Ju
ne
20
18
44 Legrand PDU User Guide
DPX2 Sensor Packages
A DPX2 sensor cable is shipped with a DPX2 sensor package. This cable is made up of one RJ-12
connector and one to three head connectors. You have to connect DPX2 sensor packages to the sensor
cable.
For more information on DPX2 sensor packages, access the Environmental Sensors and Actuators Guide
(or Online Help) on Raritan website's
Support page
(
Item
DPX2 sensor package
DPX2 sensor cable with one RJ-12
connector and three head connectors
The following procedure illustrates a DPX2 sensor cable with three head connectors. Your sensor cable may
have fewer head connectors.
Warning: If there are free head connectors between a DPX2 sensor cable's RJ-12 connector and the final
attached DPX2 sensor package, the sensor packages following the free head connector(s) on the same
cable do NOT work properly. Therefore, always occupy all head connectors prior to the final sensor
package with a DPX2 sensor package.
To connect DPX2 sensor packages to the Legrand PDU:
1. Connect a DPX2 sensor package to the first head connector of the DPX2 sensor cable.