LCN-GBL

Installation guide 

Local Control Network

1

®

PIR motion  detector and light sensor for the I-connection in glass design

The LCN-GBL is an indoor PIR motion detector with integrated light sensor in the LCN-GT 
series design. Optionally a humidity sensor  LCN-EFS can be inserted. 

The PIR motion detector works on the passive infrared principal. The changes in human 
body heat radiation are detected. 

The integrated light sensor covers a very large measuring range of 5 decades 

(1-100.000Lx).  The  measured  value  can  be  used  for  light  dependant  control  or  for  a 
constant light regulation. 

Included in delivery

Connection

The LCN-GBL is suitable for connecting to the I-ports from   
LCN-UPx, -SH, -SHS, -LD and -HU Serial number 120C05 
(Dec. 2008) or later. The connecting cable to the LCN module 
can be optionally extended up to 50 m with an LCN-IV - see 

LCN-GBL, mounting plate, 2 screws (3,2x25) 
& I-connecting cable.

 

”TDi  connection  from  periphery”  on  our  homepage 
(

www.LCN.de / downloads

).

Summary of Contents for LCN-GBL

Page 1: ...iation are detected The integrated light sensor covers a very large measuring range of 5 decades 1 100 000Lx The measured value can be used for light dependant control or for a constant light regulati...

Page 2: ...LCN PRO The configuration of the light value is carried out in regulator 2 and or with the 4 thresholds see also page 4 For the last mentioned the R2 Var must be copied into the T Var The measured lig...

Page 3: ...has ended the LCN GBL triggers off the release command If the movement lasts longer the release command will come approx 8 seconds after the last movement Detecting range When needed four LCN GBL s ca...

Page 4: ...be used Additionally a binary sensor LCN B3I can be connected to the same LCN module The LCN BT4H BU4L 4 way binary sensors cannot always be used on the same module check the key mapping first thumb r...

Page 5: ...jury caused by a fallen off glass plate After screwing the installing frame on to the wall and plugging in the I connection the sensor housing from the LCN GBLis simply snapped on to the installing fr...

Page 6: ...nly possible with modules using firmware 160A Oct 2012 or later To do this the jumper bridge must first be removed before inserting A maximum of one further LCN EFS may only be operated on one module...

Page 7: ...sor LCN EFS Air humidity triggering 1 accuracy at 20 80 air humidity 4 outside the given areas 6 Dew point resolution 0 1 C accuracy at 20 80 air humidity and 10 40 C environmental temperature 2 C Not...

Page 8: ...le debouncing time light sensor measurement spectrum measuring range accuracy installation operating temperature air humidity environmental conditions protection art resolution not needed over I conne...

Reviews: