68
7 Technical specifications
3 101 73
3 101 74
General characteristics
Nominal power (VA)
5000
6000
Active Power (W)
5000
6000
Technology
on-line, double conversion, VFI-SS-111
Waveform
sinusoidal
Bypass
internal automatic bypass
external maintenance bypass (optional)
Transfer time AC to DC
0 ms
Input characteristics
Input connection
Terminal strips
Rated input voltage
230 V
Range of input voltage
from 176 V to 280 V at full load
Rated input frequency
50 / 60 Hz ± 5 %
Maximum input current
27.5 A
33 A
Total harmonic distortion
of the input current
THDi < 3%
Input power factor
≥ 0.99 (with full linear load)
Number of input phases
Single-phase
Output characteristics
Outlets
(8) 10A,
IEC 320-C13
+
(2) 16A
IEC 320-C19
+
terminal strips
Rated output voltage
230 V ± 1%
adjustable to 200/208/220/230/240 V
Rated output frequency
50 / 60 Hz ± 0,1%
Crest factor
3:1
Summary of Contents for DAKER DK Plus 3 101 73
Page 10: ...10 3 2 2 Onduleur armoire batteries option 3 Installation Phase 1 Phase 2 ...
Page 12: ...12 3 Installation Phase 5 Phase 6 ...
Page 38: ...38 ...
Page 46: ...46 3 2 2 UPS battery cabinet optional 3 Installation Step 1 Step 2 ...
Page 48: ...48 3 Installation Step 5 Step 6 ...
Page 74: ...74 ...
Page 82: ...82 3 2 2 UPS armadio batterie opzionale Fase 1 Fase 2 3 Installazione ...
Page 84: ...84 Fase 5 Fase 6 3 Installazione ...
Page 110: ...110 ...
Page 118: ...118 118 3 2 2 USV Batterieschrank Optional 3 Installation Schritt 1 Schritt 2 ...
Page 120: ...120 3 Installation Schritt 5 Schritt 6 ...
Page 146: ...146 ...
Page 154: ...154 154 3 2 2 SAI armario de la batería opcional 3 Instalación Paso 1 Paso 2 ...
Page 156: ...156 3 Instalación Paso 5 Paso 6 ...
Page 182: ...182 ...
Page 190: ...190 190 3 2 2 ИБП батарейный модуль опциональный 3 Монтаж Шаг 1 Шаг 2 ...
Page 192: ...192 3 Монтаж Шаг 5 Шаг 6 ...
Page 218: ...218 Notes ...
Page 219: ...219 Manuel d installation ...