4.4 ECOWAY: Other functions / running in the background

 

 
4.4.1. Dry stop function - protects the heating element against damage as a result of the lack of water 
in the tank. Please note, that you can never switch on a tank that holds no water. In that case the Dry 
stop function will not prevent damage. The function is activated at any time when the heater starts 
working and lasts for 1.5 min. and may not be stopped. At this time, the HEATER LED will continue to 
be lit even if we change the program or temperature setting.

 

4.4.2. Anti-freezing function - is activated when the controller is off (only the power LED is lit). It 
prevents the water in the tank from freezing by turning on the electrical heating element.

 

4.4.3. Anti-legionella function 

– Operates automatically. Every 14 days, the controller heats the water 

in the tank to 75°C to disinfect the tank surface and eliminate any possibly present legionella 
bacteria,

 

4.4.4. Temperature limiter function - prevents overheating of the water in the tank - In case the water 
temperature increases excessively, the electricity supply to the heating element is disconnected at 
both poles.  
4.4.5. Hysteresis function - the controller turns on the heating element when the water temperature 
drops by 2°C below the set temp., which allows for lowering the number of switching cycles and 
increases the service life of the heating element and the controller components.

 

4.4.6. Clock - displays the programmed time in the controller; to display the clock, press OK.

 

4.4.7. Active protection - a set of relays which disconnects the electric heating element on two poles, 
which increases the safety of work of the heater by eliminating the possible risk of electric shock.

 

 

4.5. ECOWAY: Error codes

 

Er01 - the temperature limiter was triggered - exceeding the permissible water temp. inside the tank. 
Before re-connect the heater, it is necessary to remove the plug from the socket for at least 5 minutes 
and wait till the water temperature drops.  
Er02 - the driver has detected the lack of water in the tank. To clear the error, press OK. That switches 
the driver off and will cut of the power to the heater for 20 minutes and then resume normal operation. 
In the case of frequent Er01 messages and the fluctuation of water temp at the tank supply, it is 
recommended to turn the detection of the lack of water from the service menu - item 7.7.  

AL or AH - damage to the temperature sensor or a decrease in temperature below 0 °C or rise above 
99°C, it is necessary to call your supplier to replace the sensor.

 

 

4.6 ECOWAY: Service menu 

 

To navigate to the service menu, it is necessary to turn the driver off (the POWER LED is lit), and then 
hold the PROG button. The display will show Fx yy (yy flashing) where x is the number of the 
parameter and yy is its value. Use the up / down keys to change the value, and OK to confirm and 
move to another parameter; after editing the last parameter (6), the driver will exit the service menu. 
Each entry to the service menu causes the reset of the ECO+ function and restarts learning.  

Code 
Description  

  

Scope of 

adjustment 

Factory 

setting 

F1  

 Status of the anti-legionella function (0 - OFF; 1 - 
ON.)  

0 / 1 

F2 

 Frequency of work of the anti-legionella function  

7 - 21 days  

14 days 

F3  

Time of the anti-legionella function initiation  

0 - 23 hours 

1 hour 

F4  

 Status of the function of the lack of water in the 
tank (0 - OFF; 1 - ON.)  

0 / 1 

F5  

 Frost protection temperature  

5 - 10 °C 

7 °C 

F6   

Temp. for the ECO+ mode (at which the driver 
will aim)  

35 - 45°C  

45°C 

 

 
 
 
 

Summary of Contents for ECOWAY 100

Page 1: ...NUAL WALL MOUNTED UNVENTED ELECTRIC WATER HEATERS LEMET GREENLINE 30 50 80 100 120 and 200 Liter vertical and horizontal LEMET ECOWAY 50 80 100 120 and 200 Liter SMALL 5 and 10 liter under sink and ov...

Page 2: ...Do not use the water heater when frozen Wait until the water flows again in the water heater before using 3 Do not attempt to repair but call a certified installer Failing to do so will void your warr...

Page 3: ...um tank working pressure Mpa 0 6 0 6 0 6 Connection port spacing cm 10 10 10 Tank diameter Total height cm 44 56 44 80 44 93 Protection rating IP 24 24 24 Net weight without water kg 17 23 27 1 Domest...

Page 4: ...utlet 10 Discharge pipe to drain of expansion water GREENLINE Electric water heaters 50L 60L 80L 100L Time of heating up to 65OC t 45 min 80 95 125 160 Rated voltage V Hz 230 50 230 50 230 50 230 50 E...

Page 5: ...rature control 5 Cable with plug 6 Pressure relief valve 7 Drain valve install a discharge pipe underneath 8 stopcock on the mains water supply line 9 Stopcock on hot water outlet 10 Under sink pressu...

Page 6: ...an electronic controller An overheat protection of water heated by the electric heating element is in this case a non automatic temperature limiter which disconnects the electric circuit when the wat...

Page 7: ...ure or fluctuating water pressure will not be covered by the warrantee Pressure reducing valve 3 1 Connection to the water supply system The heater must be connected to the mains water supply in such...

Page 8: ...eater free of charge to the orifice on the pressure relief valve facing downwards to drain of expansion water uninterruptedly to a drain 2 A KIWA approved safety relief valve If you have installed a K...

Page 9: ...to the water heater The pressure relief valve must remain open to atmosphere and never further away than 2 metres from the water heater Always install the pressure relief on the cold water inlet side...

Page 10: ...o ensure an even longer lifespan of your water heater 6 GREENLINE and SMALL set the temperature with the thermo regulator knob It is recommended to set the knob in just below the MAX setting of the re...

Page 11: ...s set the required temperature within the scope of 20 to 75 C and after setting and approx 3 5 sec the controller will display the required and current temperature 4 3 2 ECOWAY ECO WORKING MODE It is...

Page 12: ...ram ECO mode is set Press the up and down buttons to select the temperature for the first program Or press the ECO button selecting the ECO mode for the first program and confirm with OK d The display...

Page 13: ...of the heater by eliminating the possible risk of electric shock 4 5 ECOWAY Error codes Er01 the temperature limiter was triggered exceeding the permissible water temp inside the tank Before re connec...

Page 14: ...ss of neutral earthing 5 3 Cleaning maintenance and replacement of the magnesium anode The heater should be cleaned with a damp cloth without the use of aggressive abrasive cleaning agents It is recom...

Page 15: ...Draining the water heater Take the power cord from the power socket Place a bucket underneath the cold water inlet side BLUE marking Close the stopcock on the mains water supply and then remove the pr...

Page 16: ...11 Use a water hose to rinse out any limescale from inside the tank Alternatively take the water heater from the wall place the unit in the bathtub or in the shower and use the shower hose to rinse ou...

Page 17: ...alve usually bloated tank or cracked cylinder is not covered by the warranty it applies to the assembly in the pressurised version Using the heater in water supply networks with a pressure greater tha...

Reviews: