![LEGRAND KEOR T EVO Installation & Operation Manual Download Page 15](http://html.mh-extra.com/html/legrand/keor-t-evo/keor-t-evo_installation-and-operation-manual_1871511015.webp)
13
KEOR T EVO
Installa
tion & Oper
ation M
anual
5. Requirement
5.2.
Placement
This product meets the safety requirements for devices to be operated in restricted access locations according to EN
60950-1 safety standard, which states that the owner should guarantee the following:
• Access to the equipment can only be gained by service persons or by users who have been instructed about the
reasons for the restrictions applied to the location and about any precautions that shall be taken and,
• Access is through the use of a tool or lock and key, or other means of security and is controlled by the authority
responsible for the location.
• UPS is not designed for outdoor application.
• The equipment and the batteries should not be exposed to direct sunlight or placed near to a heat source.
• Recommended operating temperature and humidity values are listed on the Appendix-1 Technical Specifications.
• Avoid dusty environments or areas where dust of conductive or corrosive materials is present.
• The connection and the circuit breakers are at the front of UPS. Leave access at the front of the UPS for maintenance.
(Refer to Figure.4.2-4)
• Air outlets of the UPS are at the front, back sides. Leave access at the front side, back side and from both lateral sides
for battery replacement. (Refer to Figure.5.2-1, 5.2-2, 5.2-3 and 5.2-4)
• Recommended environmental humidity condition is between 20-95% (non-condensing).
The UPS must be placed and stand in a vertical position throughout the transportation.
Use suitable equipment to remove the UPS from the pallet.
The equipment shall be packed properly during transportation. Therefore it is
recommended to keep the original package for future need.
All packing material must be recycled in compliance with the laws in force in the
country where the system is installed.
5.1.
Transportation
Environment Requirement
Model (kVA)
10
15
20
Max. dissipation at no load
(W)
144
150
204
(BTU)
491
511
696
Max. dissipation at full load
(W)
578
798
1053
(BTU)
1971
2722
3592
Storage temperatures
-25/+55 °C (-13/131 °F) (15-25 °C for maximum battery life)
Working temperature
0/40 °C (32/104 °F) (15-25 °C for maximum battery life)
Maximum relative humidity
95% max. without condensation
Maximum altitude without derating
1.000 m (3.300 ft)
Degree of protection
IP 20 (other IP as option)
Colour cabinet
RAL 7016@enclosure RAL 9005@front door metal
Table.1
Summary of Contents for KEOR T EVO
Page 1: ...KEOR T EVO 10 15 20 KVA Installation Operation Manual LE10507AA ...
Page 2: ...LE10507AA KEOR T EVO ...
Page 24: ...22 Figure 6 3 1 3 Figure 6 3 1 4 Power Cables Path Communication Cables Path ...
Page 30: ...28 Figure 6 3 1 4 1 KEOR T EVO 10 1x24pcs 9Ah BATTERY WIRING DIAGRAM ...
Page 32: ...30 Figure 6 3 1 4 3 KEOR T EVO 10 1x24pcs 9Ah BATTERY WIRING DIAGRAM ...
Page 76: ...74 SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT ...
Page 82: ...Notes ...
Page 83: ......