4Use and Operation
User Manual
44
www.lbspower.com
Fault phenomenon
Possible reason
works normally, but the
computer system halted.
Meaning of fault symbol and buzzer status
LCD fault symbol
Buzzer status
Meaning
Fault
info.
page
(page
up or page
down by "
" button)
EPO
Long beep
UPS has emergency protection (if equipped with EPO
function), Bypass output and inverting output are all
closed.
P/N
I/O
ERR
Long beep
UPS work mode setting and actual wiring mismatch,
please check the mains and bypass wiring, and see if
the wiring matches the work mode setting.
SEQ
Long beep
UPS mains phase sequence abnormal. Please check if
the phase sequence of mains wiring is normal.
BMD
Long beep
UPS maintenance bypass fault, the inverter output is
closed.
Please
check
the
detection
port
of
maintenance bypass on rear plate is short circuit.
BUS
Long beep
The inner busbar voltage fault, the inverter output is
closed.
TMP
Long beep
UPS is over-temperature protected, the inverter
output is closed. Please check if cooling fan is
damaged or air vents are blocked.
OUT
Long beep
UPS output fault. Please check if the output of thr
UPS is short-circuit or overload.
BAT
Long beep
UPS battery fault, battery low-voltage or over-
voltage protection.
PRA
Long beep
The
parameter
setting
of
parallel
system
is
mismatching. Please check if the inverter voltage
mode or parallel mode of parallel system is
mismatching.