INSTALLING THE SWITCH

DLM Slim Switches support two installation methods: surface mount or wall-box mount.

NOTE: 

Before mounting, the battery protection tab should be removed. 

Surface Mount:

Surface mounting requires use of a Legrand radiant

®

 wall plate (not included). The adhesive pad is 

suitable for mounting to multiple materials including drywall, metal, wood, glass, and some plastics.

1.  Press and jiggle the wall box screws from the rear to remove them from the switch.

2.  Use a Phillips head screwdriver to remove the grounding conductor at rear (no grounding is 

needed for surface mount switches).

3.  Peel the adhesive protector off of the rear of the switch.

4.  Press the switch firmly into the mounting surface and hold pressure for 5 seconds.

5.  Hook the radiant plate on the upper plate mount bracket, then press the bottom of the plate 

into the switch to snap on the plate.

For 

surface mounting in multi-gang applications

, snap-off side alignment wings are available to assist in proper alignment.

1.  Press and jiggle the wall box screws from the rear to remove them from the switches.

2.  Use a Phillips head screwdriver to remove the grounding conductor at rear of each switch.

3.  Twist/cut to remove only the inner wing(s) from each switch in the gang. Do 

not

 remove the alignment wings that will be on the 

outer left and right edges. So, for example, in a three gang application, remove the right alignment wing from the left switch,both 

wings  from the middle switch, and the left wing from the right switch, as shown below.

4.  Peel the adhesive protector off of the rear of the switch.

5.  Install with each switch in contact with the adjacent switch(es). After the first switch has been installed by pressing and holding for 

5 seconds, place the next switch at approximately a 45 degree angle (so that the alignment wings contact), and rotate the switch 

onto the wall, keeping the wings in contact as you do, and pressing for 5 seconds. Continue with any additional switches.

6.  Install an appropriately-sized multi-gang Radiant plate. (i.e. 3 switches needs a 3-gang, etc).

Wall box mount:

Wall box mounting allows for use of any standard decora-sized wall plate (not included). If 

using any plate other than a Legrand radiant wall plate, the top and bottom radiant mount 

wings should be removed from the switch. 

1.  Connect ground wire if installing next to Class 1 power. If not, there is no need to 

connect the ground wire (install in compliance with applicable codes).

2.  Twist/cut to remove side alignment wings. If not using a radiant wall plate, also remove 

the top and bottom wings).

3.  Use included screws to secure switch to wall box.

4.  Install wall plate per manufacturer instructions.

Alignment

Wings

Top/Bottom 

Wings

(for radiant 

wall plates)

Leave top/bottom 

wings if using a 

radiant wall plate

Remove top/bottom 

wings if using any 

other wall plate

Example of 3 gang installation with alignment wings removed

Summary of Contents for Wattstopper LMSW-610-S

Page 1: ...ified NOTE Installation shall be in accordance with all applicable regulations local and NEC codes Once paired to a wireless room controller or wireless bridge adjustment via the DLM Configuration App or LMCS 100 may be required to meet the local energy code where installed The DLM Wireless Slim Switches are wireless battery powered wall switches intended for operation with wireless room controlle...

Page 2: ...le in a three gang application remove the right alignment wing from the left switch both wings from the middle switch and the left wing from the right switch as shown below 4 Peel the adhesive protector off of the rear of the switch 5 Install with each switch in contact with the adjacent switch es After the first switch has been installed by pressing and holding for 5 seconds place the next switch...

Page 3: ...ming Ballast LED Driver etc Load Examples any relay A Switched etc B Class 1 Dimming Class 2 also available LMSW 622 S Wireless Slim Switch HYBRID ROOM CONNECTION WITH WIRED LIGHTING CONTROL AND DLM SHADING Distance Recommendations 60 max between LMSW 6xx S and mobile device 60 max between LMSW 6xx S and room controller or bridge 10 minimum and 100 maximum between LMBR 650 and room controller or b...

Page 4: ...For each device the load will toggle during step 3 and its config LED will turn solid green 4 Exit PtP mode From any device press the Config button 3 times After a few seconds the LED on each Room controller switch or sensor currently in PtP mode will flash either white or a red green blue sequence and reboot leaving the default network and migrating to the new network Then the LED on the room con...

Page 5: ...n three minutes the LMBC 650 will exit PtP mode 1 Enter PtP mode on the LMBC 650 Using a pointed tool press the Config button three times within three seconds until the LED on the LMBC 650 flashes green 2 Enter PtP mode on the LMSW 6xx S Press the Config button right side of Legrand badge three times As with the wireless bridge the LED on the switch will flash green 3 Pair the LMSW 6xx S Press the...

Page 6: ...t Press Default Hold Button 1 All Lighting Loads Toggle On Off Toggle Ramp Rocker 1 Up All Lighting Loads Send to 100 Raise Rocker1 Down All Lighting Loads Send to Off Lower Button 2 All Lighting Loads Toggle On Off Toggle Ramp Rocker 2 Up All Lighting Loads Send to 100 Raise Rocker 2 Down All Lighting Loads Send to Off Lower Toggle Ramp Button press actions will toggle loads between minimum and m...

Page 7: ...ddle on the wireless switch The LED will switch to the other color and stay lit for one second and then resume blinking red Each time you press and hold the paddle or button it will cycle to the next option Blue The button or paddle is bound to the load Red The button or paddle is not bound to the load Step 3 Exit Push n Learn Press and hold the Config button until the red LED turns OFF approximat...

Page 8: ...s been tested and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference ...