DX³ 4
-pole RCBO
6000 A / 10 kA
Cat. N°(s) :
4 111 85, 86, 87, 88, 89 / 4 112 04, 05, 06, 07,
4 112 08, 23, 24, 25, 26, 27, 28, 29, 30, 31, 32, 33, 34, 35,
4 112 36, 37, 38, 39, 40, 41, 42, 44, 45, 46, 47, 49, 50, 51,
4 112 52 / 4 113 50, 56, 57, 59, 60, 61, 62, 80, 81
5. GENERAL CHARACTERISTICS
(continued)
Discrimination with upstream Moulded Case Circuit Breakers (MCCBs) , only for sensitivities 300mA and 1000mA :
. Discrimination limit with a voltage of 230 V ~ (Values in A)
Upstream MCCB
DPX 250 / DPX-H 250
Electronic
DPX / DPX-H
630 / 1250 / 1600
DMX³ 2500 / 4000
Downstream RCBO
40A
100A
160A
250A
160 to 4000A
DX³ 6000A
B and C curves
10A
T
T
T
T
T
13A
T
T
T
T
T
16A
T
T
T
T
T
20A
5
T
T
T
T
25A
4
T
T
T
T
32A
-
5
T
T
T
Upstream MCCB
DPX 250 ER AB
DPX 400 AB
Downstream RCBO
90A
130 to 240A
320 and 400A
DX³
6000A
B and C curves
10A
T
T
T
13A
T
T
T
16A
T
T
T
20A
T
T
T
25A
T
T
T
32A
5
T
T
T = Total discrimination