Trimod HE
U
ser manual
33
5.5
POWER ON/OFF menu
When the UPS is on, it is possible to access a menu called POWER ON/OFF by pressing the ON/OFF button for less than
0,5 seconds.
The choices that can be made in this menu are the following:
L1 phase (**)
Press the ENTER key to access the submenu in which it is possible to choose whether to
turn phase L1 on or off independently of the others.
By pressing the ARROW UP/DOWN keys it is possible to choose the ON or the OFF value.
By pressing the ENTER key the value is confirmed; pressing the ESC key you leave the
submenu.
L2 phase (**)
Press the ENTER key to access the submenu in which it is possible to choose whether to
turn phase L2 on or off independently of the others.
By pressing the ARROW UP/DOWN keys it is possible to choose the ON or the OFF value.
By pressing the ENTER key the value is confirmed; pressing the ESC key you leave the
submenu.
L3 phase (**)
Press the ENTER key to access the submenu in which it is possible to choose whether to
turn phase L3 on or off independently of the others.
By pressing the ARROW UP/DOWN keys it is possible to choose the ON or the OFF value.
By pressing the ENTER key the value is confirmed; pressing the ESC key you leave the
submenu.
UPS
Press the ENTER key to accesss the submenu for shutting down the UPS.
By pressing the ENTER key again, the UPS shuts down; by pressing the ESC key you leave
the submenu.
Hot swap
Press the ENTER key to access a submenu to make the hot-swap substitution of the power
modules.
CAUTION
This operation is reserved to a skilled technician and it is possible only for MULTI CTRL
models
(**) Available with the Inverter set up with three phases independent only
5.6
Switching off the UPS
CAUTION
The shut down procedure must only be applied if the load is off or does not need powering by the UPS.
There are two possible ways to shut down the UPS.
It is possible to shut down the UPS from the POWER ON/OFF menu or it is possible to perform the following procedure:
1. Keep the ON/OFF key pressed for at least 2 seconds.
2. The display shows the text "Turn off the UPS?". Press the ENTER key.
3. Wait for the shut down operation to complete.
If a prolonged shutdown is planned, do as instructed in chapter 8.
5.7
Switching on the UPS
The operator can turn on the UPS by doing the following:
1. Press the ON/OFF key.
2. When the display shows the text "<ENTER> to confirm UPS turn ON”, press the ENTER key. If no operation is carried out
within 30 seconds, the UPS turns off.
If the display shows the message "WARNING: different UPS setup! <ENTER> to confirm UPS turn on”, the UPS setup is
different from the last power up. A skilled technican must check the UPS setup before confirming the power up.
3. Wait for the power up operations to complete. The load is only supplied when the bar with the text “UPS initialize...”
displayed reaches the end and the main screen appears.