30
Please add three-pole (3-pole) MCCB to distribu-
tion panel for UPS’s input. Do not connect any other
load to it.
Connect the phase cables to
X1 MAINS SUPPLY:
X1/L1 - X1/L2 - X1/L3
terminals, the neutral to
X1
MAINS SUPPLY: X1/N
terminal. Neutral connection
should be done directly from distribution neutral
bus to UPS neutral.
5.3.1.3
.
Auxiliary Supply Connection
If auxiliary supply exists, remove all bridges
.
When used, the residual current
earth leakage protection system must be common for the two AC inputs and in-
stalled upstream.
According to EN 62040-1, the user should place a warning label on the input distribu-
tion panel and the other primary power isolators, in order to prevent the risk of voltage
backfeed.
This label is sent with the Installation Manual. It indicates:
Risk Of Voltage Backfeed
• Isolate Uninterruptable Power Supply before working on this circuit.
• Then check for Hazardous Voltage between all terminals including the protective
earth (PE).
WARNING
WARNING
WARNING
EN
IT
FR
RISK OF BACKFEED
BACK FEED RISCHIO
RISQUE DE RETOUR DE TENSION
Before working on this circut
isotale Uninterruptible Power System (UPS),
Then check for hazardous Voltage between
all terminals includig the protective earth
(PE)
Prima di intervenire su questo circuito
isolare I’UPS dalla rete .
Controllare la prensenza di tensioni
pericolose tra tutti i terminali
Avant de travailler sur le circuit électrique
İsoler I’ alimentation sans interruption (ASI)
Puis vérifier s’ il y a présense de tension
dangereuse entre toutes les bornes incluat la
connexion de terre.
Electrical Characteristics - Bypass
Model (kVA)
10
15
20
30
40
60
Bypass frequency slew rate
2 Hz/s settable from 1 to 3 Hz/s
Bypass rated voltage
Nominal output voltage ±18% (settable)
Bypass rated frequency
50/60 Hz (selectable)
Bypass frequency tolerance
±3Hz
Table.6
WARNING
DE
RÜCKSPANNUNG RISIKO
Bevor Sie einen Eingriff am Grat
vornehmen trennen Sie die USV - Anlage
vom Netz.
Überprüfen Sie auf geharlichte spanunngen
zwischen den Anschlüssen und der
Shutzerde (PE).
..
..
Summary of Contents for KEOR T
Page 1: ...KEOR T Installation Manual LE07544AA ...
Page 2: ...2 KEOR T ENGLISH 6 EN ...
Page 5: ...5 KEOR T Installation Manual Battery Fast Fuses Installation Operating Manuals ...
Page 32: ...32 Figure 5 3 1 4 1 Keor T 10 30kVA 1x60pcs 7 9Ah BATTERY WIRING DIAGRAM ...
Page 34: ...34 Figure 5 3 1 4 3 Keor T 40 60kVA 2x60pcs 7 9Ah BATTERY WIRING DIAGRAM ...
Page 50: ...50 SEPARATED RECTIFIER AND BYPASS INPUTS ...
Page 51: ...51 KEOR T Installation Manual COMMON RECTIFIER AND BYPASS INPUTS ...