9.
SPECIAL PROGRAMMING
All parameters remain stored even if EasyAlarm® is switched off or battery has changed.
Programming mode can be locked to secure against unintended programming during operation
In that case on position PROG you will hear
Changing these parameters below does influence the operating mode. Therefore only necessary parameters should be
changed. Please test behaviour before going into operation.
9.1
Ready/Modify profile
Value Profile
Alarm units
Profile-Overview
User announcement
Connection time-out Dialling-in
7
00
EA-8-DPX/EA-8-DPXM
Repeated every 5 second
1 minute
Directly
8
01
EA-8-DPXF/EA-8-DPXFM
single
2 minutes
Directly
9
02
EA-8-DPXN (PLUS)
single
2 minutes
Two-step
10
03
EA-8-DPX/EA-8-DPXM
single
2 minutes
Directly
11
04
EA-8-DPX/EA-8-DPXM
Repeated every 8 seconds
2 minutes
Directly
Warning: After changing profile you have to activate factory settings as follows
9.2
Factory settings (Default Value)
EasyAlarm® can be reset to default values:
Keep key
3
and
#
pressed simultaneously
Release both
keys
9.3
Alarm repetitions
EasyAlarm® An alarm is triggered, as soon as the alarm criteria is fulfilled and the waiting period has expired. In some
cases it might be useful to repeat an alarm as long until an acknowledgement is received:
*9713
53
##
*
Value
#
Value Info
0
EasyAlarm® calls calling numbers within the calling number sequence just once (
Factory setting
)
1..9
EasyAlarm® starts calling the calling numbers within the calling number sequence until the alarm is confirmed by
sending
0
or until the programmed value n of alarm repetition is reached
9.4
Routine call intervall
The delay between two routine calls to calling number 9 (Control centre / WinMOS) can be read out or modified as follows:
*9713
28
##
*
Value
#
Value Info
1..254 EasyAlarm® dials calling number 9 every 1..254 * 20 minutes.
(
Factory setting: 216
*20 min = 4320 min = 72 h = call every three days)
9.5
Power failure
9.5.1
Power failure time-out
The duration of power loss before the alarm unit starts a call can be read out or modified as follows:
*9713
63
##
*
Value
#
Value
Info
1..255 Duration in steps of 10 minutes (Deviation -0/+10 min) (
Factory setting: 12
*10 min = 120 min = 2 h.)
9.5.2
Calling number in case of power failure (new from version 8.45)
*9713
62
##
*
Value
#
Value
Info
1
Alarm to standard calling-number sequence defined by
**0
(Standard up to Version 8.44)
3
Alarm to calling number 9 (routine) (
Factory setting from Version 8.45)
25
Programming deactivated: PIN
„Profile“