the pressure
drop over the coil to determine the correct blower CFM.
Refer to the unit information service manual for pressure
drop tables and procedure.
3 −
Belt Drive Blowers −
Check belt for wear and proper
tension.
4 − Check all wiring for loose connections.
5 − Check for correct voltage at unit. (blower operating)
6 − Check amp draw on blower motor.
Motor nameplate__________Actual__________.
Optional Accessories
Refer to the Engineering Handbook for optional accesso-
ries that may apply to this unit. The following may or may
not apply:
Loss of Charge Kit
High Pressure Switch Kit
Compressor Monitor
Compressor Crankcase Heater
Hail Guards
Mounting Bases
Stand−off Kit
Sound Cover
Low Ambient Kit
Monitor Kit
Mild Weather Kit
Start−Up and Performance Check List
Start−Up and Performance Check List
Job Name
Job Location
Installer
Unit Model No.
Nameplate Voltage
Rated Load Ampacity
Maximum Fuse or Circuit Breaker
Refrigerant Lines:
Service Valves Fully Opened?
Outdoor Fan Checked?
Job No.
City
City
Serial No.
Date
State
State
Service Technician
Compressor
Outdoor Fan
Indoor Filter Clean?
Electrical Connections Tight?
Supply Voltage (Unit Off)
Vapor Pressure
Thermostat
Refrigerant Charge Checked?
Calibrated?
Properly Set?
Level?
Properly Insulated?
Voltage With Compressor Operating
Leak Checked?
Service Valve Caps Tight?
Indoor Blower RPM
Outdoor Coil Entering Air Temp.
Discharge Pressure
S.P. Drop Over Indoor (Dry)