background image

Wattstopper

 

®

Power Pack
Bloc d’alimentation
Fuente de Energia

Installation Instructions • Instructions d’Installation • Instrucciones de Instalación

No: 24567 – 08/16  rev. 1

Catalog Numbers • Les Numéros de Catalogue • Números de Catálogo: BZ-200/BZ-250/BZ-250-347

Country of Origin: Made in China • Pays d’origine: Fabriqué en Chine • País de origen: Hecho en China

Models ending in -U are BAA and TAA compliant (Product produced in the U.S.)

SPECIFICATIONS

Voltages
 

BZ-200, BZ-250 ................120—277 VAC, 50/60 Hz, single phase

 BZ-250-347 ......................120—347 VAC, 50/60 Hz, single phase
Load Requirements
 Ballast/ELV/MLV/Incandescent/LED
 

BZ-200, BZ-250......................................20 A @ 120—277 VAC

 BZ-250-347 ............................................16 A @ 120—347 VAC
 E-Ballast/CFL .............................................16 A @ 120—277 VAC
 Motor
 

BZ-200, BZ-250 ....................................1 HP @ 120—240 VAC

 BZ-250-347 .........................................1/4 HP @120—347 VAC
 

Plug Load

 

(BZ-200, BZ-250) ............................................20 A @ 120 VAC

 (BZ-250-347) ...................................................15 A @ 120 VAC
Class 2 Output
 

BZ-200 (w/relay connected) ........................225 mA @ 24 VDC

 

BZ-250, BZ-250-347 ....................................225 mA @ 24 VDC

Low Voltage Input, Control ON  ............................................ 5—30 VDC
Operating Temperature .................................. -4°—131 °F (-20—55 °C)
Storage Temperature .................................... -40°—176 °F (-40—80 °C)

UL/C-UL Listed

DESCRIPTION AND OPERATION

The BZ-2xx series of power packs are the foundation for any low 

voltage lighting control system. The BZ-2xx series supplies low 

voltage power to occupancy sensors and other control devices, 

switching line voltage in response to signals from control devices. 

The BZ-2xx series of power packs attaches to existing junction 

boxes or mounts into fixture wiring trays.
Low voltage wiring should use at least 22-gauge wire. High voltage 

connections should be appropriately sized for the breaker and load. 

Always check local building codes. After initial wiring is complete, 

check wiring diagrams to verify the power pack is wired correctly. 

Improper wiring can cause damage to the power pack, lighting 

system, occupancy sensors, and other control devices.

Auto/Manual Mode Switch 

BZ-250, BZ-250-347 only
Sélecteur de mode Auto/

Manuel BZ-250, BZ-250-347 

uniquement
Interruptor deslizante de  

encendido automático/manual  

BZ -250/ BZ- 250-347 

solamente

INSTALLATION

Installation Notes

1.  * Refer to occupancy sensor data sheet to determine 

maximum number of sensors. Power pack mA output is 

225mA.

2.  Power packs should be installed in accordance with state, 

local and national electrical codes and requirements.

3.  Power packs are designed to attach to existing or new 

electrical enclosures with 1/2 inch knockouts.

4.  Most applications require UL listed, 18-22 AWG, 3-conductor, 

Class 2 cable for low voltage wiring. For plenum return 

ceilings, use UL listed plenum-approved cables.

5.  The BZ-2xx is a Class 2 Output Power Supply, suitable for 

parallel interconnection of up to 4 units maximum. This power 

pack is UL Listed for Interconnection of Power Sources in 

accordance with National Electric Code.

NOTE: 

The BZ series uses an AC power relay and is not 

typically suited for high-impedance DC or dry-contact 

applications.

WARNING:

 TURN THE POWER OFF AT THE 

CIRCUIT BREAKER BEFORE WIRING.

WIRING

Connect wires as shown in the following wiring diagrams, or as 

shown in the BI-LEVEL CONTROL section.

Low Voltage Wires

Control Output

Common

+24VDC

Neutral

Hot

White

Black

Red

Blac

k

Power Pack

Blue

Sensor

Ceiling/Wall

24VDC

Any

Red

Red

Fixture

BZ-200

**Ground

*To 

Additional

Sensor(s)

** BZ-200 Power Pack 

must be grounded to 

ensure signal integrity,

not for safety ground.

Optional 

Local Off 

Switch

Wiring for one BZ-200

http://waterheatertimer.org/Safe-electric-wiring.html

Summary of Contents for Wattstopper BZ-2 Series

Page 1: ... initial wiring is complete check wiring diagrams to verify the power pack is wired correctly Improper wiring can cause damage to the power pack lighting system occupancy sensors and other control devices Auto Manual Mode Switch BZ 250 BZ 250 347 only Sélecteur de mode Auto Manuel BZ 250 BZ 250 347 uniquement Interruptor deslizante de encendido automático manual BZ 250 BZ 250 347 solamente INSTALL...

Page 2: ...d OFF automatically using an occupancy sensor input The BZ 250 and BZ 250 347 provide additional functionality allowing for low voltage input control from a timer panel or BAS input and manually from an optional low voltage momentary switch See the section on Low Voltage Inputs for details Auto ON Manual ON Slide Switch BZ 250 BZ 250 347 only Use the Mode Switch to select either the Auto ON mode o...

Page 3: ... 250 347 only This input is for a low voltage momentary switch Applying 5 30 VDC momentary input changes the relay to the opposite state This overrides Control ON Hold ON and Hold OFF inputs Red Red Red Common 24VDC Control Output Brown Black Grey Orange Red Blue Red Hot Neutral Black White Hot Neutral Black White MANUAL ON BZ 250 B AUTO ON BZ 250 A Cap Cap Brown Black Grey Orange Red Blue Cap Cap...

Page 4: ...ntinuously the relay is closed load ON TROUBLESHOOTING The lights came ON automatically after I deliberately turned them OFF for a presentation The BZ 2xx is set for the Auto ON Mode and the occupancy sensor time delay expired The BZ 2xx reverted to Auto ON and then motion was detected Consider increasing occupancy sensor sensitivity and or time delay Generate more motion during presentations The ...

Page 5: ...Load Rating Ballast A 20 20 16 Incandescent A 20 20 16 Motor hp 1 1 1 4 Plug Load 20 A 120 240 VAC 20 A 120 240 VAC 15A 120 240 VAC Output 24 VDC 225 mA w relay connected 24 VDC 225 mA 24 VDC 225 mA Auto Manual ON Slide Switch No Yes Yes Control Inputs Control ON Yes Yes Yes Hold ON No Yes Yes Hold OFF No Yes Yes Momentary Input Manual ON OFF No Yes Yes Override Button Yes Yes Yes Power Loss Mode ...

Page 6: ... classe 2 pour bloc d alimentation est 225mA 2 Les blocs d alimentation doivent être installés conformément aux codes de règlementation électrique et exigences régionaux et nationaux 3 Les blocs d alimentation sont conçus pour être raccordés à des boîtes électriques neuves ou déjà existantes dotés de débouchures de 12 7 mm 0 5 po 4 Dans le cas d un câblage à faible tension la plupart des applicati...

Page 7: ...to ON Manuel ON BZ 250 BZ 250 347 uniquement Utilisez le commutateur de mode pour sélectionner soit le mode MARCHE automatique soit le mode MARCHE manuelle Le mode de réglage de l interrupteur est pris en compte dans les deux secondes MARCHE automatique interrupteur de mode vers le HAUT par défaut L entrée de détecteur de présence l entrée maintien de l état MARCHE et l entrée de l interrupteur mo...

Page 8: ...r les signaux de l interrupteur momentané basse tension L application d une tension de 5 30 V c c au niveau de l entrée momentanée entraîne une inversion de l état du relais Elle neutralise les entrées MARCHE de régulation maintien de l état MARCHE et maintien de l état ARRÊT RÉGULATION À DEUX NIVEAUX Le schéma sur la droite vous montre comment configurer les BZ 250 pour obtenir une régulation de ...

Page 9: ...ES pour une présentation Le BZ 2xx est réglé sur le mode MARCHE automatique et la temporisation du détecteur de présence s est écoulée Le BZ 2xx est revenu sur MARCHE automatique et des mouvements ont été détectés Envisagez d augmenter la sensibilité et ou la temporisation du détecteur de présence Créez davantage de mouvements durant les présentations La charge ne s ACTIVE pas lors de la détection...

Page 10: ... Incandescence A 20 20 16 Moteur HP 1 1 1 4 Prise de courant 20 A 120 240 V c a 20 A 120 240 V c a 15 A 120 240 V c a Sortie 24 V c c 225 mA avec connexion relais 24 V c c 225 mA 24 V c c 225 mA Commutateur à glissière MARCHE automatique manuelle Non Oui Oui Entrées de régulation Contrôle ACTIVÉE Oui Oui Oui Maintien de l état MARCHE Non Oui Oui Maintien de l ARRÊT Non Oui Oui Entrée momentanée MA...

Page 11: ...ase 2 ideal para interconexión paralela de hasta 4 unidades como máximo Esta fuente de energía está certificada por UL para la interconexión de fuentes de suministro eléctrico según el Código Eléctrico Nacional NOTA La serie BZ usa un relé de suministro eléctrico de CA y por lo general no es adecuado para CC de alta impedancia ni para aplicacione ADVERTENCIA DESCONECTE LA ALIMENTACIÓN EN EL DISYUN...

Page 12: ...ruptor deslizante de ENCENDIDO automático manual BZ 250 BZ 250 347 solamente Use el Interruptor de modo para seleccionar el modo de ENCENDIDO automático o el modo de ENCENDIDO manual El modo de ajuste del interruptor surtirá efecto en dos segundos ENCENDIDO automático Interruptor de modo hacia ARRIBA predeterminado La entrada del sensor de ocupación la entrada de Mantener ENCENDIDO y la entrada de...

Page 13: ...a entrada está prevista para un interruptor momentáneo de bajo voltaje La aplicación de una entrada momentánea de 5 a 30 VCC cambia el relé al estado opuesto Anula las entradas del Control ENCENDIDO Mantener ENCENDIDO y Mantener APAGADO CONTROL DE DOS NIVELES El diagrama de la derecha muestra cómo configurar la BZ 250 para proporcionar un control de iluminación de dos niveles con las funciones de ...

Page 14: ...una presentación La BZ 2xx está configurada para el Modo de ENCENDIDO automático y expiró el retardo de tiempo del sensor de ocupación La BZ 2xx se revirtió a ENCENDIDO automático y luego se detectó movimiento Considere aumentar la sensibilidad del sensor de ocupación y o el retardo de tiempo Genere más movimiento durante las presentaciones La carga no se ENCIENDE con la detección de ocupación El ...

Page 15: ...Incandescente A 20 20 16 Motor hp 1 1 1 4 Cargas comunes con alimentación de CA 20 A 120 VCA 20 A 120 VCA 15A 120 VCA Salida 24 VCC 225 mA con relé conectado 24 VCC 225 mA 24 VCC 225 mA Interruptor deslizante de ENCENDIDO automático manual No Sí Sí Entradas de control Control ENCENDIDO Sí Sí Sí Mantener ENCENDIDO No Sí Sí Posponer No Sí Sí Entrada momentánea ENCENDIDO APAGADO manual No Sí Sí Botón...

Page 16: ...éfauts de matériaux et de fabrication pour une période de cinq 5 ans Wattstopper ne peut être tenu responsable de tout dommage consécutif causé par ou lié à l utilisation ou à la performance de ce produit ou tout autre dommage indirect lié à la perte de propriété de revenus ou de profits ou aux coûts d enlèvement d installation ou de réinstallation Wattstopper garantiza que sus productos están lib...

Reviews: