Microwave detector - DALI/DSI dimming

Cat. No(s): 0 489 55/56/57

CONTENTS

7. SETTINGS (CONTINUED)

Parameter

Default 

value

Value after 

initialisation

Range/

option

Description

Output channel modes

Switching only

-

-

-

Only the relay part is used

Switch and dim 

together

-

The 2 outputs are synchronised and go ON/OFF at the same time

Switch and dim 

separately

-

-

-

The 2 outputs are not synchronised and the DALI luminaire can be turned off 

without switching the relay output OFF

General parameters

LED operation 

test

Off

-

ON or Off

When this option is activated, a red LED on the sensor flashes when it detects 

movement. Use this function to check that the sensitivity levels are suitable.

Inhibit 

detection

No

-

Yes/No

Disables presence/absence detection so that the detector does not control 

switching, only dimming. Use this mode for light regulation without automatic 

control according to occupancy.

Timeout

20 minutes

-

0 to 99 

minutes

Once the detector is turned on, this value sets how long the lights will stay on once 

movement has ceased. Select 0 for a 10-second period (for commissioning only).

Manual timeout 

period

10 minutes

-

0 to 99 

minutes

When a manual operation occurs, either via the switch input or the infrared, it 

invokes the timeout period.
Example 1: a detector in presence mode has a detector timeout of 15 minutes and 

a manual timeout of 3 minutes. When the user leaves the room, they press the Off 

button. The sensor will revert to automatic mode after 3 minutes. Walking back into 

the room will turn the lights on.
Example 2: using the settings above, the user turns the lights off (say for a 

presentation) but stays in the room. Every time a movement is detected, the manual 

timeout period is re-triggered, but if it doesn’t pick up anything over a short period, 

the detector will revert to automatic mode. This means that the lights may come on 

inadvertently during the presentation, even if the occupants are still present during 

the manual timeout period, so adjust the timing carefully.

On sensitivity

8

9

1 (min) 

to 9 (max)

Sensitivity level for detecting movement when the detector is already on.

Off sensitivity

8

9

1 (min) 

to 9 (max)

Sensitivity level for detecting movement when the detector is off.

On delay

0 minutes

-

0 to 99 

minutes

The On delay allows the first channel to switch on after the second channel. 

A typical application for this would be when a detector is controlling lighting and air 

conditioning in an area. When the occupant is detected, the lighting will be turned 

on immediately, whereas the air conditioning may be turned on after 15 minutes. 

If the area is vacated before the detector times out, then the air conditioning will not 

have come on. The delay can be set for channel 1 only using this parameter.

Detection mode

Presence

-

Presence 

or absence

Presence mode allows the output to turn on when movement is detected and 

off when movement ceases. Absence mode allows the output to turn off when 

movement ceases, but must be manually turned on first.

Lux On level

999

145

1-950, 

999: 

OFF 

dimming 

regulation

Sets a minimum light level below which the PIR sensor is enabled, allowing the lights 

to be turned on by movement.

Note: The "Lux Off level" value must always be greater than the "Lux On level” value.

Summary of Contents for 0 489 55

Page 1: ...n outside row of luminaires whilst internal fittings are switched Providing absence detection for two separate channels Installing a maintained illuminance system with manual override controls for dimming This detector has an adjustable sensor head that allows the detection area to be optimised for the application All functionality is fully programmable using an infrared configurator 2 TECHNICAL C...

Page 2: ...arate electronic ballast 10 LED lamps with built in electronic ballast 4 CONNECTION CONTINUED Single channel dimming with manual dimming control Single channel dimming with manual dimming control Functions Switching the luminaire according to occupancy and maintaining a defined lighting level Override dimming and switching using a centre biased retractive switch Configured for presence detection T...

Page 3: ...aintaining a defined lighting level for the dimming channel Override dimming and switching using a centre biased retractive switch for the dimming channel only Configured for presence detection Turns on automatically when occupancy is detected Maintains the lighting level switching channel only Press and release the down button to turn off press and release the up button to turn back on dimming ch...

Page 4: ...itch on immediately Set the timeout to 10 seconds vacate the room or remain very still and wait for the load to switch off Check that the load switches on when movement is detected The unit is now ready for programming Remove metal locking clip from rear of unit Adjust head to required position Push clip into the position shown below to lock head To remove clip lever out with a small screwdriver 6...

Page 5: ...rameter you can select a time during which the lamps are not allowed to deviate from maximum dimming The unit counts the time and even remembers how long has elapsed in the event of a power failure To cancel the burn in function simply select a time of 0 Note that when the lamps are changed the burn in time should be set again 7 SETTINGS The detector functions are controlled by a number of paramet...

Page 6: ...ng back into the room will turn the lights on Example 2 using the settings above the user turns the lights off say for a presentation but stays in the room Every time a movement is detected the manual timeout period is re triggered but if it doesn t pick up anything over a short period the detector will revert to automatic mode This means that the lights may come on inadvertently during the presen...

Page 7: ... before the lights go out If at any time during the timed delay the Lux level position is reversed the process is cancelled A minimum time of approximately 15 seconds is defined for a value of 0 Dimming parameters Lux level for regulation 999 150 1 950 999 disabled Sets a target light level to be maintained by the lighting system Max value 99 0 to 99 Maximum dimming output level Min value 0 82 0 t...

Page 8: ...4 If the light level is often too low Increase and adjust the value of the Lux level for regulation parameter from 150 up to 200 Adjust the value of the following parameters Lux On Level Lux level for regulation 5 Lux Off Level Lux level for regulation x 1 5 Example Lux level for regulation 180 Lux On level 175 Lux Off level 270 Lux Off time 1 Min value 82 5 If the lighting loads never switch off ...

Page 9: ... NFC 15 100 Product standards NF EN 60730 1 Environmental standards European Directive 2012 19 EU WEEE Waste Electrical and Electronic Equipment European Directive 2011 65 EU and 2015 863 RoHS Restriction of Hazardous Substances Decrees and or regulations Public buildings workplace buildings high rise buildings RED Directive 2014 53 EU Sensitivity set to 80 Detector head position set to 40 2 6 m 6...

Reviews: