LEGRAND 0 625 14 Manual Download Page 9

9/11

Technical data sheet: S000082102EN-1 

Updated: 08/10/2013 

Created: 08/10/2013

Cat. No(s): 0 625 14/24/54/64/74

Kickspot Self-testing/AutoDiag

self-contained emergency lighting unit 

4. USE (CONTINUED)

5. MAINTENANCE

n

 5.1 Routine maintenance

• Safety Regulations for Public Buildings (articles EL 18 and EC 13)

Routine  maintenance  of  self-contained  emergency  lighting  units  is 

mandatory in public buildings.

It  can  be  carried  out  in  accordance  with  the  provisions  of  standard 

NF C 71-830.

The user must ensure that the lighting units are regularly checked and 

serviced.

The  user  must  ensure  that  the  annual  maintenance  operations  are 

carried out by a qualified person.

After  every  annual  maintenance  operation,  the  qualified  person  must 

affix a new maintenance label and fill it in.

This  maintenance  label  (Cat.  No.  0  609  01)  must  be  affixed  to  each 

lighting  unit  in  a  position  where  it  can  be  seen,  and  marked  with  the 

date on which the unit is returned to service.

• Operation (article EC 14)

The emergency lighting must be set to standby state during operating 

periods.

The emergency lighting must be set to rest or off state when the normal 

lighting installation is switched off intentionally.

The use of a hard-wired remote control Cat No. 0 039 00 and keyswitch 

in accordance with wiring diagram 3.2 enables the units to be set to rest 

state at the same time as the normal lighting is switched off when the 

rooms or areas are not in use.

The user must regularly check the following:

Once a month:

- That the unit switches to operating position if the normal power supply 

fails, and that all the lights come on (operation must be strictly limited 

to the time required to carry out the visual check). These checks can be 

carried out by checking that the green self-test indicator is on on all the 

units in the installation.

- The effectiveness of the remote command to switch to rest position and 

the automatic return to standby position when the normal power supply 

is re-established.

Once every six months:

- At least one hour's standby power. These checks can be carried out by 

checking that the green self-test indicator is on on all the units in the 

installation.

n

 4.9 Operation of self-contained emergency li reinforced 

emergency light Cat. No. 0 625 54 with a remote control module Cat. 

No. 0 039 00 connected to a fire alarm control panel

Mains power 

supply

Fire alarm

Unit status

Emergency function

Present

Absent

Standby

Present

Present

Backup with flux 

dimming between 

 

45 lumens and  

120 lumens

Absent

Present or 

absent

Backup with flux 

dimming between 

 

45 lumens and  

120 lumens

Lighting unit

standby and

emergency

LEDs

Unit green

status LED

Yellow

fault LED

Summary of Contents for 0 625 14

Page 1: ...ng Self contained emergency lighting unit with LEDs used for evacuation in public buildings and work premises Cat Nos 0 625 14 24 54 74 or for background lighting Cat No 0 625 64 Conforming to standards 0 625 24 conforming to NF C 71 800 0 625 64 conforming to NF C 71 800 NF C 71 801 and UTE C 71 806 0 625 74 conforming to NF C 71 805 0 625 14 conforming to NF C 71 800 NF C 71 805 and UTE C 71 803...

Page 2: ... the support Ring Polycarbonate self extinguishing 850 C 30 s Self contained emergency lighting unit Polycarbonate self extinguishing 850 C 30 s Protective cover Polycarbonate self extinguishing 850 C 30 s Terminal block Polyamide self extinguishing 850 C 30 s Tab Polyamide 850 C 30 s Pads Polyamide 850 C 30 s Pictogram holder plate Polycarbonate self extinguishing 850 C 30 s only for self contain...

Page 3: ...it in the support Fully push in the tabs Swivel the unit only for evacuation lighting units Cat Nos 0 625 14 24 54 74 2 2 Connecting the wires to the terminal block REMOTE CONTROL Connection terminals no direction of connection with Legrand remote controls Terminal capacity 2 x 2 5 mm2 Insert the tabs in the unit Connect the terminal block to the unit N L 50 mm 10 Power supply Remote control CLICK...

Page 4: ...unit 2 Lock with a 1 4 turn 1 2 3 1 Connecting the mains power to the self contained units Art EC 12 3 of the safety regulations The branch supplying a unit must be joined upstream of the protection device and downstream of the normal lighting control device for the room or exit route where the unit is installed The polarity of the remote control may not be followed on this lighting unit if a Legr...

Page 5: ...maximum Important In the event of fire alarm activation remote control Cat No 0 039 00 memorises the alarm status for one hour to avoid accidentally setting the unit emergency lighting function to rest state emergency lighting units home lighting units emergency lighting units reinforced emergency lights if the main power supply fails again The red LED signals the fire alarm status If the fire ala...

Page 6: ...766 30 or Céliane Cat No 0 675 31 not supplied Optional remote control via keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Keyswitches cascaded Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Optional remote control via keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not sup...

Page 7: ...self testing display with LEDs AutoDiagTM self testing remote control Background lighting unit Background lighting unit Emergency lighting home lighting unit Reinforced emergency light Lighting power supply circuit The remote control power supply must be taken upstream of the normal lighting circuit protection devices It must not come from a protected auxiliary power supply 0 0 9 3 0 0 230 VA 50Hz...

Page 8: ...ery fault Electronic fault Green steady or flashing Yellow steady rapid flashing The time of the tests is set at the time the unit is first switched on The day of the test is chosen randomly in order to ensure that a minimum number of units are tested at the same time The time at which all the units are tested can be changed to the required time by simultaneously pressing the and buttons on the re...

Page 9: ...No 0 039 00 and keyswitch in accordance with wiring diagram 3 2 enables the units to be set to rest state at the same time as the normal lighting is switched off when the rooms or areas are not in use The user must regularly check the following Once a month That the unit switches to operating position if the normal power supply fails and that all the lights come on operation must be strictly limit...

Page 10: ...25 14 2 x 0 610 87 0 625 54 0 610 90 Ni Cd 1 5 Ah 2 4 V Cs 0 625 64 2 x 0 610 88 NiMH 2 2 Ah 2 4 V Cs 3 Disconnect the batteries from the unit and remove them Legrand distribution partners take back used lighting units and batteries When the batteries have been changed replace the maintenance label marking on it the date on which the unit was returned to service n 5 2 spare parts Batteries n 5 3 R...

Page 11: ... of NiMh batteries in self contained emergency lighting units EN 60 598 2 22 European standard Luminaires specific rules Luminaires for emergency lighting EN 60 598 1 European standard Luminaires The NF AEAS performance SATI mark certifies compliance with these standards NF 413 NF ENVIRONNEMENT Emergency lighting units The NF environnement mark certifies compliance with this standard EN 50172 Euro...

Reviews: