Technical data sheet: S000072383EN-2 

Updated: 17/10/2017 

Created: 04/10/2012

Catalogue number(s): 0 488 17

Corridor sensor - PIR

  9. PERFORMANCE

c

a

b

Height

m: 12

12

0

(PIR)

Sensitivity

Low (25%)

Sensitivity

Medium (50%)

a (m)

b (m)

c (m)

a (m)

b (m)

c (m)

Height (m)

2.5

7

10

3

8

14

3

3

7

10

3

8

14

3

3.5

9

10

3

12

14

3

4

10

8

3

13

9

3

Sensitivity

High (75%)

Sensitivity

Very high (100%)

a (m)

b (m)

c (m)

a (m)

b (m)

c (m)

Height (m)

2.5

10

16

3

16

24

3

3

10

16

3

16

24

3

3.5

14

16

3

17

24

3

4

15

10

3

18

14

3

  10. CARE

Keep the lens clean.

Clean the surface with a cloth.

Do not use acetone, tar-removing cleaning agents or trichloroethylene.

Resistant to the following products:  - Hexane (EN 60669-1) 

- Methylated spirit 

- Soapy water 

- Diluted ammonia 

- Bleach diluted to 10% 

- Window-cleaning products 

Caution: 

Always test before using other special cleaning products.

  11. STANDARDS

Directive: CE
Installation standards: NFC 15-100
Product standards: IEC 60669-2-1
Environmental standards: 

-  European directive 2002/96/EC: 

WEEE (Waste Electrical and Electronic Equipment)

-  European Directive 2002/95/EC: 

RoHS (Restriction of Hazardous Substances)

- Decrees and/or regulations:  Public buildings 

Workplace buildings 

High-rise buildings

PROBLEM

CAUSES

SOLUTIONS

Lighting stays on when there is no-one present

Some sources of interference, such as air 

currents, vibrations and radiators, can cause 

unintended operation

1-  Reduce the sensitivity level
2-  If the interference continues, using the 

configuration tool, go into the Detection 

system parameters, select Maintain and then 

choose PIR

3-  If the interference still continues, move 

the sensor away from the source(s) of 

interference

Lighting does not switch off during the day 

when there is an adequate level of natural light

Regulation function not active
Light level threshold set too high
Light contribution is too high

Activate the regulation function
Reduce the light level threshold
Check that the sensor is positioned correctly in 

relation to the window
Decrease the power of the luminaires

Lighting switches off when there are people 

present and the natural light level is not 

adequate (darkness)

Time delay too short
Detection sensitivity too low
Light level threshold too low

Increase the time delay
10 to 1 minutes is recommended for work areas
Increase the sensitivity
Move the sensor closer to the work area
Increase the threshold

  12. TROUBLESHOOTING

Summary of Contents for 0 488 17

Page 1: ...re 20 C to 70 C 2 TECHNICAL CHARACTERISTICS continued Cover removed CONTENTS Page 1 Use 1 2 Technical characteristics 1 3 Dimensions 2 4 Connection 2 5 Installation 4 6 Removal 4 7 Operation 5 8 Settings 6 9 Performance 7 10 Care 7 11 Standards and approvals 7 12 Troubleshooting 7 230 V 2000 W 8 5 A 1000 VA 4 3 A 10x 2x36 W 4 3 A 500 VA 2 1 A 1000 VA 4 3 A 500 VA 2 1 A I max 2A 110 V 1000 W 500 VA...

Page 2: ...3 DIMENSIONS Without protective cover 4 CONNECTION Number of terminals 4 Type of terminals automatic Terminal capacity 2 x 2 5 mm2 Stripping length 8 mm 4 1 Wiring with auxiliary control 4 2 Wiring without auxiliary control Auto on Auto off Wiring 65 93 Ø 1 2 2 50 73 Ø 1 2 2 52 With protective cover 100 m max 8 5 A max 8 5 A max 36 56 ...

Page 3: ... 17 10 2017 Created 04 10 2012 Catalogue number s 0 488 17 Corridor sensor PIR 4 CONNECTION continued 4 3 Wiring for several loads connected in parallel 4 4 Wiring for a single load connected in parallel 100 m max L1 PB L2 LN S1 S2 SN PB L S1 S2 SN 100 m max ...

Page 4: ... Technical data sheet S000072383EN 2 Updated 17 10 2017 Created 04 10 2012 Catalogue number s 0 488 17 Corridor sensor PIR 5 INSTALLATION 6 REMOVAL 1 2 3 1 2 50 Ø 68 Ø 68 Ø 65 Ø 65 Ø 120 Ø 120 0 488 75 0 3 to 20 mm ...

Page 5: ...the end of the time delay or when the light level threshold has been reached Auto ON OFF mode The load will be switched on and off automatically Option It is possible to control the sensor by infrared remote control using Cat Nos 0 882 00 01 20 31 32 33 7 1 More than one sensor and more than one load L1 OFF L2 OFF Ln OFF S1 OFF S2 OFF Sn OFF 1 s L1 ON L2 ON Ln ON S1 ON S2 ON Sn ON L1 ON L2 ON Ln O...

Page 6: ...via a manual switch 8 SETTINGS continued 8 1 Detection parameters continued Detection system Initial detection The load is switched on as soon as the first detection occurs if the natural light level is below the light level threshold Maintain The load remains active if another presence is detected Restart In manual mode After switch off any new detection within a 30 second period triggers an auto...

Page 7: ...us Substances Decrees and or regulations Public buildings Workplace buildings High rise buildings PROBLEM CAUSES SOLUTIONS Lighting stays on when there is no one present Some sources of interference such as air currents vibrations and radiators can cause unintended operation 1 Reduce the sensitivity level 2 If the interference continues using the configuration tool go into the Detection system par...

Reviews: