11 / 14 

 

EMS CX

3

 - Signalling Auxiliary Contact 

(CA + SD) 

 

Cat. N°: 

4 149 29 

 

 

 

6. SYSTEM ARCHITECTURES 

(continued)

 

6.2 Supervised system (Computer Supervisory System)

 (continued)

 

6.2.1 Supervised system with local addressing (through the track wheel)

 (continued)

 

Consequences of the local addressing mode 

(through the track wheel)

. Each device of the system must be addressed. 
. Addresses available: from 1 to 9 
. Address 0 not permitted 
It is possible to assign to several devices the same address with the purpose of grouping different functions, because they are related to the 
same electrical circuit. For example, it is possible to assign the same address to a signalling auxiliary module (cat. no 4 149 29), a universal 
control module (cat. no 4 149 32), a measuring module, and so on. In this way on the EMS CX

3

 display or in a supervision system the grouped 

function 

will be displayed as a unique “device” with all grouped functions. 

[

Refer to the scheme hereunder]

 

Note: In this configuration the Modbus address of an EMS CX

3

 module device or group of modules (several functions) is obtained considering 

the address of the interface Modbus/EMS CX

3

 Interface as tenth and the address of a device or group of function as unit (e.g. Interface address 

1 = 10 and device address = 5 

 Modbus address = 15) 

 

Consequences for the system architecture: 

-

 

for 1 IP/Modbus gateway (cat. no 0 046 89): 

o

 

up to 81 Modbus address 

o

 

mandatory limit of max. 9 Modbus/EMS CX

3

 interfaces or max. 1000 m of Modbus cable (cable Belden 9842, Belden 3106A or 

equivalent). 

-

 

for 1 Modbus/EMS CX

3

 Interface (cat. no 4 149 40): 

o

 

up to 30 EMS CX

3

 modules (ex. 30 devices grouped per functions with addresses from1 to 9) 

Note: with local addressing, the Modbus/EMS CX

3

 interface, does the automatic detection of modules (characteristics, functions, 

configuration...) 

 
 

 

Technical data sheet: F02334EN/02 

Updated: 07/11/2018 

Created: 20/07/2016 

 

 

 

Cat. no 0 046 89 

Summary of Contents for 4 149 29

Page 1: ...c module CA SD indicates contacts position open or closed and fault tripping of Legrand modular associated device MCB RCBO RCCB or Remote trip head IS Symbol 2 RANGE Cat n 4 149 29 electronic auxiliary contact CA fault signalling SD Width module 8 8 mm width 3 OVERALL DIMENSIONS 4 PREPARATION CONNECTION Fixing On symmetric rail EN IEC 60715 or DIN 35 rail Operating positions Vertical Horizontal Up...

Page 2: ... auxiliary ref 4 062 5x 6x or 4 149 29 List of allowed associations Particular rules With MCB s 1 5 modules per pole width if a remote tripping auxiliary Cat nos 4 062 76 78 80 82 84 86 87 is already mounted on this kind of device only 1 module width signalling auxiliaries Cat nos 4 062 64 66 can be added In this set up the module signalling auxiliaries will not operate Nothing changes for the oth...

Page 3: ...e plastic protection cover of the backside communication ports on the EMS CX3 module must be keep on 4 PREPARATION CONNECTION continued Data connection EMS CX3 modules inter connection continued Via specific communication rails cat nos 4 149 01 02 03 Allow data transmission between the different EMS CX3 modules This type of connection is recommended when there are several EMS CX3 modules on the sa...

Page 4: ...ords allow to connect EMS CX3 module on a row and to connect two rows 5 GENERAL CHARACTERISTICS Front face marking By permanent ink pad printing red line and laser marking Lateral side marking By laser left side Standard and programming information right side installing and traceability information Technical data sheet F02334EN 02 Updated 07 11 2018 Created 20 07 2016 Function name CA auxiliary co...

Page 5: ...linking No function Steady pressing the multifunction button longer than 20 sec Total reset any firmware updates are preserved green Slow blinking System process is running Wait until the Led turns steady Fast blinking pressing the multifunction button for 10 sec put in Stand by the EMS CX3 module no remote action and communication available Steady System OK connection is running orange Slow blink...

Page 6: ...tate Command 4 149 31 Is sufficient to configure the module locally or remotely as Slave Note association can only be of type 1 to 1 1 event and 1 action modules already associated cannot be used for other associations all the configuring procedure will be done with the Configuration Software available online for free For more details refer to the Installation Manual of EMS CX3 Configuration softw...

Page 7: ...EC EN 60695 2 12 glow wire test at 960 C Classification UL 94 IECEN 60695 11 10 V1 Ambient operating temperature Min 25 C Max 70 C Ambient storage temperature Min 40 C Max 70 C Protection Index Protection index of terminals against direct contacts IP2X IEC EN 60529 Protection index of terminals against solid and liquid bodies wired device IP 20 IEC EN 60529 Protection index of the front face again...

Page 8: ...are required Installation can be done without the intervention of a System Integrator Programming procedure For EMS CX3 modules which need some mandatory through to lateral DIP switch of each EMS CX3 modules see Module configuration Addressing procedure For all EMS CX3 modules mandatory through the track wheel located on the top upper face of each EMS CX3 modules Marked from 0 to 9 in order to loc...

Page 9: ...r EMS CX3 modules which need some possible through the lateral DIP switch of each EMS CX3 modules see Module configuration Addressing procedure It is not necessary to address the EMS CX3 modules The track wheel must be left in default position 0 All the addressing configuring procedure will be done with the Configuration Software available online for free With remote addressing the software does t...

Page 10: ... everywhere in the EMS CX3 bus 6 2 Supervised system Computer Supervisory System Supervised system System to be used through a Computer Supervisory System to remotely read data from the EMS CX3 devices and or do operations on these devices e g commands of a motor driven or contactor 6 2 1 Supervised system with local addressing through the track wheel Local addressing advantages No configuration s...

Page 11: ... function will be displayed as a unique device with all grouped functions Refer to the scheme hereunder Note In this configuration the Modbus address of an EMS CX3 module device or group of modules several functions is obtained considering the address of the interface Modbus EMS CX3 Interface as tenth and the address of a device or group of function as unit e g Interface address 1 10 and device ad...

Page 12: ...d some possible through the lateral DIP switch of each EMS CX3 modules see Module configuration Note via the configuration software it is possible to assign all the functions and characteristics of each EMS CX3 module Addressing procedure It is not necessary to address the EMS CX3 modules The track wheel must be left in default position 0 All the addressing configuring procedure will be done with ...

Page 13: ...no 4 149 40 o up to 30 EMS CX3 modules or grouped modules e g 30 devices grouped per functions with addresses from1 to 30 It is possible to assign to several devices the same address with the purpose of grouping different functions because they are related to the same electrical circuit For example it is possible to assign the same address to a signalling auxiliary module cat no 4 149 29 a univers...

Page 14: ... 2006 at the date of the publication of this document no element of the SVHC substance list updated on 27 06 2018 is present in these products WEEE directive 2012 19 EU the sale of this product is subject to a contribution to eco organisations in each country responsible for managing end of life products in the field of application of the European Waste Electronic and Electrical Equipment Directiv...

Reviews: