36
Table 2. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notifications
Component or System Operational State and Troubleshooting Tip
How to clear alert code
434
53
Service
Soon/Service
Urgent
OD Inverter
Comm Error to
Main Control
• Outdoor control has lost communications with the inverter continuously during a single thermostat
call and one hour period.
• Outdoor control will stop all compressor demands – service soon condition.
• Indoor blower will stop functioning.
NOTE:
Indoor blower will not run in test mode either when alert code 434 is active. Only after
system reset will it operate.
•
This alert code will occur if the outdoor unit power is turned off and the indoor unit power (24VAC
to Lennox outdoor control) remains on, or if the indoor unit power is turned off (24VAC to Lennox
outdoor control) and the outdoor unit power is on. This could occur while performing service or
maintenance procedures on the indoor or outdoor unit.
• The Lennox outdoor control will attempt to re-establish communication to the inverter when the
alert code 434 occurs by cycling the outdoor unit contactor off for two minutes. Upon energizing
the contactor the Lennox outdoor control will attempt to communicate to the inverter for three
minutes. This process will be repeated three times in attempt to establish communication before
locking out.
•
If the unit is locked out with a service soon alert code 434, reset the system by cycling the outdoor
unit power off and back on. Then cycle the indoor power off (24VAC to the Lennox outdoor
control) and then back on.
• If this condition continuously occurs during a one hour period and during a single thermostat call,
the outdoor unit will lock out and display alert code 434 – service urgent condition.
Troubleshooting Options:
•
Check for loose or disconnected electrical connections.
• Interruption of main power to inverter.
•
Inverter LEDs will flash code 53.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Inverter flash code 53.
The sequence is:
•
Red LED: Five Flashes
•
Green LED: Three Flashes
NOTE:
Inverter normal operations with no error code present is as follows. Red LED is ON and
Green LED is OFF
Automatically clears when the system
detects that the issue no longer exists.
If the unit is locked out with a service urgent
alert code 434, reset the system by first
cycling the outdoor unit power off and back.
Then cycle the indoor power off (24VAC to
the Lennox outdoor control) and then back
on.