Cnnection between MPS-8S units must be done by standar T568B ehernet cable. Maximum

connection distance for the entire bus 1000m (3280ft). In total, up to 8 MPS-8Z devices can 
be connected to each ZES-22.
The ACSI bus does not provide power to the equipment remotely, so each MPS-8Z 
microphone must have its own local source.
Each device has a priority selector inside the bus. Depending on the priority set, you will be 
allowed to occupy the channel when it is occupied by another device. The priority of the 

MPS 8Z matches the direction of the ACSI bus.  To set the ACSI address of the MPS 8Z, 
follow these steps:

Make sure the team has no word granted. The "CW" indicator will be off.

Press and hold the "CANCEL" button and the "MEM" button for at least 2 seconds.

Access to the address setting will be confirmed by flashing the "LINK" and "EMG" 
indicators. The configured bus address will be indicated by lighting the associated zone

memory indicator.

Press the memory selection button whose number corresponds to the desired 
address. Remember that the address matches the priority. The corresponding zone 
memory selection indicator will light up.

Press the "TALK" button to confirm, "CANCEL" to cancel the address change.

The unit will restart with the new bus address.

In case of "LINK", "FAULT" and "EMG" flash simultaneously when the MPS-8Z is started, 

there is an address conflict on the ACSI bus with this device. In this case, the address must 
be changed.

 1.4 

MPS-8Z Configuration

It is possible to configure MPS-8Z Paging Microphone according to several operation 
parameters. To access the configuration mode of the device, follow these steps:

Picture 6: MPS-8Z ports