Whad HE 800, 1000, 1500 VA
EN
33
CONSTRUCTION SPECIFICATIONS
3 101 60
3 101 63
3 100 86
3 101 61
3 101 64
3 110 14
3 101 62
3 101 65
3 110 15
Batteries and Battery Charger Characteristics
Rated battery voltage (V)
48
No. of batteries
4
Battery type
Maintenance-free sealed lead-acid (VRLA)
12Vdc – 5,4Ah
Recharge time up to 90% of the total charge
5-6 h depending on the discharge level reached
Average battery life
3-6 years depending on use and operating
temperature
Reserve notification (V)
42.7 - 45.3
(can be programmed by the user using the
software)
Minimum battery operation voltage (V)
38 – 42
(with automatic selection based on the applied
load, or programmable by the user using the
software)
Features
Signals and alarms
Multicolour status indicator, acoustic
notification
Communication ports
1 RS 232 port
Software
A free copy of the free software can be
downloaded from
http://www.ups. legrand.com
Protective devices
Electronics against overloads, short-circuit and
excessive battery discharge.
Operation stop due to end of autonomy.
In-rush limiter on start up.
Neutral correct connection sensor. Integrated
Backfeed Protection
Mechanical characteristics
Dimensions L x H x D (mm)
88 x 390 x 355
Net weight (kg)
12