Arrow Board Operators Manual V1.2          

 

 Page 8 of 12 

 

 

 

At a voltage drop of 11 volts or less, the system will enter the non-directional warning state 
(mode D) indicated on both the sign and the AC4S controller. 
At a further voltage drop to 10.4 volts the lamp modules will cease to illuminate completely. 
(System enters low voltage shut down) until power is restored to 11.6 volts or above, when 
the sign will again turn on and resume normal function. 

 

 

The current used by the Arrow Board lamps is constantly monitored by a microcontroller on 
the Arrow Board computer, if the current is detected to be outside the range of normal 
operation, an error is generated and the user is informed on the AC4S controller and the 
Arrow Board is shut down. 

 

Troubleshooting 

 

The AC4S Arrow Controller and Arrow Board are similar in operation to a computer network. The 
control switches on the Arrow Controller are the master controls and communicate with the 
computer in the Arrow board, which in turn responds to given commands. The unit also has a light 
sensor mounted at the bottom of the Arrow Board 
 

 

If the LED display on the controller does not light, check the isolator switch to ensure it is in the 
ON or RESET position.  
 

 

In the event of a failure of any kind, the sign will enter an error state as indicated by a large red 

X

 

on the controller screen and the sign will stop operating.  
 
Note: No change of mode will take place to the flashing of the sign, it will stop.   

 

 

If the unit fails to operate, first check that the Isolator is switched ON (RESET), this isolator is also 
a circuit breaker and will automatically switch off, should the wiring to the Arrow Board be 
damaged, or there is a failure in one of the Arrow Board modules. 

 

 

To reset the system, switch the isolator to OFF, wait 10 seconds and turn ON (RESET). 

 

 

The system automatically dims the lamps in response to a light sensor mounted at the bottom of 
the Arrow Board, if the lamps appear dull during daylight hours; clean the light sensor with a 
damp cloth. 

 

 

In the case where one or more of the lamp units fail to light as normal, or if any of the lamps 
appear as unusually bright or dim, first check the lamp units are clean and that the apparent 
difference is not due to dirt on the LEDs or an obstruction in the shroud.  

 
 

 

 

 

 

 

Summary of Contents for LDC ABC

Page 1: ...ors Manual V1 2 Page 1 of 12 LDC EQUIPMENT LDC AB C Size Arrow Board Installation and Instruction Manual Single Sided Arrow Board Controller Quality Management System Approved to AS NZS ISO 9001 2008...

Page 2: ...duction 3 LDC AB C Arrow Board 4 Sign Positioning 5 Inside the Control Box 5 Arrow Board Operation 6 Operation 6 Controller Operation Modes for Arrow Board 7 Fail Safe Techniques Employed 7 Troublesho...

Page 3: ...tor that provides for disconnection of power in the event that service is required or in the event of an overload The controller screen displays the current operation mode and a real time mimic of the...

Page 4: ...Page 4 of 12 LDC AB C Arrow Board AC4S Controller Single and Double sided Arrow Boards Isolator switch Optional Beacon Switch OLED Display Screen Control Knob LED Lamps with Visors Light Sensor Solar...

Page 5: ...d Deploy the stabilising legs from their travelling position horizontal to their set up position vertical by pulling out the spring loaded leg locking pin and pivoting the leg 90 degrees until the loc...

Page 6: ...l knob so that the pointer points to the desired mode to be displayed on the sign The mode selected on the controller will be illuminated on the sign as viewed from the REAR of the vehicle When switch...

Page 7: ...ime what the sign is displaying During the normal operation of the system the AC4S controller communicates continually with the Arrow Board computer requesting the current status of the Arrow Board Sh...

Page 8: ...ght sensor mounted at the bottom of the Arrow Board If the LED display on the controller does not light check the isolator switch to ensure it is in the ON or RESET position In the event of a failure...

Page 9: ...ck the wiring from the battery to the controller for poor connections Replace the battery if necessary Lamp Fault One or more lamps have failed Visually check operation of lamps check lamp connections...

Page 10: ...ing the unit DO NOT USE THE EQUIPMENT FOR ANY OTHER PURPOSE THAN IT WAS INTENDED FOR Maintenance On a WEEKLY basis perform the following activities to ensure safe trouble free operation of the equipme...

Page 11: ...r replaced for a period of 12 months Any sign that has failed as a result of a traffic accident abuse or act of vandalism or incorrect use after delivery shall not be covered under warranty provisions...

Page 12: ...onal Warning Controls Power Isolation Switch Circuit Breaker Mode Selection Switch Rotary Encoder Mode Indication LEDs 4 LEDs Beacon operation Toggle Switch Lamp Brightness 625 cd Minimum 0 0 Axis 100...

Reviews: