Cat. No(s): 0 625 14/24/54/64/74
Kickspot Self-testing/AutoDiag
self-contained emergency lighting unit
3. CONNECTION (CONTINUED)
3.2 Remote control for setting to rest state
Operation with Evacuation and/or Background lighting units in buildings
open to the public that have neither sleeping accommodation nor a safe
waiting area.
3.3 Connection for an installation in self-testing mode
3.3.1 Operation with [emergency lighting units + home lighting units],
[emergency lighting units + reinforced emergency lights] and self-
contained emergency lighting units in buildings open to the public
having sleeping accommodation (French regulations) and/or safe
waiting areas.
00
93
0
0
230 V
A
50Hz
15 mA
DBR
Remote control circuit
breaker
Cat. No. 0 039 00
300 units maximum
Important:
In the event of fire alarm activation, remote control Cat. No. 0 039 00 memorises the
alarm status for one hour to avoid accidentally setting the unit emergency lighting
function to rest state [emergency lighting units + home lighting units], [emergency
lighting units + reinforced emergency lights] if the main power supply fails again.
The red LED signals the fire alarm status.
If the fire alarm is reset too soon (<1 hour) (tests, false alarm, nuisance tripping),
deactivate the remote control alarm status by pressing the button
00
93
0
0
230 V
A
50Hz
15 mA
DBR
Lighting
circuit
circuit
breakers
(
*)
Remot
e
con
tr
ol
cir
cuit
br
eakers
Fire alarm panel
Cat.
No. 0 039 00
Normal
lighting
switch
(*) The remote control power supply
must be taken upstream of the
normal lighting circuit protection
devices.
It must not come from a backed-up
auxiliary power supply.
Normal
lighting
switch
[Emergency li
home lighting units]
Sleeping areas
Non-sleeping areas
Evacuation lighting unit
Emergency lighting
units + reinforced
emergency lights