Installation may be made on a damp surface. Expansion joints shall 
be  provided  through  the  tile  work  from  all  construction  or  

expansion joints in the substrate. Follow ANSI specification A108.01-
3.7:  Requirements  for  Movement  Joints:  Preparations  by  Other 
Trades”  or  TCNA  detail  EJ-171  “Movement  joints-Vertical  & 
Horizontal”. Do not cover expansion joints with mortar. 
Typically  Linear  Drains  should  run  from  sill  plate  to  sill  plate  (the 

width of the shower) against a wall (see ES-B415LD Bonded Corner  
Placement). Alternatively they can also be placed in medial locations 
(see  ES-B415LD  Unbonded  Medial  Placement)  or  at  the  shower 

entrance.  In  all  locations  the  waste  line  for  standard  size 
LATICRETE

®

 Hydro Ban

®

 Linear Drains are in the center of the linear 

drain.  When  installed  against  a  wall  the  center  of  the  waste  line 
should  be  located  far  enough  away  from  the  sill  plate  to 
accommodate wall sheathing and finished tile  surface. For 1/2" (12 

mm)  wall  board  and  3/8"  (9  mm)  tile  the  center  of  the  waste  line 
should be located 2 1/4" (57 mm) out from the sill plate. 

Mortar Bed—Installation over  concrete

 (see ES-B415LD  Bonded 

Corner Placement and ES-B415LD Unbonded Medial) For a Bonded 
mortar  bed  over  concrete  installation,  before  placing  mortar,  apply  a 

slurry bond coat made from LATICRETE 254 Platinum or LATICRETE 
4237  Latex  Additive  mixed  with  LATICRETE  211  Powder.  While  the 
slurry bond coat is wet, spread LATICRETE 3701 Fortified Mortar Bed 

and compact well.  Bonded  mortar beds over concrete shall be 3/4"(19 
mm) minimum to 2"(50 mm) maximum. For an unbonded installation 
over  concrete  (see  ES-415LD  Unbonded  Medial)  a  cleavage 

membrane as specified in ANSI A108.02-3.8 should be used in place 
of the slurry bond coat.  The LATICRETE 3701 Fortified Mortar Bed 

should  be  reinforced  with  2"  x  2"  (50  x  50  mm)  reinforcing  mesh. 
Unbonded Mortar beds over concrete shall be 1-1/4"(32 mm) minimum 
to  2"(50  mm)  maximum.  In  both  Bonded  and  Unbonded  mortar  Bed 

installations  place  enough  LATICRETE  3701  Fortified  Mortar  Bed 
where the linear drain will be set to support the bottom and under the 
flanges  of  the  drain  trough.  Minimum  height  from  the  flange  to  the 
substrate should be 1-1/2" (37 mm). Make the connection to the waste 
line  when  the  drain  is  set  into  place  using  a  no  hub  connection  (not 

supplied),  see  installation  instructions  below.  Next  place  a  ribbon  of 
LATICRETE  3701  Fortified  Mortar  Bed  along  the  opposite  wall  to 
create a 1/4" (6 mm) per foot slope to the LATICRETE Linear Drain. Fill 

the  area  between  the  drain  and  the  walls  with  LATICRETE  3701 
Fortified Mortar Bed; screed and compact well. Mortar beds in excess 

of 2"(50 mm) thick shall be detailed by the architect per TCNA F112.  

Mortar Bed – Installation over Exterior Glue Plywood ( EGP)

 (see 

ES-415LD  EGP  Bonded  Corner  Placementl  and  ES-415LD  EGP 

Unbonded Medial Placement) 
For  a  bonded  mortar  bed  over  EGP  installation,  before  placing 
mortar, install a cleavage membrane as specified in ANSI A108.02-

3.8. Expanded metal lath (minimum 2.5 pounds (1.1 kg)/square yard 
(0.8 square meters) and complying with  ANSI  A108.02 3.6) is then 
nailed  or  stapled  to  the  subfloor  over  the  cleavage  membrane. 
Following the lath spread LATICRETE 3701 Fortified Mortar Bed and 
compact well. Bonded mortar beds over EGP shall be 3/4"(19 mm) 

minimum to 1 1/2"(38 mm) maximum. For an unbonded installation 
over EGP (see ES-415LD EGP Unbonded Medial Placement) install 
a  cleavage  membrane  as  specified  in  ANSI  A108.02-3.8  and  then 

spread  the  LATICRETE  3701  Fortified  Mortar  Bed.  In  both  bonded 
and  unbonded  mortar  bed  installations  place  enough  LATICRETE 

3701 Fortified Mortar Bed where the linear drain will be set to support 
the bottom and under the flanges of the drain trough. Minimum height 

from the flange to the substrate should be 1-1/2" (38 mm). Make the 
connection to the waste line when the drain is set into place using a 

no hub connection (not supplied). Next place a ribbon of LATICRETE 
3701 Fortified Mortar Bed along the opposite wall to create a 1/4" (6 
mm)  per  foot  slope  to  the  LATICRETE  Linear  Drain.  Fill  the  area 
between  the  drain  and  the  walls  with  LATICRETE  3701  Fortified 
Mortar Bed; screed and compact well. Mortar beds in excess of 2"(50 

mm) thick shall be detailed by the architect per TCNA F112.  

Installation Instructions (Fig. 1) 

1.

 

Connect  outlet  (D)  to  waste  pipe  (F)  via  2"(50  mm)  no  hub 

connection  using  a  rubber  coupling  (E)  (not  provided).  Note: 
outlet  section  (D)  is  3"(76  mm)  long  and  can  be  modified  for 

height  adjustment.  Grate  A  has  adjustable  feet  for  finer 
adjustment  (Minimum  tile  height  with  thin-set  is  3/8"(10  mm), 
maximum tile height is 3/4"(19 mm)). 

2.

 

Using  a  LATICRETE  3701  Fortified  Mortar  Bed  set  and  level 
channel (C)  

3.

 

Spread  LATICRETE  3701  Fortified  Mortar  Bed,  slope  1/4"  per 

foot (19mm per m) away from drain in a single plane. Note: tile 
height should finish 1/16"(1.5 mm) higher than grate height the 

tile in the Tile in Drain Grate. 

4.

 

When the mortar is dry install backer board per manufacturer’s 
instructions.  The  backer  board  will  sit  on  the  drain  flange  and 

mortar  (see  ES-B415LD  Bonded  Corner  Placement  or  ES-
B415LD EGP Bonded Corner Placement). 

5.

 

After  the  backer  board  has  been  installed  waterproof  the 

installation  using  LATICRETE  Hydro  Ban  per  instructions  in 
DS663.0  and  663.5.  The  stainless  steel  from  the  linear  drains 

needs  to  be  clean  and  free  of  any  grease,  dirt  or  fingerprints 
prior  to  coating  with  Hydro  Ban.  The  LATICRETE  Hydro  Ban 
should cover the metal flange on the linear drain trough to the 

top of the first radius and extend up the walls and over the entire 
mortar bed. If the gap between the linear drain flange and the 
wall  board  is  larger  than  1/8" (3  mm)  it  should  be  filled  with  a 
LATICRETE  Polymer  Modified  Thin-Set  e.g.  LATICRETE  254 
Platinum)  or  alternatively  use  6"  (150  mm)  wide  LATICRETE 

Waterproofing/Anti-Fracture  Fabric  imbedded  into  the 
LATICRETE  Hydro  Ban  around  four  sides  of  the  linear  drain 
overlapping  the  flange  and  the  LATICRETE  3701  Fortified 

Mortar  Bed.  Lap  LATICRETE  Waterproofing/Anti-Fractrure 
Fabric  and  LATICRETE  Hydro  Ban  liquid  up  the  wall  when 

adjacent  to  show¬er  wall  and  over  wall  board.  DO  NOT 
waterproof  the  inside  walls  and  bottom  of  the  linear  drain 
channels. 

6.

 

Take  measures  to  protect  grate (A)  prior  to  tiling.  Keeping  the 
grate (A) in the channel (C), thin-set and tile on the waterproof 
membrane.  Ensure  tile  allows  for  clearance  of  grate  (A) 

removal. Tile finishes 1/16"(1.5 mm) higher than grate or the tile 
in the Tile in Drain Grate.  

7.

 

If the grate has adjustable feet then adjust grate (A) height with 
adjustable feet (B) as needed. 

8.

 

When  installing  the  LATICRETE  Hydro  Ban  Linear  Tile  Drain 

Grate (A) will need to be primed with two coats of LATICRETE 
Hydro  Ban  prior  to  thin-setting  the  tile  into  the  top  grate.   The 
stainless steel from the linear drains needs to be clean and free 

of  any  grease,  dirt  or  fingerprints  prior  to  coating  with  Hydro 
Ban. 

9.

 

When  the  second  coat  of  LATICRETE  Hydro  Ban  is  dry  the 
installation  can  be  tiled  using  a  LATICRETE  polymer  fortified 