Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)

Wattstopper

 

®

Passive Infrared 0–10 Volt Wall Switch Occupancy Sensor (Version 2)
Interrupteur mural 0–10 Volt avec détecteur de mouvement à infrarouges passif (v2)
Sensor de ocupación con interruptor de pared y tecnología de infrarrojo pasivo de 

voltaje 0 a 10 (v2)

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 26168 – 01/18  rev. 3

DESCRIPTION

The PW Passive Infrared Wall Switch 

sensors use advanced passive infrared 

(PIR) technology. 

•  The PW sensor has Optional Neutral 

capability for applications requiring 

neutral wiring. It also has Multi-Way 

available on all models. 

•  A “walk-through” mode can turn 

lights off after only 3 minutes, if no 

activity is detected after 30 seconds 

following an occupancy detection.

•  The PW-311 has one relay with 

dimming control capability and 

two buttons to allow control of the 

dimming. 

•  PW sensors contain a light level 

sensor. If adequate daylight is 

present, the sensor holds the load

 

OFF

 until light levels drop, even if 

the area is occupied. See the 

Light 

Level Adjustment

 section.

SPECIFICATIONS

Voltages: 
 PW-311 ....................................................120/277 VAC, 50/60 Hz
 PW-311-347 ....................................................347 VAC, 50/60 Hz
Load Limits:
 

@120 VAC ........... 1000-W tungsten ballast, E-ballast, LED, 1/4 HP

 

@277 VAC ...................... 1200-W ballast, E-ballast, LED, 1/4 HP

 

@347 VAC ........................................1500W ballast, LED, 1/4 HP

Time Delay Adjustment ..................................................3 to 30 minutes
Walk-Through Mode ....................... 3 minutes if no activity after 30 sec.
Test Mode ............................................. 10 min. with 10-sec. time delay
PIR Adjustment .................................................................... High or Low
Light Level Adjustment .......................................................8fc to 180+fc
Alerts   ........................................................Selectable Audible & Visual
Optional Neutral .....................................................................All models
Multi-Way Capability ...............................................................All models
Terminal screw torque ............................................ 16 lbf-in (18 kgf-cm)
High Trim ..................................................................................6 to 10 V
Low Trim .....................................................................................0 to 4 V
Ramp Up .......................................................................1 to 10 seconds
Fade Down .................................................................2.5 to 30 seconds

WARNING:

 TURN THE POWER OFF AT THE 

CIRCUIT BREAKER BEFORE WIRING.

INSTALLATION

1.  Make sure that the power has been turned OFF at the circuit breaker.
2.  Connect wires to the PW flying leads as shown in the wiring diagram that 

is appropriate to the PW model and electrical supply. 

The ground wire 

(green) must be fastened to ground for the sensor to work properly.

 

3.  Attach the sensor to the wall box by inserting screws into the two wide 

holes on the top and bottom of the attached metal bracket. Match them 

up with the holes in the wall box and tighten. 

Do not use excessive 

force when installing the sensor into the wallbox

. Doing so can 

bend the mounting strap which can affect button operation.

4.  Turn the circuit breaker 

ON

. Wait one minute, then push the 

Auto ON/

OFF

 switch and the lights will turn 

ON

. There is a delay due to initial 

power-up of the sensor that only occurs during installation.

5.  Test and adjust the sensor if necessary.
6.  Install industry standard decorator wall switch cover plate (not included).

WARNING: 

Grounding the violet and gray wires can damage the unit.  Do not apply power to 

the sensor until 

all

 wires are connected or capped off if the driver is to be installed at a future time.

Driver

or Ballast

Red

Black

Neutral

Line

Green

White

(optional)

Ground

Violet

Yellow

Gray

0 a 10V

Dimming

PW-311 and PW-311-347 Wiring

#12 – #14 AWG

Strip Gage

1/2"

12.7mm

Cu Wire Only

Breakaway 

tab

Optional neutral 

terminals behind 

breakaway tab

8" flying leads for 

line, load, ground 

and multi-way 

connections

Black

Red

Green

Yellow

Violet

Grey

OPTIONAL NEUTRAL WIRING

For applications requiring neutral wiring, remove tab  

as shown to expose terminals for wiring. 

Summary of Contents for Wattstopper PW-311

Page 1: ...t 8fc to 180 fc Alerts Selectable Audible Visual Optional Neutral All models Multi Way Capability All models Terminal screw torque 16 lbf in 18 kgf cm High Trim 6 to 10 V Low Trim 0 to 4 V Ramp Up 1 to 10 seconds Fade Down 2 5 to 30 seconds WARNING TURN THE POWER OFF AT THE CIRCUIT BREAKER BEFORE WIRING INSTALLATION 1 Make sure that the power has been turned OFF at the circuit breaker 2 Connect wi...

Page 2: ...lems 4 1 2m 20 6 1m 35 10 6m 0 PIR Coverage 7 5 2 2m 15 4 5m 20 6 1m 35 10 6m Major motion Minor motion Top View Side View BUTTON FUNCTIONS Pressing and holding the UP button will ramp the lights up to the maximum value as determined by the High Trim setting Pressing and holding the DOWN button will dim the lights down to the minimum value as determined by the Low Trim setting See Additional Progr...

Page 3: ...l programmable features See the DIP SWITCH SETTINGS section for a table showing the switch combinations for each feature as well as the specific values indicated by the blinking green LED Alerts The PW can provide audible and or visible alerts as a warning before the load turns OFF By default visible alert is disabled and audio alert is enabled Walk Through The Walk Through mode shortens the time ...

Page 4: ...e The load returns to the same state as before the power failure ON or OFF If it was previously ON the load will return to the most recent dimming level and if it was previously OFF it will remain OFF If the load was previously ON and the room is now unoccupied the load will turn OFF once vacancy is detected This is the default Default To On The load will turn ON at 100 level after power is restor...

Page 5: ...e sure that the correct lights come ON If the lights turn ON verify that Sensitivity is on High 2 Check the wire connections in particular the Line connection Verify that connections are tightly secured 3 If lights still do not turn ON call 800 879 8585 for technical support Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify proper operat...

Page 6: ...STALLATION 1 Assurez vous que le courant a bien été COUPÉ au niveau du disjoncteur 2 Raccordez les fils aux câbles volants du PW comme illustré dans le schéma de câblage correspondant à votre modèle de PW et à votre alimentation électrique Le fil de terre vert doit être relié à la terre pour que le détecteur puisse fonctionner correctement 3 Fixez le capteur sur le boîtier mural en insérant des vi...

Page 7: ...s non souhaitées Étant donné que cette obstruction diminue la portée n oubliez pas d en tenir compte en cas de dépannage des problèmes de portée 4 1 2m 20 6 1m 35 10 6m 0 IRP Portée 7 5 2 2 m 15 4 5 m 20 6 1 m 35 10 6 m Mouvement important Mouvement faible Vue latérale Vue du haut FONCTIONS DES BOUTONS Le fait de maintenir le bouton HAUT enfoncé permet d augmenter la lumière jusqu à la valeur maxi...

Page 8: ...lités niveaux maximum et minimum maintenez le bouton HAUT ou BAS enfoncé jusqu à ce que la lumière atteigne le niveau souhaité La valeur de la fonctionnalité de réglage du niveau de luminosité doit être modifiée grâce à une méthode spécifique Consultez la section correspondante pour plus d informations Une fois la programmation terminée replacez les quatre interrupteurs DIP sur OFF Le PW 311 quitt...

Page 9: ...nctionnalité 3 Enfoncez puis relâchez le bouton HAUT afin que la DEL verte clignote deux fois si vous souhaitez sélectionner le mode standard Enfoncez puis relâchez à nouveau le bouton HAUT afin que la DEL verte clignote trois fois si vous souhaitez sélectionner le mode niveau de luminosité intelligent 4 Placez les quatre interrupteurs DIP vers le bas 5 Éloignez vous du capteur Après 10 secondes l...

Page 10: ...res S ALLUMENT vérifiez que le bon mode de marche est sélectionné à l aide de l interrupteur DIP 1 2 Assurez vous que le contrôle du niveau de luminosité est activé couvrez la lentille du détecteur avec votre main Si les lumières S ALLUMENT réglez le paramétrage du niveau de luminosité 3 Si les lumières ne S ALLUMENT toujours pas appelez le 1 800 879 8585 pour obtenir une assistance technique Les ...

Page 11: ... Los sensores PW contienen un sensor de nivel de luz En caso de haber luz de día adecuada el sensor mantiene la carga Apagada hasta que cae el nivel de luz aun cuando el área está ocupada Consulte la sección de Ajuste de nivel de luz INSTALACIÓN 1 Asegúrese de haber apagado la energía en el disyuntor 2 Conecte los cables a los conductores volantes del PW como se muestra en el diagrama de cableado ...

Page 12: ...res de 0 a 10 V al balasto de regulación de una PW 311 únicamente Driver o Balasto Cableado típico de múltiples vías PW 311 o PW 311 347 hasta 4 sensores DIAGRAMAS DE COBERTURA La prueba de cobertura se realizó de acuerdo con los lineamientos NEMA WD 7 Para un mejor desempeño utilícelo en espacios no superiores a 4 5 x 3 6 m 15 x 12 Sensor del PIR El sensor tiene una lente Fresnel de vista multice...

Page 13: ...ONMUTADOR SELECTOR PARA BASCULAR para obtener los valores de configuración específicos FUNCIONES PROGRAMABLES ADICIONALES Los conmutadores selectores para bascular 6 a 9 proveen acceso a varias funciones adicionales Cada función se selecciona eligiendo una combinación única de los conmutadores selectores para bascular Una vez que seleccione los valores específicos el LED rojo parpadea para indicar...

Page 14: ...de luz ambiente Esta función está disponible únicamente cuando el PW 311 se configura en Encendido automático Hay dos modos de ajuste de nivel de luz En el modo Estándar se establece un nivel mínimo fijo La carga no volverán a encenderse automáticamente hasta que la luz ambiente disminuya por debajo del nivel mínimo En el modo Nivel de luz inteligente el PW 311 establece un nivel mínimo inicial Lu...

Page 15: ...Encendido automático Encendido manual Modo 9 1 2 3 4 5 6 7 8 Tiempo de demora Modo ON Funciones adicionales No usado Prueba 3 min 15 minutos 30 minutos 5 minutos 2 3 Tiempo de demora Salir del Modo de Programación Alerta de Audio Recorrido Alerta visual 6 7 8 9 Sensibilidad de PIR Corte alto Corte bajo Tiempo de aumento Tiempo de atenuación Ajuste de nivel de luz Modo de pérdida de energía Modo de...

Page 16: ...de haber un tiempo de demora de hasta 30 minutos después de haber detectado el último movimiento Para verificar el funcionamiento adecuado configure los conmutadores 2 y 3 en Apagado para iniciar el modo de prueba Aléjese de la vista del sensor Las luces deben apagarse en aproximadamente 10 segundos 2 Verifique que el sensor esté montado al menos a seis pies 2 metros de distancia de cualquier disp...

Reviews: