Page 33/95
21January2021/Version 0
LEM International SA
Chemin des Aulx 8
1228 PLAN-LES-OUATES Switzerland
www.lem.com
You can connect the product with bus bars and lugs.
F
The product is compatible for one lug per connection configuration with all lugs from standard:
• NF C 20-130: 2004
• DIN 46220: 1965
• DIN 46234: 1980
• DIN 46235: 1983
!
2 lugs can connect on each terminal, not all the lugs are compatible. Please check the dimensions.
A
B
H
H
E
D
F
G
C
A
Figure 17: Sensor Unit integration
DCBM_SU40XX
DCBM_SU60XX
A
15 mm
15 mm
B
62 mm
62 mm
C
19 mm
27 mm
D
30 mm
40 mm
E
9 mm max.
1)
13 mm max.
1)
F
34.6 mm
52.9 mm
G
13 mm
18 mm
H
15.9 mm
15.9 mm
1)
Maximum thickness
for bus bar or lugs
Fire
hazard
Reference
Nominal tightening
torque (N.m)
DCBM_SU40XX
10.4 ±0.5
DCBM_SU60XX
36.4 ±0.5
Size of stud
⌀
Drilling
hole (mm)
M8
8.5
M12
12.5
Table 2: Torque values for installation