UPS user manual
Manuel de l'utilisateur de l'UPS
Utilizzo dell’UPS
54
OMD10074 REV. C
Alarm
A53
FIRMWARE ERROR
Description
The controller has detected an incompatibility in the control software.
Possible
causes
The software update was not performed properly.
Solutions
1. Contact our Technical Support Service.
Alarm
A54
CAN ERROR
Description Internal
error.
Possible
causes
Microcontroller communication problems.
Solutions
1. Contact our Technical Support Service.
Alarm
A55
PAR CABLE DISC
Description
Parallel cable doesn't communicate.
Possible
causes
Parallel cable disconnected or damaged.
Solutions
1. Check the connection of cable
2. Contact our Technical Support Service.
Alarm
A56
MAINS UNBALANCE
Description
The rectifier input voltage is unbalanced.
Possible
causes
Problems on the LV or MV distribution network
Defect of the measuring circuit
Solutions
1. Check the input voltage
2. Contact our Technical Support Service.
Alarm
A63
START SEQ BLOCK
Description
During the UPS start-up a failure prevented the proper execution of the
sequence.
Possible
causes
Control devices in wrong position or operated improperly.
Possible internal fault.
Solutions
1. Make sure the position of the control devices (isolators, selectors)
is as specified in the procedures (see “Installation and start-up”
section).
2. If the alarm persists, contact our Technical Support Service.
Summary of Contents for KEOR HP 100kVA
Page 55: ...UPS user manual Manuel de l utilisateur de l UPS Utilizzo dell UPS OMD10074 REV C 55 FRANÇAIS ...
Page 85: ...UPS user manual Manuel de l utilisateur de l UPS Utilizzo dell UPS OMD10074 REV C 85 ...
Page 87: ...UPS user manual Manuel de l utilisateur de l UPS Utilizzo dell UPS OMD10074 REV C 87 ...
Page 136: ...UPS user manual Manuel de l utilisateur de l UPS Utilizzo dell UPS 136 OMD10074 REV C ...