Table 2. Alert Codes and Troubleshooting
GF= Gas Furnace, AH=Air Handler, ID=Indoor unit (GF or AH), HP=Heat Pump, AC=Air Conditioner, OD=Outdoor Unit (AC or HP), PA=Pure Air S, ZA=Zone system and TS=Thermostat
Alert
Code
Inverter
Flash
Code
Priority
Condition
Actual Displayed
Alert Text
Under dealer
control center >
Notifications
Component or System Operational State and Troubleshooting Tip
How to clear alert code
430
26
Service
Soon/Service
Urgent
OD Inverter
Compressor
Startup Fail
Compressor start-up failure.
• If condition is detected, outdoor unit will stop (compressor and fan) – service soon condition.
• Anti-short cycle is initiated.
•
If condition occurs 10 times within 60 consecutive minutes, the system will lockout – service
urgent condition.
•
Inverter LEDs will flash code 26.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Inverter flash code 26.
The sequence is:
•
Red LED: Two Flashes
•
Green LED: Six Flashes
NOTE:
Inverter normal operations with no error code present is as follows. Red LED is ON and
Green LED is OFF.
•
Check refrigerant
• Replace outdoor control board
• Replace inverter.
To clear, disconnect power to outdoor unit
and restart.
431
27
Service
Soon/Service
Urgent
OD Inverter PFC
Fault
The inverter has detected a PFC circuit over-current condition
.
•
Error occurs when PFC detects an over current condition of 100A peak.
• If condition is detected, outdoor unit will stop (compressor and fan) – service soon condition.
• Anti-short cycle timer is initiated.
•
If condition occurs 10 times within 60 consecutive minutes, the system will lockout – service
urgent condition.
•
Inverter LEDs will flash code 27.
• Refer to the unit service documentation for detailed troubleshooting procedures.
Inverter flash code 27.
The sequence is:
•
Red LED: Two Flashes
•
Green LED: Seven Flashes
NOTE:
Inverter normal operations with no error code present is as follows. Red LED is ON and
Green LED is OFF.
To clear, disconnect power to outdoor unit
and restart.