3Installation
19
www.lbspower.com
10kVA
15kVA
20/25kVA
33
mode
31
mode
11
mode
33
mode
31
mode
11
mode
33
mode
31
mode
11
mode
(U/V/W)
AC input neutral wire
(N)
4*1
10*1
10*1
6*1
16*1
16*1
10*1
16*1
16*1
Bypass input live wire
(U/V/W)
4*3
10*1
10*1
6*3
16*1
16*1
10*3
16*1
16*1
AC output live wire
(U/V/W)
4*3
10*1
10*1
6*3
16*1
16*1
10*3
16*1
16*1
AC output neutral wire
(N)
4*1
10*1
10*1
6*1
16*1
16*1
10*1
16*1
16*1
DC input (+/BATN/-)
6*3
6*3
6*3
10*3
10*3
10*3
10*3
10*3
10*3
Grounding wire (PE)
6*1
6*1
6*1
10*1
10*1
10*1
10*1
10*1
10*1
Contrast list between wires and wiring terminals
Wire cross-sectional area(unit: mm
2
)
Wiring terminal type
4
RV3.5-6
6
RV5.5-6
10
RNBS8-6
16
RNBS14-6
25
RNBS22-6
The equipped wires by our company are all passed the national standard or UL certification, the quality
is perfect and meets the requirements of safety standard. The above wire cross-sectional area is just
for the wiring reference of 5m, when the wire length exceeds 20, the cross-sectional area needs to
increase correspondingly.