background image

5/11

Technical data sheet: S000082102EN-1 

Updated: 08/10/2013 

Created: 08/10/2013

Cat. No(s): 0 625 14/24/54/64/74

Kickspot Self-testing/AutoDiag

self-contained emergency lighting unit 

3. CONNECTION (CONTINUED)

 

3.2 Remote control for setting to rest state

Operation with Evacuation and/or Background lighting units in buildings 

open to the public that have neither sleeping accommodation nor a safe 

waiting area.

 

3.3 Connection for an installation in self-testing mode

3.3.1 Operation with [emergency lighting units + home lighting units], 

[emergency  lighting  units  +  reinforced  emergency  lights]  and  self-

contained  emergency  lighting  units  in  buildings  open  to  the  public 

having  sleeping  accommodation  (French  regulations)  and/or  safe 

waiting areas.

00

93

0

0

230 V

A

50Hz
15 mA

DBR

Remote control circuit 

breaker

Cat. No. 0 039 00

300 units maximum

Important:

In the event of fire alarm activation, remote control Cat. No. 0 039 00 memorises the 

alarm  status  for  one  hour  to  avoid  accidentally  setting  the  unit  emergency  lighting 

function to rest state [emergency lighting units + home lighting units], [emergency 

lighting units + reinforced emergency lights] if the main power supply fails again.

The red LED signals the fire alarm status.

If  the  fire  alarm  is  reset  too  soon  (<1  hour)  (tests,  false  alarm,  nuisance  tripping), 

deactivate the remote control alarm status by pressing the button 

00

93

0

0

230 V

A

50Hz
15 mA

DBR

Lighting 

circuit  

circuit 

breakers

(

*) 

Remot

con

tr

ol 

cir

cuit 

br

eakers

Fire alarm panel

Cat.  

No. 0 039 00

Normal 

lighting 

switch

(*) The  remote  control  power  supply 

must  be  taken  upstream  of  the 

normal  lighting  circuit  protection 

devices.

It  must  not  come  from  a  backed-up 

auxiliary power supply.

Normal 

lighting 

switch

[Emergency li 

 

home lighting units]

Sleeping areas

Non-sleeping areas

Evacuation lighting unit

Emergency lighting 

units + reinforced 

emergency lights

Summary of Contents for 0 625 14

Page 1: ...ng Self contained emergency lighting unit with LEDs used for evacuation in public buildings and work premises Cat Nos 0 625 14 24 54 74 or for background lighting Cat No 0 625 64 Conforming to standards 0 625 24 conforming to NF C 71 800 0 625 64 conforming to NF C 71 800 NF C 71 801 and UTE C 71 806 0 625 74 conforming to NF C 71 805 0 625 14 conforming to NF C 71 800 NF C 71 805 and UTE C 71 803...

Page 2: ... the support Ring Polycarbonate self extinguishing 850 C 30 s Self contained emergency lighting unit Polycarbonate self extinguishing 850 C 30 s Protective cover Polycarbonate self extinguishing 850 C 30 s Terminal block Polyamide self extinguishing 850 C 30 s Tab Polyamide 850 C 30 s Pads Polyamide 850 C 30 s Pictogram holder plate Polycarbonate self extinguishing 850 C 30 s only for self contain...

Page 3: ...it in the support Fully push in the tabs Swivel the unit only for evacuation lighting units Cat Nos 0 625 14 24 54 74 2 2 Connecting the wires to the terminal block REMOTE CONTROL Connection terminals no direction of connection with Legrand remote controls Terminal capacity 2 x 2 5 mm2 Insert the tabs in the unit Connect the terminal block to the unit N L 50 mm 10 Power supply Remote control CLICK...

Page 4: ...unit 2 Lock with a 1 4 turn 1 2 3 1 Connecting the mains power to the self contained units Art EC 12 3 of the safety regulations The branch supplying a unit must be joined upstream of the protection device and downstream of the normal lighting control device for the room or exit route where the unit is installed The polarity of the remote control may not be followed on this lighting unit if a Legr...

Page 5: ...maximum Important In the event of fire alarm activation remote control Cat No 0 039 00 memorises the alarm status for one hour to avoid accidentally setting the unit emergency lighting function to rest state emergency lighting units home lighting units emergency lighting units reinforced emergency lights if the main power supply fails again The red LED signals the fire alarm status If the fire ala...

Page 6: ...766 30 or Céliane Cat No 0 675 31 not supplied Optional remote control via keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Keyswitches cascaded Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not supplied Optional remote control via keyswitch Mosaic Cat No 0 766 30 or Céliane Cat No 0 675 31 not sup...

Page 7: ...self testing display with LEDs AutoDiagTM self testing remote control Background lighting unit Background lighting unit Emergency lighting home lighting unit Reinforced emergency light Lighting power supply circuit The remote control power supply must be taken upstream of the normal lighting circuit protection devices It must not come from a protected auxiliary power supply 0 0 9 3 0 0 230 VA 50Hz...

Page 8: ...ery fault Electronic fault Green steady or flashing Yellow steady rapid flashing The time of the tests is set at the time the unit is first switched on The day of the test is chosen randomly in order to ensure that a minimum number of units are tested at the same time The time at which all the units are tested can be changed to the required time by simultaneously pressing the and buttons on the re...

Page 9: ...No 0 039 00 and keyswitch in accordance with wiring diagram 3 2 enables the units to be set to rest state at the same time as the normal lighting is switched off when the rooms or areas are not in use The user must regularly check the following Once a month That the unit switches to operating position if the normal power supply fails and that all the lights come on operation must be strictly limit...

Page 10: ...25 14 2 x 0 610 87 0 625 54 0 610 90 Ni Cd 1 5 Ah 2 4 V Cs 0 625 64 2 x 0 610 88 NiMH 2 2 Ah 2 4 V Cs 3 Disconnect the batteries from the unit and remove them Legrand distribution partners take back used lighting units and batteries When the batteries have been changed replace the maintenance label marking on it the date on which the unit was returned to service n 5 2 spare parts Batteries n 5 3 R...

Page 11: ... of NiMh batteries in self contained emergency lighting units EN 60 598 2 22 European standard Luminaires specific rules Luminaires for emergency lighting EN 60 598 1 European standard Luminaires The NF AEAS performance SATI mark certifies compliance with these standards NF 413 NF ENVIRONNEMENT Emergency lighting units The NF environnement mark certifies compliance with this standard EN 50172 Euro...

Reviews: