32
CONSTRUCTION SPECIFICATIONS
3 101 60
3 101 63
3 100 86
3 101 61
3 101 64
3 110 14
3 101 62
3 101 65
3 110 15
Electrical output characteristics (normal mode)
Output
1 x IEC C14
Rated output voltage (V)
230 ± 1%
Rated output frequency (Hz)
50 / 60 (synchronised with the input)
50 / 60 ± 1% (if not synchronised with the
input)
Rated output current (A)
3,5
4,4
6,6
Crest factor admitted on the output current
3,5:1
Total harmonic distortion of output voltage on
linear rated load
< 1%
Total harmonic distortion of output voltage on
non-linear rated load (PF=0,7)
< 3%
Overload capacity
200% for at least 2 seconds without automatic
bypass activation
150% for at least 5 seconds without automatic
bypass activation
100% for at least 10 seconds without automatic
bypass activation
Permitted applied load power factor range
PF 0,7-1
Efficiency
at 50% of the load
at 75% of the load
at 100% of the load
90,7%
92,3%
93,0%
91,7%
93,0%
93,3%
93,0%
93,5%
93,4%
Electrical output characteristics (battery mode)
Rated output voltage (V)
230 (adjustable in steps of 1V from 184V
to 255V using the software)
Rated output frequency (Hz)
50 / 60 ± 1%
Rated output frequency (Hz)
< 1%
Total harmonic distortion of output voltage
on linear rated load
< 3%
Total harmonic distortion of output voltage
on non-linear rated load (PF=0,7)
> 100% per 15 secondi
Overload capacity
PF 0,7-1
®
7 Technical data