17
Code
parameter
9005
Mode change mechanism: Allows the user to choose whether the changeover from intruder mode to
surveillance mode is performed by entering codes on the keypad (value 1) or by analysing the mode
selection input (value 0).
Example: Mode selection by entering codes on the keypad: 9005 e 1 e
9006
locking control: Operation with locking control (value 0) or with release control (value 1).
Example: Electric release connected to the locking control: 9006 e 1 e
9009
surveillance activation for the radio receivers: Enable (value 1) or disable (value 0) this function.
The green indicator light flashes when this option is enabled and the link with a radio receiver is broken.
Example: Disabling the radio surveillance function: 9009 e 0 e
9010
adding a wristband number to the surveillance chart: Adds the number stated to the list of
wristbands to be kept under surveillance. The chart may contain 50 numbers.
Example: Adding the number 123 to the list of wristbands to be kept under surveillance: 9010 e 123 e
9011
Deleting a wristband number from the surveillance chart: Removes the number stated from
the chart of numbers under surveillance. If the number to be removed is 0 then all the numbers are
deleted.
If there are no numbers in the chart then the system is open, i.e. detections from all the wristband
numbers are acknowledged.
Example: Deleting the number 123: 9011 e 123 e
Example: Deleting the chart: 9011 e 0 e
9012
Door contact: Using a normally closed (value 0) or normally open (value 1) door contact.
Example: Connecting a normally open door contact: 9012 e 1 e
9013
setting a time delay for the door contact: Period in seconds that the door contact is still considered
active following its return to the initial status. This period can be programmed for between 1 and 30
seconds. This period is equal to 5 seconds by default.
Example: 10-second time delay: 9013 e 10 e
9014
Immediate restart for the alarm: When this option is confirmed (value 1) an escape alarm can be
restarted immediately following acknowledgement of the alarm. Otherwise the wristband has to leave
the detection zone for at least 20 seconds before a new escape alarm is possible again from this
number.
Example: Immediate restart for authorised alarm: 9014 e 1 e