Models S 1200, S 2400, S 4400, POU 3300, POU 3500
-
16
-
2.7.
Secondary Containment
As a precaution, it is recommended that the user of this equipment install a secondary
containment container for potential leaks. This container shall installed under the unit to catch
any leaks, be large enough to contain the volume of each particular unit – see table below.
These secondary containment devices should not interfere with access to the PCW or drain
fittings on the bottom of the unit and be designed for easy removal of the collected fluids.
Module
Minimum volume of
Secondary Containment (L)
S1200
1.10
S 2400
1.50
S 4400
2.75
POU 3300
1.50
POU 3500
2.75
As a final precaution, these secondary storage containers must have fluid detection and alarm
capabilities in order to prevent continuous leaks. This sensor must be installed at the lowest
point of the storage container, and notify the end user in the case of activation.