14
AC INPUT
Input Voltage range
160V-280V
Max Input Current
4.6Arms Max.
Nominal Input Frequency
50Hz/60Hz±10%
Input Power Factor
> 0.85
Input Phases
Single phase
DC OUTPUT
Nominal DC Output Voltage
273Vdc±3Vdc (No Load)
Nominal DC Output Current
2,5A (5A max)
Nominal Output Power
1000W Max
AC-DC conversion efficiency
>0,7 at full load
Power Up Time
< 75ms
Line Regulation
≤ 1% (No Load)
Ripple
~ ± 5V
Noise
~ ± 3V
ENVIRONMENT
Operating temperature range
0°C ~ 40°C
Cooling
Forced air ventilation by DC fan
Relative Humidity
10% ~ 90% (without condensation)
DIMENSIONS
UNIT Dimensions(WxLxH)mm
166 x 282 x 86
UNIT Net Weight (Kgs)
3.2
STANDARD COMPLIANCE
Certification
CE
Safety
IEC 60950-1
EMC
EN 61000-6-4, IEC 61000-3-2, IEC 61000-3-3,
EN 61000-6-2 (EN 61000-4-2, EN 61000-4-3,
EN 61000-4-4, EN 61000-4-5, EN 61000-4-6,
EN 61000-4-8, EN 61000-4-11)
WARNING : This is a product for commercial
and industrial area.In a different environment-
installation restrictions or additional measures
may be needed to prevent disturbances
5 Warranty
The guarantee conditions may vary depending on the country where the battery charger is sold
so please check with your local Legrand sale representative for validity and duration.
4 Specifications
Summary of Contents for Battery Charger 240V
Page 1: ...Part LE07976AB 12 15 01 GF Chargeur de batterie 240V Manuel d installation Installation manual...
Page 33: ...33...
Page 34: ...34...
Page 35: ......