6 / 26
DX³ 4
-pole RCBO
6000 A/10 kA
Cat. N°(s) :
4 111 85, 86, 87, 88, 89 / 4 112 04, 05, 06, 07,
4 112 08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35,
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51,
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81
5. GENERAL CHARACTERISTICS
(continued)
Derating of RCBOs in the event of use with fluorescent tubes:
Electronic or ferromagnetic ballasts provide a high inrush current for a very short time. These currents are liable to cause tripping of the
RCBOs
.
The maximum number of ballasts per RCBOs stated by the lamp and ballast manufacturers in their catalogues should be taken into account
during installation.
Impact of height:
≤
2,000 m
3,000 m
4,000 m
5,000 m
Dielectric strength
3,500 V
2,500 V
2,000 V
1,500 V
Maximum operating voltage
400 V
400 V
400 V
400 V
Derating at 30°C
none
none
none
none
Dissipated power for the phase pole in In:
. B and C curve RCBOs, all types and all sensitivities
Derating of RCBOs depending on the ambient temperature:
. The nominal characteristics of a RCBO are modified depending on the ambient temperature which prevails in the cabinet or enclosure where
the RCBO is located.
. Reference temperature: 30°C in accordance with standard IEC/EN 60947
-2.
Ambient Temperature/In
In (A)
-
25℃
-
10℃
0℃
10℃
20℃
30℃
40℃
50℃
60℃
10
13
12
12
11
11
10
10
10
10
13
17
16
15
14
14
13
13
13
13
16
20
19
18
18
18
16
16
16
16
20
26
24
23
22
21
20
20
20
20
25
32
30
29
28
26
25
25
25
25
32
41
38
37
35
34
32
32
32
32
Association and coordination with upstream fuses:
. Three-phase network (+N) 400/415 V, in accordance with standard IEC 60947-2
. TT neutral earthing or TNS system
Upstream fuse
gG and aM types
Downstream
RCBO
≤20 A
25 A
32 A
40 A
50 A
63 A
80 A
100 A
125 A
160 A
DX³ 6000 A
B and C curves
≤13 A
100 kA
100 kA
100 kA
100 KA 100 KA 100 kA
100 kA
100 kA
100 kA
40 kA
16 A
-
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
40 kA
20 A
-
-
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
40 kA
25 A
-
-
-
100 kA
100 kA
100 kA
100 kA
100 kA
100 kA
40 kA
32 A
-
-
-
-
100 kA
100 kA
100 kA
100 kA
100 kA
40 kA
Rated current
10 A
13 A
16 A
20 A
25 A
32 A
Power (W)
4.7
5.7
8.9
9.3
10.4
12.3
Technical data sheet: F01315EN/03
Updated on: 30/05/2018
Created on: 27/05/11