LEGRAND WattStopper DW-100 Installation Instructions Manual Download Page 3

Fixed Time Delay

(DIP 1 ON & 2 OFF)

High 

(DIP #4 OFF)

Walk-Through
Mode

(DIP #3 ON)

The DW sensor turns the load OFF 3 minutes after the
a rea is initially occupied, if no motion is dete c ted afte r
the first 30 seconds. If motion continues beyond the
f i rst 30 seconds, the set time delay applies.

Alerts

The DW can provide audible alerts as a warning befo re the load turns OFF.

D e fault setting. Suita b le for most applica t i o n s .

PIR Sensitivity Adjustment

The DW sensor co n sta n t ly monito rs the co n t ro l led environment and
a u to m a t i ca l ly adjusts the PIR to avoid common ambient conditions that ca n
cause false detections, while providing maximum cove rage. 

Time delays of 5, 

1 5

( d e fault), or 30 minutes are

a va i l a b le. See DIP SWITCH SETTINGS for info r m a t i o n .

SmartSet™ auto
adjust time delay
and Test Mode

R e co rds typical occupancy patterns. Using this histo r y
(which is co n sta n t ly updated), it chooses an optimal
time delay from 7 minutes (if the space is usually
va cant) up to 30 minutes (if the space gets heavy
usage). SmartSet behavior starts immediate ly, and is
refined co n t i n u a l ly as history is co l le c te d .

A Te st Mode with a short time delay of 5 seconds is set
when DIP switches 1 & 2 are OFF. It ca n ce l s
a u to m a t i ca l ly after five minutes, or when you set a
f i xed time delay. To re start Te st Mode, change the time
delay setting to any fixed amount and then return it to
the Auto

/ Te st setting.

R e d u ces sensitivity by approx i m a te ly 50%. Useful in
cases where the PIR is detecting movement outside of
the desired area (also consider masking the lens) and
w h e re heat sources cause unnece ssary activa t i o n .

Low, 50%

(DIP #4 ON)

No Alerts

" W h i st les" twice, at one minute and at 30 seco n d s
b e fo re turning OFF load. “Chirps” 10 seconds befo re
turning OFF load. “Beeps” three times 10 seco n d s
b e fo re the load goes OFF for Wa l k - T h ro u g h .

Audible Alerts

(DIP #7 ON)

No warnings prov i d e d .

Walk-Through

The Wa l k - T h rough mode shortens the time delay to re d u ce the amount of time
the load is ON after a brief moment of occ u p a n c y, such as returning to an office
to pick up a fo rg o t ten item then immediate ly ex i t i n g .

No Walk-Through

Wa l k - T h rough mode disable d .

Summary of Contents for WattStopper DW-100

Page 1: ...ballast HorsepowerRating each relay 1 6 HP 120VAC Time Delay Adjustment 5 to 30 minutes Walk Through Mode 3 minutes if no activity after 30 sec Test Mode 5 sec at initial power up or DIP switch reset...

Page 2: ...oad ON The relays are programmed independently for either Auto ON or Manual ON In either mode the load can be turned ON or OFF using the ON OFF button Load turns ON and OFFautomatically based on occup...

Page 3: ...to 30 minutes if the space gets heavy usage SmartSet behavior starts immediately and is refined continually as history is collected A Test Mode with a short time delay of 5 seconds is set when DIP sw...

Page 4: ...Trigger Mode The DW sensor has 4 occupancy trigger options set with DIP switches 5 and 6 Determine the appropriate option using the Trigger matrix In the Trigger Mode DIP switch setting table in order...

Page 5: ...metalbracket M a tchthem up with the holes in the wall box and tighten 4 Turn the circuit breaker ON Wait one minute then push the ON OFF button for each load and the lights will turn ON 5 Test and ad...

Page 6: ...sonic PIR Lens DIP SWITCH SETTINGS Call 800 879 8585 for Technical Support Ultrasonic Cones Ultrasonic Sensitivity Adjustment Trimpot Button Hinges Tabs DW 200 shown DW 100 has a single button and the...

Page 7: ...together the top sides of the buttonassembly Gently pull it away from the unit When the adjustments arecompleted replace the button cap by inserting its hinges into the tabs on the main unit and then...

Page 8: ...ASP 422 Blank cover plate for 2 gang box ASP 432 Switch option cover plate for 2 gang box Lights do not turn OFF 1 There can be up to a 30 minute time delay after the last motion is detected To verify...

Reviews: