![Lasermet ICS-6 Instruction Manual Download Page 17](http://html.mh-extra.com/html/lasermet/ics-6/ics-6_instruction-manual_678408017.webp)
ICS-6 Instruction Manual
01000-53-000
Page 17 of 42
Issue 11 19 January 2021
Option 3
Two-way Illuminated Warning Sign
The first warning sign will come on when the ICS-6 mains switch is turned on. The first warning sign
will go off and the second warning sign will come on when the ‘Arm Laser’ button is pressed. Note
that in the case of the Lasermet Miniature Warning Sign, both indications are displayed in the same
unit.
Note. Terminal J8 on the ICS Interlock Board are for 24VDC signs only.
If there are a large number of signs the ICS-6 internal power supply may be insufficient. The
maximum total load that may be placed on the internal power supply is 4A, which includes any other
equipment being run from the 24V supply, such as door locks, shutters etc.
In such cases the signs may be run from a separate power supply. The mains input of this power
supply is connected to the L OUT and N OUT terminals of the mains terminal block J9. The PSU
output is fed through the sign control terminals to operate the signs. Please contact Lasermet for
suitable power supplies and assistance.