16
Installation Parameters
Model (kVA)
10
15
20
Phase in/out
3Ph+N+PE / 3Ph+N+PB
Rated output apparent power (kVA)
10
15
20
Rated output active power (kW)
9
13,5
18
Rated input current (A) at 400V nominal input voltage
14
21
28
Maximum input current (A) at 358V input v full load + battery charging
18
26
36
Rated bypass current (A) at 400V nominal input voltage
15
22
29
Maximum bypass current (A) at 400V, 125% overload 10 min
19
28
36
Inverter output current @ 400V (A)
15
22
29
Maximum Inverter output current (A) at 400V, 125% overload 10 min
18
27
36
Overload tolerated by the inverter (with mains power present) (kW)
10 min
12,5
18,75
-
8 min
-
-
25
1 min
15
22.5
30
Recommended Protection Devices - Rectifier/Mains Supply -*
D curve circuit breaker (A) (3 or 4-pole according neutral system)
20
25
32
GG fuse (A)
20
25
32
Recommended Protection Devices – General Bypass/Auxiliary Mains Supply –*
D curve circuit breaker (A) (3 or 4 pole according neutral system)
20
25
32
Maximum I2t supported by the bypass (A2s) (10ms)
6700
11200
15000
Icc max (A)
1200
1500
1700
Protection Devices – Battery Fast Fuse –
Ferrule style high speed fuses and with indicating striker
(High Speed FWP Bussmann Fuse 22x58mm 690VAC (IEC)) (A)
63
63
63
Recommended Protection Devices – Output –
C curve circuit breaker (A) (3 or 4 pole according neutral system)
≤3
≤4
B curve circuit breaker (A) (3 or 4 pole according neutral system)
≤6
≤8
Maximum inverter short circuit current for 50 ms: IK1=IK2=IK3 =IF
2.1xIn
Min-Max. Cable Cross-Section for Terminals**
Rectifier (mm²)
2.5 – 10
4 – 10
6 – 10
General Bypass (mm²)
2.5 – 10
4 – 10
6 – 10
Battery (+/-/N) (mm²)
2.5 – 10
4 – 10
6 – 10
Output (mm²)
2.5 – 10
4 – 10
6 – 10
Neutral (mm²)
4 – 10
6 – 10
10
Protective Earth/Bonding
Recommended cross section for ground wire
at least half of the section of cable phases AND
shall comply with the standards of the country
(for example NFC 15100 in France).
Leakage Current Protection ***
Minimum 300 mA delayed (Type-B). When
used, the residual current earth leakage
protection system must be common for the
two AC inputs (common & auxiliary mains) and
installed upstream.
Table.2
Summary of Contents for KEOR T EVO
Page 1: ...KEOR T EVO 10 15 20 KVA Installation Operation Manual LE10507AA ...
Page 2: ...LE10507AA KEOR T EVO ...
Page 24: ...22 Figure 6 3 1 3 Figure 6 3 1 4 Power Cables Path Communication Cables Path ...
Page 30: ...28 Figure 6 3 1 4 1 KEOR T EVO 10 1x24pcs 9Ah BATTERY WIRING DIAGRAM ...
Page 32: ...30 Figure 6 3 1 4 3 KEOR T EVO 10 1x24pcs 9Ah BATTERY WIRING DIAGRAM ...
Page 76: ...74 SEPARATED RECTIFIER AND BYPASS INPUTS FOR SINGLE UPS UNIT ...
Page 82: ...Notes ...
Page 83: ......