background image

Page 6

505128M 03/06

Leak Testing

After the line set has been connected to the indoor and out-
door units, check the line set connections and indoor unit
for leaks.

WARNING

Danger of fire!

Bleeding the refrigerant charge from
only the high side may result in the
low side shell and suction tubing be-
ing pressurized. Application of a braz-
ing torch while pressurized may re-
sult in ignition of the refrigerant and
oil mixture − check the high and low
pressures before unbrazing.

WARNING

Refrigerant can be harmful if it is inhaled. Refriger-
ant must be used and recovered responsibly.

Failure to follow this warning may result in personal
injury or death.

WARNING

Danger of explosion!

Can cause equipment damage, injury
or death. Never use oxygen to pres-
surize a refrigeration or air condition-
ing system. Oxygen will explode on
contact with oil and could cause per-
sonal injury.

WARNING

Danger of explosion!

When using a high pressure gas such
as dry nitrogen to pressurize a refrig-
eration or air conditioning system,
use a regulator that can control the
pressure down to 1 or 2 psig (6.9 to
13.8 kPa).

Using an Electronic Leak Detector or Halide

1. Connect a cylinder of HCFC-22 to the center port of

the manifold gauge set.

2. With both manifold valves closed, open the valve on

the HCFC-22 cylinder (vapor only).

3. Open the high pressure side of the manifold to allow

the HCFC-22 into the line set and indoor unit. Weigh
in a trace amount of HCFC-22.

 

[A trace amount is a

maximum of 2 ounces (57 g) or 3 pounds (31 kPa)
pressure.]

 

Close the valve on the HCFC-22 cylinder

and the valve on the high pressure side of the manifold
gauge set. Disconnect the HCFC-22 cylinder.

4. Connect a cylinder of nitrogen with a pressure regulat-

ing valve to the center port of the manifold gauge set.

5. Connect the manifold gauge set high pressure hose to

the vapor valve service port. 

(Normally, the high pres-

sure hose is connected to the liquid line port; however,
connecting it to the vapor port better protects the man-
ifold gauge set from high pressure damage.)

6. Adjust the nitrogen pressure to 150 psig (1034 kPa).

Open the valve on the high side of the manifold gauge
set which will pressurize line set and indoor unit.

7. After a few minutes, open a refrigerant port to ensure

the refrigerant you added is adequate to be detected.
(Amounts of refrigerant will vary with line lengths.)
Check all joints for leaks. Purge nitrogen and
HCFC-22 mixture. Correct any leaks and recheck.

Evacuation

Evacuating the system of noncondensables is critical for
proper operation of the unit. Noncondensables are defined
as any gas that will not condense under temperatures and
pressures present during operation of an air conditioning
system. Noncondensables and water vapor combine with
refrigerant to produce substances that corrode copper pip-
ing and compressor parts.

IMPORTANT

Use a thermocouple or thermistor electronic vacuum
gauge that is calibrated in microns. Use an instrument
that reads from 50 microns to at least 23,000 microns.

1. Connect manifold gauge set to the service valve ports

as follows:

low pressure gauge to 

vapor 

line service valve

high pressure gauge to 

liquid 

line service valve

2. Connect micron gauge.
3. Connect the vacuum pump (with vacuum gauge) to

the center port of the manifold gauge set.

4. Open both manifold valves and start the vacuum

pump.

5. Evacuate the line set and indoor unit to an 

absolute

pressure

 of 23,000 microns (29.01 inches  of mercu-

ry). During the early stages of evacuation, it is desir-
able to close the manifold gauge valve at least once to
determine if there is a rapid rise in 

absolute pressure

.

A rapid rise in pressure indicates a relatively large
leak. If this occurs, repeat the leak testing procedure.

NOTE − The term 

absolute pressure

 is defined as the

total actual pressure within a given volume or system,
above the absolute zero of pressure. Absolute pres-
sure in a vacuum is equal to atmospheric pressure mi-
nus vacuum pressure.

6. When the absolute pressure reaches 23,000 microns

(29.01 inches  of mercury), close the manifold gauge
valves, turn off the vacuum pump and disconnect the
manifold gauge center port hose from vacuum pump.
Attach the manifold center port hose to a nitrogen cyl-
inder with pressure regulator set to 150 psig (1034
kPa) and purge the hose. Open the manifold gauge
valves to break the vacuum in the line set and indoor
unit. Close the manifold gauge valves.

Summary of Contents for 10ACE Series

Page 1: ...ox Industries Inc P O Box 799900 Dallas TX 75379 9900 INSTALLATION INSTRUCTIONS 10ACE Series Units CONDENSER UNITS 505 128M 03 06 Supersedes 01 06 Table of Contents 10ACE Outdoor Units 1 Shipping Pack...

Page 2: ...16 24 1 4 565 048 33 838 32 1 4 819 24 1 4 616 060 33 940 32 1 4 921 24 1 4 718 General Information These instructions are intended as a general guide and do not supersede national or local codes in a...

Page 3: ...l installation instructions for additional wiring application diagrams and refer to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size 1 Install line voltage power sup...

Page 4: ...es square free from nicks or dents Debur the ends The pipe must remain round do not pinch end of the line 2 Wrap a wet cloth around the valve body and copper tube stub to protect it from heat damage d...

Page 5: ...he stem cap Tighten finger tight then torque per table 1 Page 2 To Close Front Seated Service Valves 1 Remove the stem cap with an adjustable wrench 2 Use a service wrench with a hex head extension 3...

Page 6: ...valve on the high side of the manifold gauge set which will pressurize line set and indoor unit 7 After a few minutes open a refrigerant port to ensure the refrigerant you added is adequate to be det...

Page 7: ...ig positive pressure in the line set and indoor unit Close manifold gauge valves and shut off the HCFC 22 cylinder and remove the manifold gauge set Start Up IMPORTANT If unit is equipped with crankca...

Page 8: ...iate charging procedure Charge Using Weigh in Method Fixed Orifice TXV Systems Outdoor Temp 65 F 18 C If the system is void of refrigerant or if the outdoor ambient temperature is cool use the weigh i...

Page 9: ...eratures 4 Check the liquid line temperature The difference be tween the ambient and liquid temperatures should match values given in table 6 Loss of charge results in low capacity and efficiency 5 If...

Page 10: ...ight out to extract the push pins along one side of the coil If necessary remove the push pins along the back of the unit it is usually unnecessary to fully re move the inner mesh screen Drape the mes...

Page 11: ...cklist Job Name Job no Date Job Location City State Installer City State Unit Model No Serial No Service Technician Nameplate Voltage Rated Load Ampacity Compressor Outdoor Fan Maximum Fuse or Circuit...

Page 12: ......

Reviews: